Skip to main content
HHS Author Manuscripts logoLink to HHS Author Manuscripts
. Author manuscript; available in PMC: 2017 May 1.
Published in final edited form as: J Occup Environ Hyg. 2016 May;13(5):356–371. doi: 10.1080/15459624.2015.1117617

Hexavalent Chromium and Isocyanate Exposures during Military Aircraft Painting under Crossflow Ventilation

James S Bennett 1,*, David A Marlow 1, Fariba Nourian 1, James Breay 2, Duane Hammond 1
PMCID: PMC4916860  NIHMSID: NIHMS795423  PMID: 26698920

Abstract

Exposure control systems performance was investigated in an aircraft painting hangar. The ability of the ventilation system and respiratory protection program to limit worker exposures was examined through air sampling during painting of F/A-18C/D strike fighter aircraft, in four field surveys. Air velocities were measured across the supply filter, exhaust filter, and hangar midplane under crossflow ventilation. Air sampling conducted during painting process phases (wipe-down, primer spraying, and topcoat spraying) encompassed volatile organic compounds, total particulate matter, Cr[VI], metals, nitroethane, and hexamethylene diisocyanate, for two worker groups: sprayers and sprayer helpers (“hosemen”). One of six methyl ethyl ketone and two of six methyl isobutyl ketone samples exceeded the short term exposure limits of 300 and 75 ppm, with means 57 ppm and 63 ppm, respectively. All 12 Cr[VI] 8-hr time-weighted averages exceeded the recommended exposure limit of 1 µg/m3, 11 out of 12 exceeded the permissible exposure limit of 5 µg/m3, and 7 out of 12 exceeded the threshold limit value of 10 µg/m3, with means 38 µg/m3 for sprayers and 8.3 µg/m3 for hosemen. Hexamethylene diisocyanate means were 5.95 µg/m3 for sprayers and 0.645 µg/m3 for hosemen. Total reactive isocyanate group—the total of monomer and oligomer as NCO group mass—showed six of 15 personal samples exceeded the United Kingdom Health and Safety Executive workplace exposure limit of 20 µg/m3, with means 50.9 µg/m3 for sprayers and 7.29 µg/m3 for hosemen. Several exposure limits were exceeded, reinforcing continued use of personal protective equipment. The supply rate, 94.4 m3/s (200,000 cfm), produced a velocity of 8.58 m/s (157 fpm) at the supply filter, while the exhaust rate, 68.7 m3/s (146,000 cfm), drew 1.34 m/s (264 fpm) at the exhaust filter. Midway between supply and exhaust locations, the velocity was 0.528 m/s (104 fpm). Supply rate exceeding exhaust rate created re-circulations, turbulence, and fugitive emissions, while wasting energy. Smoke releases showing more effective ventilation here than in other aircraft painting facilities carries technical feasibility relevance.

Keywords: Ventilation, hexavalent chromium, isocyanates, aircraft painting

INTRODUCTION

National Institute for Occupational Safety and Health (NIOSH) researchers investigated ventilation system performance—the effectiveness of contaminant removal and worker exposure control—in an aircraft paint finishing hangar. This topic addresses potentially hazardous chemicals, such as isocyanates and hexavalent chromium, present during painting of F/A-18C/D strike fighter aircraft. The appropriateness of the existing respiratory protection program was also evaluated.

Isocyanates are respiratory sensitizers and are one of the leading chemical causes of occupational asthma in the US and many other industrialized countries. Affected workers must take steps to eliminate exposure to prevent symptom progression, often by leaving their jobs or moving to different roles. Irritation to the mucous membranes of the eyes and gastrointestinal and respiratory tracts can lead to tearing, nasal congestion, dry/sore throat, cold-like symptoms, shortness of breath, wheezing and chest tightness. Moreover, the most serious cases of chemical sensitization to isocyanates can result in severe asthma attacks, which are sometimes fatal.(1,2) Isocyanate products can contain a mixture of monomeric diisocyanates and oligomeric isocyanates. While the toxicity of monomeric diisocyanates is well-known, higher molecular weight isocyanates, the oligomers, also can cause health effects.(3,4)

Potential health effects of exposure to other chemicals in aircraft paints include central nervous system depression and nasal cancer, linked to various solvents(5) and chromates,(6) respectively. Ideally, the ventilation system controls to below occupational exposure limits (OELs) set by regulatory and advisory organizations, such as NIOSH recommended exposure limits (RELs), OSHA permissible exposure limits (PELs), and American Conference of Governmental Industrial Hygienists (ACGIH©) threshold limit values (TLVs©), while limiting releases to the ambient. Table I provides a list of salient OELs. In the aircraft painting process, however, adequate protection against possible chemical sensitization to isocyanates and exceedance of Cr(VI) OELs requires controlling exposures down to levels that may be feasible only when a respiratory protection program supplements engineering controls.

Table I.

Evaluation Criteria for Air Sampling Results Collected during Spray Painting, Fleet Readiness Center Southwest, Naval Base Coronado Specialty Coatings, Building 465, Bay 6.(8,23)

Compound Cas # Lower
Explosive
Limit (%)
OSHA
Permissible
Exposure Limit
NIOSH
Recommended
Exposure Limit
Other Exposure Limits
Total particulate not
otherwise regulated
NA NA TWA 15 mg/m3 NA ACGIH TLV TWA 10 mg/m3 (using an
inhalable particulate sampler)
Hexavalent
chromium
7440-47-3 NA TWA 0.005
mg/m3
TWA 0.001
mg/m3
ACGIH TLV TWA 0.010 mg/m3 (insoluble)
Barium 7440-39-3 NA NA TWA 0.5 mg/m3 ACGIH TLV TWA 0.5 mg/m3
Chromium 7440-47-3 NA TWA 0.5 mg/m3 TWA 0.5 mg/m3 NIOSH IDLH 250 mg/m3
Copper 7440-50-8 NA TWA 1 mg/m3 TWA 1 mg/m3 NIOSH IDLH 100 mg/m3
Strontium 7440-24-6 NA NA NA NA
Tin 7440-31-5 NA TWA 2 mg/m3 TWA 2 mg/m3 NIOSH IDLH 100 mg/m3
Titanium 7440-32-6 NA NA NA NA
Nitroethane 79-24-3 3.4 TWA 100 ppm TWA 100 ppm NIOSH IDLH 1000 ppm
1,2,4-
Trimethylbenzene
95-63-6 0.9 NA TWA 25 ppm ACGIH TLV TWA 25 ppm; EU TWA 20 ppm;
NIOSH IDLH 1000 ppm
1,3,5-
Trimethylbenzene
108-67-8 0.9 NA TWA 25 ppm ACGIH TLV TWA 25 ppm; NIOSH IDLH 1000
ppm
2-butoxyethanol 111-76-2 1.1 TWA 50 ppm TWA 5 ppm ACGIH TLV TWA 20 ppm; NIOSH IDLH 700
ppm
Cumene 98-82-8 0.9 TWA 50 ppm TWA 50 ppm NIOSH IDLH 900 ppm
Ethyl benzene 100-41-4 1.2 TWA 100 ppm TWA 100 ppm ACGIH TLV TWA 20 ppm; NIOSH STEL 125
ppm; NIOSH IDLH 800 ppm
Methyl n-amyl ketone 110-43-0 1.1 TWA 100 ppm TWA 100 ppm ACGIH TLV TWA 50 ppm; NIOSH IDLH 800
ppm
Methyl ethyl ketone 78-93-3 1.4 TWA 200 ppm TWA 200 ppm NIOSH STEL 300 ppm; NIOSH IDLH 3000
ppm
Methyl isobutyl
ketone
108-10-1 1.4 TWA 100 ppm TWA 50 ppm ACGIH TLV TWA 20 ppm; NIOSH STEL 75
ppm; NIOSH IDLH 500 ppm
n-Butyl acetate 123-86-4 1.7 TWA 150 ppm TWA 150 ppm NIOSH STEL 200 ppm; NIOSH IDLH 1700
ppm
Toluene 108-88-3 1.1 TWA 200 ppm TWA 100 ppm ACGIH TLV TWA 20 ppm; EU TWA 50 ppm;
OSHA Ceiling 300 ppm; OSHA 10 min. Max.
peak 500 ppm; NIOSH STEL 150 ppm;
NIOSH IDLH 500 ppm
Hexamethylene
diisocyanate (HDI)
monomer
822-06-0 0.9 NA TWA 0.035
mg/m3
NIOSH Ceiling 0.140 mg/m3 (10 min.);
ACGIH TLV TWA 0.034 mg/m3
Total Reactive
Isocyanate Group
(NCO)
NA NA NA UK-HSE WEL TWA 0.020 mg/m3; UK-HSE
STEL 0.070 mg/m3

NA = none vailable

% = percent

CAS # = Chemical Abstracts Service registry number

OSHA = Occupational Safety and Health Administration

NIOSH = National Institute for Occupational Safety and Health

mg/m3 = milligrams of analyte per cubic meter of air

ppm = parts analyte per million parts air

TWA = time-weighted average

STEL = short term exposure limit (15 minute)

ACGIH TLV = American Conference of Governmental Industrial Hygienist Threshold Limit Value [ACGIH 2001].

IDLH = Immediately Dangerous to Life or Health

EU = European Union

UK-HSE= United Kingdom Health and Safety Executive [HSE 2011]

WEL= Workplace Exposure Limit

OSHA standard, 29 CFR 1910.94 – Ventilation, requires that spray booths maintain an air velocity in the booth cross-section of 100 fpm (0.508 m/s), from Table G-10, Minimum Maintained Velocities Into Spray Booths.(7) However, an OSHA interpretation of 1910.94 prepared for the facility in this study stated that its hangar is a spray area rather than a booth. Recent communication between NIOSH and OSHA suggested that the large size of the painting hangars leads to the spray area designation. This painting operation must comply with training and respiratory protection standards and ensure compliance with 29 CFR1910, Subpart Z, which provides PELs for most of the materials involved in this study.(8) The hexavalent chromium (Cr[VI]) standard, 29 CFR 1910.1026, also must be considered. Specifically, part (f)(1)(ii), on painting large aircraft, allows respiratory protection to achieve the PEL (5 µg/m3), if 8-hr TWA concentrations controlled through other methods do not exceed 25 µg Cr[VI]/m3, “unless the employer can demonstrate that such controls are not feasible.”(9)

The subject facility was designed to meet the 100 fpm velocity requirement, although measurements showed the supply delivered more than needed (Table II). The design velocity was chosen to: (1) prevent explosions, (2) reduce overspray and (3) protect worker health. In this aircraft painting operation, items 2 and 3 are addressed also to some extent by modern paint application methods. These include using high-volume low-pressure (HVLP) spray guns, which significantly reduce paint overspray, and the airline respirators worn by the sprayers and some sprayer helpers (“hosemen”). Interestingly, the ACGIH recommends only 50 fpm (0.254 m/s) for large vehicle paint booths.(10) The current study included comprehensive personal and area air sampling under the observed ventilation conditions, with four field surveys conducted between June 2009 and April 2010.

Table II.

Airflow Indicators

Flow Variable Conditions Supply
[range]
Bay Midplane
[range]
Exhaust
[range]
Measured Velocity
mean, m/s (fpm)
[range in fpm]
{Number of
Measurements}
Before priming 0.792 (156)
[131, 189]
{43}
0.542 (107)
[52, 161]
{16}
1.42 (279)
[188, 316]
{24}
Volumetric Rate
mean, m3/s (cfm)
94.1 (199,000) 74.0 (157,000) 72.5 (154,000)
Normalized Velocity
mean, m/s (fpm)
0.686 (135) -- 0.529 (104)
Filter Pressure Drop
(in. water)
1.33

Measured Velocity
mean, m/s (fpm)
[range in fpm]
{Number of
Measurements}
After topcoat 0.803 (158)
[122, 193]
{43}
0.513 (101)
[45, 140]
{16}
1.28 (252)
[83, 357]
{24}
Volumetric Rate
mean, m3/s (cfm)
95.1 (202,000) 70.1 (148,000) 65.4 (139,000)
Normalized Velocity
mean, m/s (fpm)
0.696 (137) -- 0.479 (94.2)
Filter Pressure Drop
(in. water)
1.67

Measured Velocity
mean, m/s (fpm)
[range in fpm]
{Number of
Measurements}
All data 0.798 (157)
[122, 193]
{86}
0.528 (104)
[45, 161]
{32}
1.34 (264)
[83, 357]
{48}
Volumetric Rate
mean, m3/s (cfm)
94.4 m3/s
(200,000 cfm)
72.2 m3/s
(153,000 cfm)
68.7 m3/s (146,000 cfm)
Normalized Velocity
mean, m/s (fpm)
0.691 (136) -- 0.504 (99.3)

Normalized air velocities (VCS) are based on the cross-sectional area (ACS) of the bay: VCS = (A/ACS) V, where A and V are the face area and face velocity of the supply or exhaust openings.

Plant and Process Description

This study occurred in a hangar bay, where approximately twenty aircraft are painted per year, by a team of seven painters, termed artisans by the Navy: the foreman, two sprayers, two hosemen, and two workers who would rotate in as a sprayer or hoseman or do various jobs, such as material inventory and equipment preparation. One entire bay wall is a door to the outside that swings open for moving aircraft in and out. This door contains the supply plenum and filter. Supply air flows from this end of the bay to the exhaust filter on the opposing wall.

The bay is one of two in a large hangar. An accordion door (folding wall) separates the two bays when only one bay is required, as with painting of strike fighter aircraft or helicopters (blades removed). For wheeling in larger (cargo, transport) aircraft the supply walls of both bays are opened like a gate, the accordion door is folded and the two bays become one big hangar, served by two identical ventilation systems, side-by-side. The accordion door is the wall on the right shown in Figure 1.

Figure 1.

Figure 1

Drawing showing filter area of the aircraft painting bay.

The Specialty Coatings Group receives the aircraft after it has been abrasive blasted. When the aircraft enters the bay, it is first sanded until smooth with hand held sanders. Next, the aircraft surfaces are examined for defects. These are then “potted,” i.e. repaired with epoxy putty, which is sanded down when cured. The artisans then wipe-down the plane with rags soaked in a mixture of methyl ethyl ketone (MEK) and methyl isobutyl ketone (MIBK). Air sampling began here (phase one) and the workers were given the job classification “wiper.”

In phase two the aircraft was sprayed with a chemically-cured, two-component epoxy polyamide, water reducible primer paint. Phase three was spraying the aircraft using a chemically-cured, two-component polyurethane topcoat paint in both light and dark gray. During sanding, wipe-down, and painting, the ventilation system is running at full capacity. Spray painting involves three military-specification (MILSPEC) products (Deft, Inc., Irvine CA): green primer, and the two topcoat colors: dark gray paint for the airframe’s upper surfaces and light gray paint for the lower. Leading the list of hazardous materials are hexavalent chromium (Cr[VI]) in the primer and hexamethylene diisocyanate (HDI) in the topcoats. Two sprayers and two hosemen work during painting, while workers assigned a role in the next phase wait near the supply air wall.

Hangar temperature is maintained near 75 ° F, heated with steam coils in the supply fans if necessary. There is no cooling, and the hangar can reach 80 ° F on warmer days in the mild climate of San Diego. After primer application and again after application of both paints, the artisans exit to the outdoors, and the bay is brought up to 120 ° F to bake the coatings, while the airflow is reduced to 25% of the full-flow condition used for painting.

Engineering Controls

Four supply and four exhaust fans serve the bay, with exhaust rpm linked to supply function via variable frequency drive (VFD) controllers. Two supply fans are equipped with steam heat elements. The ventilation system was designed to maintain a safe and healthy work environment, to control and collect sanding particulate and paint overspray before they enter the ambient, and to maintain the temperature needed for painting operations. Performance is sensitive to exhaust filter loading, and the current replacement criterion is a pressure drop of 2.5 in. water gauge across the filter bank. Figures 1 and 2 show the configuration of the bay, filters, and aircraft, with a supply wall blowing air toward an exhaust wall at the opposite end of the bay.

Figure 2.

Figure 2

Drawing showing interior of bay, F/A-18C/D Hornet aircraft, and area sample locations (A1 – A4).

Personal Protective Equipment

All hangar personnel wore Tyvek® suits and neoprene gloves. Airline hood respirators were always used by the sprayers. The hosemen were observed to wear either full-face continuous flow airline respirators or full-face air-purifying respirators (APRs) fitted with combination organic vapor and particulate cartridges. These two respirator types have assigned protection factors (APF) of 1000 and 50, respectively.(11) Respirators are needed because the ventilation system by itself does not adequately protect against Cr[VI] and isocyanates. The respirators also reduce exposure to VOCs and other airborne stressors, either gas or aerosol.

METHODS

Ventilation Evaluation

Velocities were measured using an AMD-860AirData Multimeter (Shortridge Instruments, Inc., Scottsdale AZ), with current calibration certification, a Shortridge VelGrid, two sections of 20-foot Tygon® tubing, and a 25-foot extension pole. Basic system operation, i.e. which fans were on or off, was observed by noting the operational setting or sequence number, initially verified by climbing up to the hangar building roof and noting sound and vibration from individual fans. Secondarily, a facility computer was sometimes available with software that tracked the performance of the exhaust fans. The facility’s air permit from the San Diego Air Pollution Control Board requires exhaust filter pressure drop to be “maintained between 0.5 and 2.25” in. water gauge and that “exhaust fans and exhaust filters…are installed and operating properly."(12)

Exhaust pressure drop was read from the control room manometer before each painting phase to verify proper operation. Also, differential pressures were measured across bay/ambient, bay/control room, and control room/ambient, using the ShortRidge AirData Multimeter. Filter face velocities were measured before and after painting, on two separate survey dates, on a grid overlaying the physical grid formed by the filter housing beams (Figures 3 and 4). During one survey, velocity measurements were taken in a matrix of 16 locations in a plane midway between supply and exhaust.

Figure 3.

Figure 3

Industrial hygienist measuring supply air velocity, using extension pole to reach high on the filter.

Figure 4.

Figure 4

Supply velocity measurement matrix of 43 locations on the filter, viewed from inside the bay.

Air Sampling

Air sampling conducted to evaluate concentrations of compounds in paints, primers, and solvents used on F/A-18C/D Hornet strike fighter aircraft occurred under existing, full-flow ventilation conditions, on three separate surveys: July 23, 2009; August 4, 2009; and April 13, 2010. One Hornet was painted per survey. Sampling was performed in all three phases of the painting process during each survey: wipe-down, primer, and topcoat. Each of the five job classification, e.g. primer-hoseman, was populated by two workers per survey, for a total of 30 sampled workers. Four areas were sampled (Figure 2) per survey for a total of twelve. Each sampled worker and area sample tripod was fitted with multiple pumps and sampling trains.

Using Material Safety Data Sheets (MSDS) as a guide, air samples were collected for select VOCs, total particulate matter (TPM), Cr[VI], select metals, nitroethane, and HDI. The source of Cr[VI] was the epoxy polyamide primer, which contained barium chromate and zinc chromate. During the aircraft wipe-down phase, only VOC samples were collected. VOCs, TPM, Cr[VI], select metals, and nitroethane samples were collected during the primer phase. VOCs, TPM, select metals, and HDI air samples were collected during the topcoat phase. Both personal breathing zone (PBZ) and area air samples were collected during all phases. PBZ samples were collected by attaching, to a worker’s belt, an air sampling pump connected by Tygon® tubing to the sample media, attached to the outside of their Tyvek® hood. Area samples were collected on tripods at four corners surrounding the F/A-18C/D Hornet, two upwind of the source (aircraft) and two downwind, as shown in Figure 2. The area sample media were approximately 5 ft above the floor.

VOCs sampled included: 2-butoxyethanol, also known ethylene glycol butyl ether (EGBE); n-butyl acetate; cumene; ethyl benzene; methyl amyl ketone (MAK); methyl ethyl ketone (MEK), also known as 2-butanone; methyl isobutyl ketone (MIBK); toluene;1,2,4-trimethylbenzene; and 1,3,5-trimethylbenzene. Samples were collected on charcoal tubes (100 mg front section and 50 mg back section) at air sampling flow rates of 50 ml/min and 200 ml/min. Charcoal tubes were analyzed using NIOSH Method 1501,(13) modified to accommodate MEK, MIBK, MAK, and EGBE by changing the desorbing solvent from carbon disulfide to a 5% n-propanol/95% carbon disulfide solution.

TPM and Cr[VI] air samples were collected on pre-weighed polyvinyl chloride (PVC) filters (37 mm diameter and 5.0 µm pore size) at a flow rate of 2.0 liters per minute (lpm). TPM and Cr[VI] were analyzed according to NIOSH Methods 0500 and 7605, respectively.(14,15) The select metals sampled included barium (Ba), chromium (Cr), copper (Cu), tin (Sn), strontium (Sr), and titanium (Ti), collected on pre-weighed PVC filters (37 mm diameter and 5.0 µm pore size) at a flow rate of 2.0 lpm. The filters were first analyzed for TPM gravimetrically according to NIOSH Method 0500, then digested and analyzed for metals according to NIOSH Method 7303.(16) Nitroethane samples were collected using XAD-2 tubes (600 mg front section and 300 mg back section) at 50 ml/min and analyzed according to NIOSH Method 2526.(17) The select metals and nitroethane were only collected as area samples.

HDI was collected on glass fiber filters (37 mm diameter) impregnated with 1-(9-anthracenylmethyl)piperazine (MAP) at 1.0 lpm. Filters were field extracted in 5 ml solutions of acetonitrile with 1 × 10−4 M MAP. Impingers containing 15 milliliters butyl benzoate with 2 × 10−4 M MAP collected HDI alongside the filters. Analyses followed NIOSH Method 5525.(18) Oligomeric HDI is presented as isocyanate functional group (NCO) mass. HDI monomer is presented as monomer mass and NCO group mass, the latter enabling oligomer comparison.

During each of the three surveys, two wipers sampled for VOCs took approximately 30 minutes to clean the aircraft with solvent-soaked rags. Two sprayers and two hosemen were sampled for VOCs, TPM, and Cr[VI] during primer spraying, which lasted from 30 to 50 minutes. Two sprayers and two hosemen were sampled for VOCs and HDI during the light and dark gray topcoat phase, lasting between 75 and 100 minutes. Thus, each job classification was sampled six times.

Sampling was performed only during the specific painting phases (wipe-down, priming, topcoat) rather than over the work shift. Because Cr(VI) and HDI exposures occurred only in one phase, e.g. Cr(VI) during priming, task-specific sampling was an efficient method. VOC exposures occurred in all three phases, and the 8-hr TWA was constructed as the sum of contributions to the 8-hr TWAs from each phase. The sampled phases included material handling and tool clean-up tasks. Sampling began (ended) as the artisans put on (took off) their required PPE. Break or lunch occurred between phases, in a separate building.

Isocyanate samples were analyzed by the Chemical Exposure & Monitoring Branch (CEMB) of NIOSH (Cincinnati, OH). Bureau Veritas North America (Novi, MI) performed all other analyses. CEMB and Bureau Veritas are accredited by the American Industrial Hygiene Association.

RESULTS

Air Velocities

As shown in Table II, the supply rate of 94.4 m3/s (200,000 cfm) produced a velocity of 0.798 m/s (157 fpm) at the supply filter. The supply filter area was nearly as large as the bay cross-sectional area, and when the supply rate was divided by the cross-sectional area, the resulting normalized velocity was 0.691 m/s (136 cfm/ft2), which exceeded the design specification of 0.508 (m3/s)/m2 (100 cfm/ft2). Comparing measurements before and after painting operations, the most noticeable difference was increased pressure drop across the exhaust filter, with loading from overspray. Interestingly, the range of exhaust filter face velocities also increased—the flow became less uniform—going from [0.995 (188), 1.61 (316)] m/s (fpm) (before primer spraying) to [0.422 (83), 1.81 (357)] m/s (fpm) (after topcoat spraying). The exhaust rate of 68.7 m3/s (146,000 cfm) produced a filter face velocity of 1.34 m/s (264 fpm).

Dividing this rate by the bay cross-sectional area resulted in 0.504 (m3/s)/m2 or 99.3 cfm/ft2; thus, the exhaust system was generally functioning to achieve the design specification, although filter loading decreased the exhaust rate and widened the velocity distribution across the filter (Table II). Before primer spraying, the exhaust velocity ranged from 0.955 m/s (188 fpm) to 1.61 m/s (316 fpm), whereas the range expanded to [0.422 (83), 1.81 (357)] m/s (fpm) after topcoat spraying. More paint was visible on the lower than the upper surfaces of the exhaust filter, and the measured velocity increased with height above the bay floor. This pattern was more pronounced after topcoat spraying.

Air Sampling

Air sampling results from the three surveys were tabulated and summarized into the three phases: aircraft wipe-down, primer spray painting, and topcoat spray painting. During all three phases, the ventilation system was at full flow. Summary statistics included the number of samples, geometric process and 8-hr TWA means, and 95th percentile concentrations (process and 8-hr TWAs, assuming a lognormal distribution underlies the samples). In the reporting below, “mean” refers to geometric mean. For calculations where a third or less of the results were below the limit of detection (LOD), the left-sensored values were replaced by either the LOD divided by the square root of 2 or the LOD divided by 2, depending on whether the geometric standard deviation was less than or equal to 3 or greater than 3, respectively. When at least half of the results were below the LOD, the LOD was used in the mean calculation and reported as less than the resultant value to clearly indicate the overestimation.(19, 20) Table III condenses noteable exposures by process, and Table IV lists individual worker exposures.

Table III.

Summary of Notable Exposures during Aircraft Paint Finishing

Operation
and Job
Statistic Duration
(min.)
MEK
(ppm)
MIBK
(ppm)
TPM
(mg/m3)
Cr[VI]
(µg/m3)
HDI
monomer
(µg HDI/m3)
HDI
monomer
(µg NCO/m3)
HDI
oligomer
(µg NCO/m3)
TRIG
(µg NCO/m3)
Wipe-down N 6 6 6 N/A N/A N/A N/A N/A N/A
Wiper Gmean
[8-hr TWA]*
27 57
[3.2]
63
[3.5]
95th %-ile
[8-hr 95th %-ile]
380
[20]
490
[26]
Primer
application
N 6 6 6 6 6 N/A N/A N/A N/A
Hoseman Gmean
[8-hr TWA]
34 0.22
[0.015]
0.56
[0.039]
4.3
[0.30]
120
[8.3]
95th %-ile
[8-hr 95th %-ile]
1.3
[0.13]
4.6
[0.46]
8.9
[0.54]
260
[16]
Sprayer Gmean
[8-hr TWA]
37 0.42
[0.032]
1.1
[0.087]
18
[1.4]
500
[38]
95th %-ile
[8-hr 95th %-ile]
22
[1.5]
20
[1.4]
25
[1.9]
640
[52]
Topcoat
application
N 6 6 6 6** N/A 6 6 6 6
Hoseman Gmean
[8-hr TWA]
79 0.88
[0.14]
1.2
[0.19]
4.1
[0.68]
3.99
[0.645]
2.06
[0.332]
42.7
[6.90]
45.2
[7.29]
95th %-ile
[8-hr 95th %-ile]
1.8
[0.26]
2.4
[0.35]
8.2
[1.7]
11.2
[2.13]
5.56
[1.06]
148
[24.9]
152
[26.0]
Sprayer Gmean
[8-hr TWA]
89 0.95
[0.17]
1.6
[0.30]
17
[3.2]
32.2
[5.95]
16.1
[2.97]
259
[47.9]
276
[50.9]
95th %-ile
[8-hr 95th %-ile]
4.1
[0.80]
6.5
[1.3]
23
[4.8]
45.8
[7.33]
22.9
[3.66]
448
[70.7]
471
[74.4]
Full Shift
Total
Wiper &
Hoseman
Gmean 8-hr
TWA
[8-hr 95th %-ile]
480 3.4
[20]
3.7
[27]
0.98
[2.2]
8.3
[16]
0.645
[2.13]
0.332
[1.06]
6.90
[24.9]
7.29
[26.0]
Wiper &
Sprayer
Gmean 8-hr
TWA
[8-hr 95th %-ile]
480 3.4
[22]
3.7
[29]
4.6
[6.7]
38
[52]
5.95
[7.33]
2.97
[3.66]
47.9
[70.7]
50.9
[74.4]
*

All mean 8-hr TWAs were calculated as geometric means.

**

Estimated from area samples and personal samples.

Table IV.

Individual results as short term samples and 8-hr TWAs

Sample Date Work Activity Worker ID MEK
(ppm)
4/13/2010 Wipe-down 015 16
4/13/2010 Wipe-down 016 22
7/23/2009 Wipe-down 017 32
7/23/2009 Wipe-down 018 63
8/4/2009 Wipe-down 019 71
8/4/2009 Wipe-down 007 670
Sample Date Work Activity Worker ID MIBK
(ppm)

4/13/2010 Wipe-down 015 14
4/13/2010 Wipe-down 016 20
7/23/2009 Wipe-down 017 48
7/23/2009 Wipe-down 018 63
8/4/2009 Wipe-down 019 77
8/4/2009 Wipe-down 007 920
Sample Date Work Activity Wroker ID MEK 8-hr TWA
(ppm)

8/4/2009 Primer hoseman 001 0.01
7/23/2009 Primer sprayer 002 0.02
4/13/2010 Light sprayer 003 0.03
7/23/2009 Dark hoseman 004 0.03
4/13/2010 Primer sprayer 005 0.05
7/23/2009 Light sprayer 006 0.05
7/23/2009 Primer sprayer, light hoseman, dark hoseman 007 0.07
4/13/2010 Light sprayer 008 0.12
8/4/2009 Primer sprayer, dark sprayer 009 0.15
8/4/2009 Primer sprayer, light sprayer 008 0.15
8/4/2009 Light hoseman, dark hoseman 010 0.18
7/23/2009 Primer hoseman, dark hoseman 011 0.27
8/4/2009 Dark sprayer, light hoseman 012 0.28
8/4/2009 Primer hoseman, light sprayer, dark hoseman 013 0.28
7/23/2009 Dark sprayer 014 0.56
7/23/2009 Light sprayer 013 0.56
4/13/2010 Wipe-down, primer hoseman, light hoseman 015 1.3
4/13/2010 Wipe-down, primer hoseman, light hoseman 016 1.4
7/23/2009 Wipe-down 017 1.7
7/23/2009 Wipe-down, primer hoseman, light hoseman 018 3.4
8/4/2009 Wipe-down 019 4.1
4/13/2010 Primer sprayer 020 4.2
8/4/2009 Wipe-down 007 35
Sample Date Work Activity Wroker ID MIBK 8-hr TWA
(ppm)

8/4/2009 Primer hoseman 001 0.04
4/13/2010 Light sprayer 005 0.05
4/13/2010 Primer sprayer 003 0.05
7/23/2009 Primer sprayer 002 0.06
7/23/2009 Dark hoseman 004 0.10
8/4/2009 Primer sprayer, dark sprayer 010 0.13
4/13/2010 Light sprayer 008 0.16
7/23/2009 Light sprayer 006 0.16
7/23/2009 Primer sprayer, light hoseman, dark hoseman 007 0.21
8/4/2009 Primer sprayer, light sprayer 009 0.35
8/4/2009 Light hoseman, dark hoseman 008 0.35
8/4/2009 Dark sprayer, light hoseman 012 0.35
8/4/2009 Primer hoseman, light sprayer, dark hoseman 013 0.37
7/23/2009 Primer hoseman, dark hoseman 014 0.79
7/23/2009 Dark sprayer 013 0.79
7/23/2009 Light sprayer 011 0.94
4/13/2010 Wipe-down, primer hoseman, light hoseman 015 1.2
4/13/2010 Wipe-down, primer hoseman, light hoseman 016 1.3
7/23/2009 Wipe-down 017 2.5
4/13/2010 Primer sprayer 020 2.5
7/23/2009 Wipe-down, primer hoseman, light hoseman 018 3.4
8/4/2009 Wipe-down 019 4.5
8/4/2009 Wipe-down 007 48
Sample Date Work Activity Worker ID TPM 8-hr TWA
(mg/m3)

7/23/2009 Primer hoseman 018 0.11
8/4/2009 Primer hoseman 001 0.29
7/23/2009 Primer hoseman 011 0.30
4/13/2010 Primer hoseman 015 0.32
8/4/2009 Primer hoseman 013 0.35
4/13/2010 Primer hoseman 020 0.63
7/23/2009 Primer sprayer 002 0.69
8/4/2009 Primer sprayer 009 1.3
4/13/2010 Primer sprayer 016 1.3
8/4/2009 Primer sprayer 008 1.5
4/13/2010 Primer sprayer 005 1.8
7/23/2009 Primer sprayer 007 1.9
Sample Date Work Activity Worker ID Cr[VI] 8-hr TWA
(µg/m3)

7/23/2009 Primer hoseman 018 graphic file with name nihms795423ig1.jpg
7/23/2009 Primer hoseman 011 7.7
8/4/2009 Primer hoseman 001 7.9
8/4/2009 Primer hoseman 013 9.3
4/13/2010 Primer hoseman 015 10
4/13/2010 Primer hoseman 020 18
7/23/2009 Primer sprayer 002 22
8/4/2009 Primer sprayer 009 35
4/13/2010 Primer sprayer 016 37
8/4/2009 Primer sprayer 008 42
4/13/2010 Primer sprayer 005 44
7/23/2009 Primer sprayer 007 55
Sample Date Work Activity Worker ID HDI monomer 8-hr TWA
(µg HDI/m3)

7/23/2009 Light hoseman 018 0.45
4/13/2010 Light hoseman 015 0.92
7/23/2009 Dark hoseman 004 1.2
4/13/2010 Light hoseman 016 1.5
7/23/2009 Light hoseman 007 1.6
8/4/2009 Light sprayer, dark hoseman 013 2.5
8/4/2009 Dark sprayer, light hoseman 012 2.5
7/23/2009 Dark sprayer 014 2.7
7/23/2009 Light sprayer 013 2.7
8/4/2009 Light sprayer 008 3.0
8/4/2009 Dark sprayer 009 3.0
7/23/2009 Dark sprayer 011 3.1
7/23/2009 Light sprayer 006 3.1
4/13/2010 Light sprayer 008 5.8
4/13/2010 Light sprayer 003 7.8
Sample Date Work Activity Worker ID TRIG 8-hr TWA
(µg NCO/m3)

7/23/2009 Light hoseman 018 4.6
7/23/2009 Dark hoseman 004 14
4/13/2010 Lighthoseman 015 18
8/4/2009 Light sprayer, dark hoseman 013 19
8/4/2009 Dark sprayer, light hoseman 012 19
7/23/2009 Light hoseman 007 19
4/13/2010 Light hoseman 016 19
7/23/2009 Dark sprayer 014 19
7/23/2009 Light sprayer 013 19
7/23/2009 Dark sprayer 011 23
7/23/2009 Light sprayer 006 23
8/4/2009 Light sprayer 008 28
8/4/2009 Dark sprayer 009 28
4/13/2010 Light sprayer 008 61
4/13/2010 Light sprayer 003 80

Inline graphic = NIOSH, ACGIH, or UK-HSE OEL exceeded. Inline graphic = OSHA PEL exceeded.

Aircraft Wipe-down

During the approximately 30 minutes of wipe-down, most of the full-shift VOC exposures occurred, with MEK and MIBK means for workers performing this task of 57 ppm and 63 ppm, respectively. One of six samples exceeded the MEK short-term exposure limit (STEL: ACGIH = 300 ppm, NIOSH = 300 ppm), and two of six exceeded the MIBK STEL (ACGIH = 75 ppm, NIOSH = 75 ppm). One of the six personal samples showed concentrations of 670 ppm for MEK and 920 ppm for MIBK, which are at least an order of magnitude higher than the other five samples. In addition, there was more than 50% breakthrough of MEK on this sample. While these values were retained in the calculations, it is possible this sample was an anomaly. In any case, the exposure was adequately controlled by air-purifying respirators (APRs), which have an assigned protection factor (APF) of 10 or 50, for half-face or full-face types, respectively.

Full-shift OELs (MEK: REL = 200 ppm, PEL = 200 ppm, TLV = 200 ppm and MIBK: REL = 50 ppm, PEL = 100 ppm, TLV = 20 ppm) were not exceeded (Table III). After wipe-down, workers would become either sprayers or hosemen. For workers in the sprayer job classification for the remainder of the day, the MEK and MIBK 8-hr TWAs were 3.4 ppm and 3.7 ppm, respectively. The 8-hr TWAs were essentially the same for the hosemen, since the means were dominated by wipe-down exposures, and subsequent job classification had negligible effect. Table V shows area means for MEK and MIBK at the four tripods, with the upwind results (tripods #3 and #4) near or below the LOD.

Table V.

Summary of Select VOC Air Concentrations during F/A-18C/D Hornet Wipe-down

Work
Activity
or
Sample
Location
Sample
Type
[Mean
Volume]
(L)
Number
of
Samples
[Task
Duration
Mean]
(min)
1, 2, 4-
Trimethyl-
benzene
Gmean
(ppm)
1, 3, 5-
Trimethyl-
benzene
Gmean
(ppm)
2-
Butoxy
ethanol
Gmean
(ppm)
Cumene
Gmean
(ppm)
Ethyl-
benzene
Gmean
(ppm)
Methyl
Amyl
Ketone
Gmean
(ppm)
Methyl
Ethyl
Ketone
Gmean
{95th %-tile}
(ppm)
Methyl
Isobutyl
Ketone
Gmean
{95th %-tile}
(ppm)
N-Butyl
Acetate
Gmean
(ppm)
Toluene
Gmean
(ppm)
Wipe-
down
Worker
P
[5.5]
6
[27]
<0.02a <0.02 <0.05 <0.02 <0.03 <0.04 57
{380}
63
{490}
<0.03 0.05b
Tripod
#1
A
[4.0]
6
[32]
<0.03 <0.03 <0.07 <0.04 <0.04 <0.06 1.7b 2.0 <0.06 <0.02
Tripod
#2
A
[4.4]
6
[35]
<0.03 <0.03 <0.07 <0.04 <0.04 <0.06 1.6 2.3 <0.05 <0.03
Tripod
#3
A
[4.3]
6
[34]
<0.03 <0.03 <0.08 <0.04 <0.04 <0.06 <0.3 0.21b <0.05 <0.03
Tripod
#4
A
[4.4]
6
[35]
<0.03 <0.03 <0.08 <0.04 <0.04 <0.06 <0.08 0.10b <0.05 <0.03
a

When at least half of the sample results were below the limit of detection, the LOD was used in the mean calculation and reported as less than the resultant value.

b

A third or less of the sample results contributing to the mean calculation were less than the limit of detection and were replaced by either the LOD /√2 or the LOD/2..

Aircraft Primer Spray Painting

VOC results for the primer spray painting phase are summarized in Table VI. While measureable levels of 1,2,4-trimethylbenzene, 1,3,5-trimethylbenzene, 2-butoxyethanol (EGBE), MEK, and MIBK were detected in these samples, 1,2,4-trimethylbenzene and 1,3,5-trimethylbenzene will not be discussed here as the levels were well below the OEL of 25 ppm. Mean PBZ sample results for EGBE, MEK, and MIBK for sprayers were 2.5, 0.42, and 1.1 ppm, respectively, and for hosemen: 0.36, 0.22, and 0.56 ppm.

Table VI.

Summary of Select VOC Air Concentrations during Primer Spray Painting

Work
Activity
or
Sample
Location
Sample
Type
[Mean
Volume]
(L)
Number
of
Samples
[Task
Duration
Mean]
(min.)
1, 2, 4-
Trimethyl
-benzene
Gmean
(ppm)
1, 3, 5-
Trimethyl
-benzene
Gmean
(ppm)
2-Butoxy-
ethanol
Gmean
{95th %-tile}
(ppm)
Cumene
Gmean
(ppm)
Ethyl-
benzene
Gmean
(ppm)
MAK
Gmean
(ppm)
MEK
Gmean
{95th %-
tile}
(ppm)
MIBK
Gmean
{95th %-tile}
(ppm)
N-Butyl
Acetate
Gmean
(ppm)
Toluene
Gmean
(ppm)
Primer
Sprayer

P
[7.5]
6
[37]
1.3 0.40 2.5
{3.6}
0.06 <0.02 <0.03 0.42b
{22}
1.1
{20}
<0.02 0.03 b
As 8-hr
TWA
P 6 0.19
{0.29}
0.032 b
{1.5}
0.087
{1.4}
Primer
Hosemen

P
[6.9]
6
[34]
0.34 0.11 0.36 b
{1.2}
<0.02 <0.02 <0.03 0.22 b
{1.3}
0.56
{4.6}
<0.03 <0.02
As 8-hr
TWA
P 6 0.025 b
{0.0856}
0.015 b
{0.13}
0.039
{0.46}
Tripod
#1
A
[5.2]
6
[41]
0.63 0.19 b 1.1 0.04 b <0.03 <0.05 <0.2 0.19 b <0.04 <0.03
Tripod
#2
A
[5.2]
6
[41]
0.29 0.09 b 0.57 <0.03 <0.03 <0.05 <0.1 0.13 b <0.04 <0.03
Tripod
#3
A
[5.4]
6
[43]
<0.1 a <0.04 <0.1 <0.03 <0.03 <0.05 0.12 b 0.14 b <0.04 <0.03
Tripod
#4
A
[4.9]
6
[39]
0.07 b <0.04 0.14 b <0.03 <0.03 <0.05 <0.1 <0.1 <0.06 <0.03
a

When at least half of the sample results were below the limit of detection, the LOD was used in the mean calculation and reported as less than the resultant value.

b

A third or less of the sample results contributing to the mean calculation were less than the limit of detection and were replaced by either the LOD /√2 or the LOD/2.

EGBE 8-hr TWAs were 0.19 ppm and 0.025 ppm for sprayers and hosemen— below the OELs (REL = 5 ppm, PEL = 50 ppm) — and only during primer painting were concentrations clearly above the LOD. Note that MEK and MIBK full-shift TWAs were reported in the Wipe-down section. All the EGBE, MEK, and MIBK results were well below the STELs during primer spraying.

As worker 8-hr TWAs, all 12 Cr[VI] samples exceeded the NIOSH REL of 1 µg/m3, 11 out of 12 exceeded the OSHA PEL of 5 µg/m3, and 7 out of 12 exceeded the ACGIH TLV of 10 µg/m3, with means of 38 µg/m3 and 8.3 µg/m3 for sprayers and hosemen, respectively. With Cr[VI] exposures occurring only during primer painting, it is noteworthy that mean exposures for both sprayers and hosemen exceeded the NIOSH REL and the OSHA PEL. All six hoseman exposures, however, were below 25 µg/m3, so that controlling to below the PEL of 5 µg/m3 using respiratory protection complied with the OSHA chromium standard, for this job group. Reducing the sprayer exposure (outside the respirator) through engineering controls must still be accomplished to come into compliance using respirators. TPM and Cr[VI] concentrations sampled during primer painting were 18 mg TPM/m3 and 500 µg Cr[VI]/m3 for sprayers and 4.3 mg TPM/m3 and 120 µg Cr[VI]/m3 for hosemen (Tables III and VII).

Table VII.

Summary of TPM and Cr[VI] Air Concentrations during Primer Spray Painting

Work Activity or
Sample Location
Sample
Type
[Mean
Volume]
(L)
Number of
Samples
[Task
Duration
Mean]
(min)
Total
Particulate
Matter
Gmean
{95th %-tile}
(mg/m3)
Hexavalent
Chromium
Gmean
{95th %-tile}
(µg/m3)
Primer Sprayer P
[74]
6
[37]
18
{25}
500
{640}
Primer Hosemen P
[68]
6
[34]
4.3
{8.9}
120
{260}
Tripod #1 A
[83]
3
[41]
4.8
{9.8}
160
{310}
Tripod #2 A
[78]
3
[41]
1.6b
{3.7}
44
{98}
Tripod #3 A
[86]
3
[43]
<0.7a 0.29b
Tripod #4 A
[80]
3
[39]
<0.7 0.46b
a

When at least half of the sample results were below the limit of detection, the LOD was used in the mean calculation and reported as less than the resultant value.

b

A third or less of the sample results contributing to the mean calculation were less than the limit of detection and were replaced by either the LOD /√2 or the LOD/2.

Table IV shows that sprayers’ and hosemen’s 8-hr TWAs for TPM were all below the OELs (TLV = 10 mg/m3, PEL = 15 mg/m3), and Table III reports mean 8-hr TWAs as 1.4 and 0.30 mg/m3, respectively. Because TPM was measured using 37 mm PVC filters in closed-face cassettes (CFC) and not inhalable particulate samplers, comparison to the inhalable fraction TLV carries the uncertainty of size selection difference between the two methods. A recent study found that an IOM inhalable sampler collected from 1.62 to 2.97 more mass than the CFC.(21) As the highest TPM 8-hr TWA was 1.9 mg/m3, exceeding the TLV would require the real inhalable mass to be 5.3 times greater than the CFC result. The conclusion that the TPM TLV and PEL were not exceeded is then apparently consistent with the reported IOM/CFC performance ratio. TPM and Cr[VI] area means for downwind tripods were 4.8 mg/m3 TPM and 160 µg/m3 Cr[VI] for tripod #1 and 1.6 mg/m3 TPM and 44 µg/m3 Cr[VI] for tripod #2. Upwind, TPM was below the LOD, while Cr[VI] means were 0.29 µg/m3 and 0.46 µg/m3 for tripods #3 and #4, respectively.

Area samples for select metals collected during primer application (Table VIII) also included TPM, as it was available gravimetrically during metals analysis, which detected Ba, Cr, and trace amounts of Cu and Sr. Only trace amounts of nitroethane were detected (Table XI).

Table VIII.

Summary of TPM and Select Metals Air Concentrations during Primer Spray Painting

Work
Activity
or
Sample
Location
Sample
Type
[Mean
Volume]
(L)
Number
of
Samples
[Task
Duration
Mean]
(min)
Total
Particulate
Matter
Gmean
(mg/m3)
Barium
Gmean
(µg/m3)
Chromium
Gmean
(µg/m3)
Copper
Gmean
(µg/m3)
Strontium
Gmean
(µg/m3)
Tin
Gmean
(µg/m3)
Titanium
Gmean
(µg/m3)
Tripod #1 A
[83]
3
[41]
5.7 710 270 1.1 b 3.5 <7 <2
Tripod #2 A
[81]
3
[41]
2.0 240 90 <1 1.1 <7 <2
Tripod #3 A
[87]
3
[43]
<0.7 a 0.58 <3 <0.8 <0.2 <6 <2
Tripod #4 A
[80]
3
[39]
<0.7 0.73b <5 1.3 b <0.2 <7 <2
a

When at least half of the sample results were below the limit of detection, the LOD was used in the mean calculation and reported as less than the resultant value.

b

A third or less of the sample results contributing to the mean calculation were less than the limit of detection and were replaced by either the LOD /√2 or the LOD/2.

Table XI.

Summary of Select VOC Air Concentrations during Topcoat Spray Painting

Work
Activity or
Sample
Location
Sample
Type
[Mean
Volume]
(L)
Number
of
Samples
[Task
Duration
Mean]
(min)
1, 2, 4-
Trimethyl
-benzene
Gmean
(ppm)
1, 3, 5-
Trimethyl
-benzene
Gmean
(ppm)
2-
Butoxy-
ethanol
Gmean
(ppm)
Cumene
Gmean
(ppm)
Ethyl
benzene
Gmean
(ppm)
MAK
Gmean
{95th %-ile}
(ppm)
MEK
Gmean
{95th %-ile}
(ppm)
MIBK
Gmean
{95th %-ile}
(ppm)
N-Butyl
Acetate
Gmean
{95th %-ile}
(ppm)
Toluene
Gmean
(ppm)
Paint
Sprayer
P
[18]
6
[89]
0.09 2.0 0.07 b <0.01 0.09 9.2
{15}
0.95
{4.1}
1.6
{6.5}
4.7
{7.1}
<0.02
As 8-hr
TWA
P 6 1.7
{2.6}
0.17
{0.80}
0.30
{1.3}
0.86
{1.3}
Paint
Hosemen
P
[16]
6
[79]
0.02 0.45 0.04 b <0.01 0.02 b 1.8
{3.2}
0.88
{1.8}
1.2
{2.4}
0.94
{1.7}
<0.01
As 8-hr
TWA
P 6 0.29
{0.51}
0.14
{0.26}
0.19
{0.35}
0.15
{0.32}
Tripod #1 A
[14]
6
[111]
0.03 b 0.68 <0.04 <0.01 0.03 b 2.5 0.31 0.41 1.2 <0.01
Tripod #2 A
[14]
6
[113]
0.03 b 0.70 0.04 b <0.01 0.02 b 2.6 0.05 0.12 1.3 <0.01
Tripod #3 A
[15]
4
[116]
<0.01a <0.01 <0.02 <0.01 <0.01 <0.02 <0.02 <0.01 <0.02 <0.01
Tripod #4 A
[15]
4
[118]
<0.01 <0.01 <0.02 <0.01 <0.01 <0.02 0.03 b 0.05 b <0.02 <0.01
a

When at least half of the sample results were below the limit of detection, the LOD was used in the mean calculation and reported as less than the resultant value.

b

A third or less of the sample results contributing to the mean calculation were less than the limit of detection and were replaced by either the LOD /√2 or the LOD/2.

Aircraft Topcoat Painting

During the topcoat phase, mean HDI monomer 8-hr TWAs were 5.95 µg/m3 for sprayers and 0.645 µg/m3 for hosemen (Table III). None of the 15 personal samples exceeded an HDI OEL (REL = 35 µg/m3, TLV = 34 µg/m3). However, concentrations of Total Reactive Isocyanate Group (TRIG)—the total of HDI monomer and HDI oligomer in terms of NCO group mass—showed six of 15 samples exceeded the United Kingdom-Health and Safety Executive (UK-HSE) workplace exposure limit (WEL) of 20 µg/m3. The U.S. does not have a TRIG OEL at this time. The UK has a STEL of 70 µg/m3, in addition to the WEL.(4, 22) The topcoat paint consists mostly of HDI oligomers, with less than 1% HDI monomer, making pertinent the use of an OEL that encompasses exposure to both the monomeric and oligomeric forms of HDI like the UK-HSE WEL for TRIG. TRIG 8-hr TWAs in Table IV show 50.9 µg/m3 for sprayers and 7.29 µg/m3 for hosemen.

Table III shows mean personal exposures for sprayers during topcoat application: 32.2 µg/m3 HDI monomer (16.1 µg/m3 NCO), 259 µg/m3 HDI oligomer, and 276 µg/m3 TRIG. For hosemen the means were 3.99 µg/m3 HDI monomer (2.06 µg/m3 NCO), 42.7 µg/m3 HDI oligomer, and 45.2 µg/m3 TRIG. Means were formed from the individual results in Table X. For the two tripods downwind from the aircraft, monomer, NCO, and oligomer area concentrations were 4.76, 2.38 and 88.7 µg/m3 for tripod #1 and 5.21, 2.60 and 70.9 µg/m3 for tripod #2, respectively. Results for upwind tripods were below the LODs. During one survey, impinger samples were collected alongside the filters for comparison. Tripod #1 had 11.0 µg/m3 (impinger) vs. 3.27 µg/m3 (filter) for HDI monomer and 148 µg/m3 vs. 103 µg/m3 for HDI oligomer. Tripod #2 showed 11.2 µg/m3 (impinger) vs. 3.83 µg/m3 (filter) for HDI monomer and 139 µg/m3 vs. 82.1 µg/m3 for HDI oligomer.

Table X.

HDI Monomer and HDI Oligomer Air Concentrations during Topcoat Spray Painting

Sample
Date
Work
Activity or
Sample
Location
Sample
Type
Sample
Time
(min.)
Air
Sample
Volume
(m3)
Hexamethylene
Diisocyanate
Monomer
Mean
(µg HDI/m3)
Hexamethylene
Diisocyanate
Monomer
Mean
(µg NCO/m3)
Hexamethylene
Diisocyanate
Oligomer
Mean
(µg NCO/m3)
Total
Reactive
Isocyanate
Group
Mean
(µg NCO/m3)
7/23/2009 Hosemen A P 102 0.1038 11.3 5.62 130 136
7/23/2009 Hosemen B P 96 0.1006 4.48 2.24 44.3 46
7/23/2009 Sprayer A P 95 0.0957 27.3 13.7 180 193
7/23/2009 Sprayer B P 102 0.1037 29.1 14.6 198 212
7/23/2009 Tripod #1 A 105 0.1067 8.97 4.48 147 152
7/23/2009 Tripod #2 A 114 0.1160 2.59 1.29 36.5 37.8

8/4/2009 Hosemen A P 83 0.0839 1.93 0.97 27.6 28.6
8/4/2009 Hosemen B P 75 0.0755 <0.7 <0.4 <3 <3
8/4/2009 Sprayer A P 95 0.0951 25.0 12.5 178 190
8/4/2009 Sprayer B P 90 0.0917 31.5 15.7 279 295
8/4/2009 Tripod #1 A 93 0.0948 3.67 1.84 46.0 47.8
8/4/2009 Tripod #2 A 91 0.0934 14.2 7.11 119 126
8/4/2009 Tripod #3 A 97 0.0950 <0.5 <0.3 <2 <2
8/4/2009 Tripod #4 A 98 0.1015 <0.5 <0.3 <2 <2

4/13/2010 Hosemen A P 66 0.0627 10.8 5.40 133 139
4/13/2010 Hosemen B P 54 0.0546 8.21 4.10 153 157
4/13/2010 Sprayer A P 78 0.0830 35.9 18.0 356 374
4/13/2010 Sprayer B P 75 0.0754 49.6 24.8 484 509
4/13/2010 Tripod #1 A 135 0.1327 3.27 1.64 103 105
4/13/2010 Tripod #2 A 135 0.1316 3.83 1.91 82.1 84.0
4/13/2010 Tripod #3 A 135 0.1405 <0.3 <0.1 <0.3 <0.3
4/13/2010 Tripod #4 A 137 0.1344 <0.3 <0.1 <0.3 <0.3
4/13/2010 Tripod #1 A* 135 0.1346 11.0 5.49 142 148
4/13/2010 Tripod #2 A* 135 0.1374 11.2 5.58 139 145
4/13/2010 Tripod #3 A* 135 0.1344 <0.6 <0.3 <0.5 <0.5
4/13/2010 Tripod #4 A* 137 0.1391 <0.6 <0.3 <0.5 <0.5
*

Impinger Sample

The VOC results summarized in Table XI indicate only MAK, MEK, MIBK, and n-butyl acetate as clearly above LODs, with PBZ sample means 9.2, 0.95, 1.6, and 4.7 ppm, respectively, for sprayers and 1.8, 0.88, 1.2, and 0.94 ppm, for hosemen. While 8-hr TWAs for MEK and MIBK were reported for individual artisans earlier in the Wipe-down section, sprayers as a job category had MAK and n-butyl acetate 8-hr TWAs of 1.7 and 0.86 ppm, respectively, with 0.29 ppm and 0.15 ppm for hosemen. All personal samples were below the OELs (MAK: REL = 100 ppm, PEL = 100 ppm and n-butyl acetate: REL = 150 ppm, PEL = 150 ppm), and topcoat painting was the only phase with concentrations above the LOD. Area means for MAK, MEK, MIBK and n-butyl acetate (Table XI) followed the pattern where upwind samples were near or below the LOD. Of the metals in Table XII, only titanium was detected at notable levels, with means 39 µg/m3 on tripod #1 and 45 µg/m3 on tripod #2.

Table XII.

Summary of TPM and Select Metals Air Concentrations during Topcoat Spray Painting

Work
Activity or
Sample
Location
Sample
Type
[Mean
Volume]
(L)
Number of
Samples
[Task
Duration
Mean]
(min)
Total
Particulate
Matter
Gmean
(mg/m3)
Barium
Gmean
(µg/m3)
Chromium
Gmean
(µg/m3)
Copper
Gmean
(µg/m3)
Strontium
Gmean
(µg/m3)
Tin
Gmean
(µg/m3)
Titanium
Gmean
(µg/m3)
Tripod #1 A
[226]
3
[111]
3.0 <0.2 <1 <0.3 <0.1 <2 39
Tripod #2 A
[217]
3
[113]
3.4 <0.1 <1 0.30b <0.07 <2 45
Tripod #3 A
[232]
3
[115]
<0.2a <0.1 <1 <0.3 <0.07 <2 <0.7
Tripod #4 A
[241]
3
[118]
<0.2 <0.1 <1 <0.3 <0.07 <2 <0.7
a

When at least half of the sample results were below the limit of detection, the LOD was used in the mean calculation and reported as less than the resultant value.

b

A third or less of the sample results contributing to the mean calculation were less than the limit of detection and were replaced by either the LOD /√2 or the LOD/2.

DISCUSSION

The imbalance in the ventilation system-- the supply rate substantially exceeds the exhaust rate-- creates large circulations, additional turbulence, fugitive emissions, and wastes energy (especially due to the large, sometimes tempered, bay air volume). As fugitive emissions occurred along the length of this bay under positive pressure, the supply rate dropped to the bay midplane flow rate, which then diminished to the exhaust rate (Table II).

Another way to think about the excess capacity is to calculate a normalized velocity, by dividing the volumetric flow through the supply filter, 94.4 m3/s, by the bay cross-sectional area, 137 m2, resulting in 0.691 m/s (136 fpm). This conceptual velocity must be distinguished from the measured supply filter face velocity of 0.798 m/s (157 fpm). In comparing 0.691 m/s (136 fpm) to the workzone design velocity of 0.508 m/s (100 fpm), the excess is clear. Also, this normalized velocity was higher than the velocity measured midway between supply and exhaust, because the midplane flow was influenced also by the exhaust flow.

While the supply fans were clearly overspecified, exhaust filter bank resistance determines to some extent whether exhaust can match supply, and keeping filters at the lower end of their maintenance life, i.e. filter pressure drop, would reduce flow resistance. Lowering, then, the filter replacement benchmark from a Δp of 622 Pa (2.5 in. water) to 498 Pa (2.0 in. water) would be a good operating policy change toward system balance. A layer of inexpensive felt-like material (not as designed) was observed on top of the pre-filter, i.e. a pre-pre-filter or “pre-layer,” added to protect downstream filter material from sanding particulate and paint droplet loading, thereby reducing filter replacement frequency (cost). However, the intended exhaust velocity and airflow pattern in the bay cannot be achieved with extra flow blockage, especially when pre-layer loading disrupts the uniform face velocity field. Also, energy costs increase as exhaust fans work harder to deliver the required flow.

The ventilation system inadequately controlled exposures in this operation, without additional reduction provided by respiratory protection. OSHA regards this large facility as a “spray area,” which does not have a specific air velocity requirement, unlike a “spray booth,” which requires 100 fpm (0.508 m/s). With mean Cr[VI] concentrations during primer application 100 times greater for sprayers than the OSHA PEL concentration, control measures are clearly needed. Because balanced ventilation adhering to 29 CFR 1910.94 (100 fpm) would still need supplementation with appropriate respirators, the level of protection engineering controls must deliver is best defined by the aircraft painting section of the OSHA hexavalent chromium standard. In other words, controlling Cr[VI] concentrations below 25 µg/m3, as an 8-hr TWA, is probably a more applicable performance metric than maintaining an air velocity of 100 fpm (0.508 m/s). That being said, a balanced flow of 0.508 m/s (100 fpm) has not been tried for this operation, and this condition might be more effective than the trials presented here.

Hosemen wearing full-face APRs (APF of 50) rather than airline respirators during primer application causes concern. The resulting Cr[VI] exposure is below the REL, but not by a comfortable margin of safety, as the highest individual and 95th percentile 8-hr TWAs were 18 and 16 µg/m3, respectively. Applying the APF of 50 results in 0.36 and 0.32 µg/m3 or 36% and 32% of the REL (1 µg/m3). Use of full face airline respirators by the hosemen would relieve this concern because the APF is 200 times greater.

Variation in exposure among individual workers highlights the importance of control strategies additional to ventilation. Table IV shows Worker 007 having the highest exposures in whatever job he performed. The study team observed that this individual worked harder and longer than most of his cohort. During wipedown, his process exposures were more than ten times the mean, and this extreme excursion is likely due to his subtask within wipe-down of actually reaching into the barrel of solvent to obtain soaked rags for himself and the other wiper. As a work practice control, tongs should be used, or another means of extracting the rags at a distance from the solvent surface, and the container should be closed immediately. That only one of two workers on one of three sample dates had this high exposure suggests variation in material handling technique.

As monomeric HDI represents less than 1% of the NCO content of HDI paint products, oligomeric HDI is the primary source of isocyanate expsosure. Only the airborne route was documented in this study. However, workers had limited exposed skin during paint application, as they wore Tyveks, gloves and either full-face respirators or air-supplied hoods.

CONCLUSION and RECOMMENDATIONS

The respiratory protection program should remain in place to protect aircraft painting artisans from significant exposures to MEK and MIBK. Additionally, moving the hosemen from full-face APRs into air-supplied hoods during primer application would provide enhanced protection against Cr[VI] exposure. Hosemen should be trained to avoid being downwind of the sprayers or the spray plume by staying behind the sprayers, opposite the spray direction. During topcoat painting, the possibility of isocyanate exposure exceeding the UK-HSE STEL of 0.070 mg/m3 further mandates respirator use.

While existing ventilation practices combined with appropriate use of supplied-air hoods and full-face APRs adequately controlled exposures, air pollution permit compliance, energy footprint, and possibly exposure control could be improved by balancing the supply flow rate to the exhaust flow rate. The exhaust already provides the correct volumetric flow rate to produce a velocity of approximately 0.508 m/s (100 fpm) in the bay cross section, depending on exhaust filter pressure drop. Replacing the exhaust pre-layer more frequently and lowering the filter replacement Δp from 622 Pa (2.5 in. water) to 498 Pa (2.0 in. water) would be good steps toward system balance. Lower capacity supply fans or lower RPM operation are system balancing techniques worth considering.

Table IX.

Summary of Nitroethane Air Concentrations during Primer Spray Painting

Work Activity or
Sample Location
Sample Type
[Mean Volume]
(L)
Number of Samples
[Task Duration Mean]
(min)
Nitroethane Gmean
(ppm)
Tripod #1 A
[2.0]
3
[41]
0.26 b
Tripod #2 A
[1.9]
2
[37]
0.38
Tripod #3 A
[2.2]
3
[43]
<0.1a
Tripod #4 A
[2.0]
3
[39]
<0.2
a

When at least half of the sample results were below the limit of detection, the LOD was used in the mean calculation and reported as less than the resultant value.

b

A third or less of the sample results contributing to the mean calculation were less than the limit of detection and were replaced by either the LOD /√2 or the LOD/2.

Acknowledgments

Carol Lavery generously made her staff and offices at Naval Base Coronado Industrial Hygiene Division available to support the NIOSH team during field surveys, in which Allan Hammar contributed professionally during air sampling with mission-focused expertise and provided essential process and work practice information. Raymond Lucy and Kathleen Paulson, of the Naval Facilities Engineering and Expiditionary Warfare Center, provided expert technical guidance and project stewardship, while working tirelessly to bring the proper resources together.

Footnotes

DISCLAIMER

The findings and conclusions in this article have not been formally disseminated by the National Institute for Occupational Safety and Health and should not be construed to represent any agency determination or policy.

REFERENCES

  • 1.U.S. Department of Health and Human Services. Preventing Asthma and Death from Diisocyanate Exposure. Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health; 1996. DHHS (NIOSH) Publication No. 96–111. [Google Scholar]
  • 2.U.S. Department of Health and Human Services. NIOSH ALERT: Preventing asthma and death from MDI exposure during spray-on truck bed liner and related applications. Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health; 2006. DHHS (NIOSH) Publication No. 2006-149. [Google Scholar]
  • 3.Vandenplas O, Cartier A, Lesage J, et al. Prepolymers of hexamethylene diisocyanate as a cause of occupational asthma. J. of Allergy and Clin. Immunol. 1993;91:850–861. doi: 10.1016/0091-6749(93)90342-d. [DOI] [PubMed] [Google Scholar]
  • 4.Bello D, Woskie SR, Streicher RP. Polyisocyanates in occupational environments: a critical review of exposure limits and metrics. Am. J. Ind. Med. 2004;46:480–491. doi: 10.1002/ajim.20076. [DOI] [PubMed] [Google Scholar]
  • 5.Levy BS, Wegman DH. Occupational Health; recognizing and preventing work-related disease. 2nd. Boston: Little, Brown; 1988. p. 203. 1988. [Google Scholar]
  • 6.U.S. Department of Health and Human Services. Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health; [accessed: June 12, 2015]. Workplace Safety and Health Topics: Hexavalent chromium. Available at: http://www.cdc.gov/niosh/topics/hexchrom. [Google Scholar]
  • 7.Code of Federal Regulations, Part 1910: Occupational Safety and Health Standards, Subpart G: Occupational Health and Environmental Control, Standard 1910.94: Ventilation, Section (c)(6): Velocity and airflow requirements.
  • 8.Code of Federal Regulations, Part 1910: Occupational Safety and Health Standards, Subpart Z: Toxic and Hazardous Substances, Standard 1910.1000: Air contaminants.
  • 9.Code of Federal Regulations, Part 1910: Occupational Safety and Health Standards, Subpart G: Occupational Health and Environmental Control, Standard 1910.1026: Chromium (IV), part (f)(1)(ii).
  • 10.American Conference of Governmental Industrial Hygienists (ACGIH) Industrial Ventilation—A Manual of Recommended Practice. 27th. Cincinnati, Ohio: ACGIH; 2010. pp. 13–134.pp. 135 [Google Scholar]
  • 11.U.S. Department of Labor. Assigned Protection Factors for the Revised Respiratory Protection Standard. Occupational Safety and Health Administration, OSHA; 2009. 3352-02. [Google Scholar]
  • 12.U.S. Department of Health and Human Services. Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health; [accessed 10/08/2015]. In-Depth Survey Report: Experimental and Numerical Research on the Performance of Exposure Control Measures for Aircraft Painting Operations, Part I (EPHB Report No. 329-12a, issued December 2011) Available at: www.cdc.gov/niosh/surveyreports/pdfs/329-12a.pdf. [Google Scholar]
  • 13.U.S. Department of Health and Human Services. Hydrocarbons, aromatic: Method 1501 (supplement issued 3/15/2003) In: Ashley KA, editor. NIOSH Manual of Analytical Methods. 4th. Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health; [accessed 6/12/2015]. DHHS (NIOSH) Publication Number 94–113. Available at: www.cdc.gov/niosh/nmam. [Google Scholar]
  • 14.U.S. Department of Health and Human Services. Particulates not otherwise regulated, total: Method 0500. In: Ashley KA, editor. NIOSH Manual of Analytical Methods. 4th. Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health; [accessed 6/12/2015]. DHHS (NIOSH) Publication Number 94–113. Available at: www.cdc.gov/niosh/nmam. [Google Scholar]
  • 15.U.S. Department of Health and Human Services. Chromium, hexavalent (by ion chromatography): Method 7605 (supplement issued 3/15/2003) In: Ashley KA, editor. NIOSH Manual of Analytical Methods. 4th. Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health; [accessed 6/12/2015]. DHHS (NIOSH) Publication Number 94–113. Available at: www.cdc.gov/niosh/nmam. [Google Scholar]
  • 16.U.S. Department of Health and Human Services. Elements by ICP: Method 7303 (supplement issued 3/15/2003) In: Ashley KA, editor. NIOSH Manual of Analytical Methods. 4th. Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health; [accessed 6/12/2015]. DHHS (NIOSH) Publication Number 94–113. Available at: www.cdc.gov/niosh/nmam. [Google Scholar]
  • 17.U.S. Department of Health and Human Services. Nitroethane: Method 2526 (supplement issued 3/15/2003) In: Ashley KA, editor. NIOSH Manual of Analytical Methods. 4th. Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health; [accessed 6/12/2015]. DHHS (NIOSH) Publication Number 94–113. Available at: www.cdc.gov/niosh/nmam. [Google Scholar]
  • 18.U.S. Department of Health and Human Services. Isocyanates, total (MAP): Method 5525 (supplement issued 3/15/2003) In: Ashley KA, editor. NIOSH Manual of Analytical Methods. 4th. Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health; [accessed 6/12/2015]. DHHS (NIOSH) Publication Number 94–113. Available at: www.cdc.gov/niosh/nmam. [Google Scholar]
  • 19.Hornung RW, Reed LD. Estimation of average concentration in the presence of nondetectable values. Appl. Occup. Environ. Hyg. 1990;5:46–51. [Google Scholar]
  • 20.Rappaport SM, Kupper LL. Quantitative Exposure Assesment. El Cerrito: Rappaport; 2008. p. 35. [Google Scholar]
  • 21.Getschman BJ. MS thesis. University of Iowa; 2013. [accessed 03/30/2015]. Evaluation of the Validity of the Inhalable and ‘Total’ Dust Concentration Ratio. Available at: http://ir.uiowa.edu/etd/2500. [Google Scholar]
  • 22.United Kingdom Health and Safety Executive. EH40/2005 Workplace Exposure Limits. 2nd. Sudbury, Sussex, England: Health and Safety Executve, HSE Books; 2011. [accessed 06/12/2015]. Available at http://www.hse.gov.uk/pubns/priced/eh40.pdf. [Google Scholar]
  • 23.American Conference of Governmental Industrial Hygienists (ACGIH) 2011 Threshold limit values for chemical substances and physical agents and biological exposure indices. Cincinnati, OH: ACGIH; 2011. [Google Scholar]

RESOURCES