Skip to main content
Materials logoLink to Materials
. 2016 Mar 5;9(3):163. doi: 10.3390/ma9030163

Polyamide Fiber Reinforced Shotcrete for Tunnel Application

Joong Kyu Jeon 1, WooSeok Kim 2,*, Gyu Yong Kim 3, Chan Ki Jeon 4
Editor: Luciano Feo
PMCID: PMC5456736  PMID: 28773293

Abstract

This study intends to establish the mechanical properties of polyamide fiber reinforced shotcrete (PAFRS) in terms of compressive and flexural strengths, in accordance with ASTM C1609/C1609M-12. The mechanical properties identified the influence of polyamide fiber content on the PAFRS strength. This study evaluated the toughness of PAFRS and proposed additional toughness level criteria to better represent organic fiber performance. In addition, the fiber rebounding rate and PAFRS performance in tunneling application were evaluated based on a tunnel application in Korea. PAFRS with 0.6%~0.8% volume content in tunneling shotcrete could significantly improve flexural ductility, toughness, and ultimate load capacity. Fiber rebounding tests exhibited a low rebounding rate (8.5%) and low fiber drop (63.5%). Therefore, PAFRS applied to a tunnel exhibited stability and constructability.

Keywords: fiber, macro, polyamide, shotcrete, tunnel

1. Introduction

Concrete and cementitious materials are vulnerable to tension developing in individual components and structures. Reinforcing materials such as steel fibers [1,2,3,4,5,6] are commonly used in concrete structures to control cracks [7,8,9,10,11,12]. The application of steel fiber reinforced shotcrete (SFRS) in tunneling construction has been part of tunneling practice since the 1970s, especially in Europe and the United States [13,14,15,16]. SFRS is characterized by ductile behavior, namely better post-cracking strength and energy absorption, where the latter is referred to as the “toughness” of a material. More specifically, toughness is the amount of energy that is absorbed before and after fracture [16].

Polyamide fiber reinforced shotcrete (PAFRS) was developed to improve mechanical properties and workability. The detailed manufacturing process has been described in other documents [17,18]. A comparison of 0.47 m diameter and 30 mm long polyamide (PA) fiber to 1.0 mm × 0.5 mm rectangular and 42 mm long polypropylene (PP) fiber [19] shows that 650 MPa tensile strength of PA fiber is higher than 550 MPa of PP fiber, though PA fiber (3 GPa) has less elastic modulus than PP fiber (8.2 GPa). Note also that a higher density of PA fiber (1.14 g/cm3) compared to PP fiber (0.9–0.92 g/cm3) is advantageous because higher density of PA fiber prevents the fiber from floating in the cement matrix.

Compared to steel fibers, PA fiber has lower weight density, which prevents the fiber from sinking down in the cement matrix and improves the durability without corrosion. Steel fibers may sometimes induce a mixing problem that prevents a uniform distribution of fibers in concrete [20]. The improved mechanical and mixing properties and adhesion characteristics of PA fiber lead to improved workability and less rebounding during spouting of shotcrete.

The objective of this study is to establish PAFRS mechanical properties in terms of compressive and flexural strengths, in accordance with ASTM C1609/C1609M-12 [21]. The mechanical properties reveal the influence of PA fiber content on the PAFRS strength. This study evaluated the toughness of PAFRS using the Morgan level [14] and proposed additional toughness level criteria to better represent organic fiber performance. In addition, based on PAFRS application in Korea, the rebounding rate and performance in a tunneling application were evaluated. PA fibers in tunneling shotcrete significantly improved flexural ductility, toughness, and ultimate load capacity.

2. Characterization of PAFRS Flexural Strength

Flexural strength of PAFRSs can be tested in accordance with ASTM C1609/C1609M-12 [21]. As in Figure 1, this study identified two peak loads: (1) the first-peak load (P1) on the load-deflection curve, which was caused by crack initiation of the specimen; and (2) the second-peak load (P2) on the load-deflection curve when the PA fibers reached the ultimate strength. Corresponding strengths and deflections are denoted as f1 and δ1 for P1 and f2 and δ2 for P2, respectively. Residual loads (P600D and P150D) and strength (f600D and f150D) at a net deflection of L/600 and L/150 (L = clear span) were measured for a beam with a depth of d (=100 mm in Figure 2a). Toughness (T150D) and equivalent flexural strength ratio (RT,150D) at a net deflection of L/150 (=300 mm in Figure 2a) were also identified. Flexural strength of f1 and f2, equivalent bending strength of fe and equivalent flexural strength ratio of RT,150D were computed as follows:

fi=PiLbd2 (1)
fe=AbLδ150bd2 (2)
RT,150D=fife×100  (%)=150T150Df1bd2×100  (%) (3)

where Pi = ith peak load at δi; L = clear span length (=300 mm); b and d = beam cross-section width and depth at the fracture surface, respectively; Ab = area under the load-deflection curves up to δ150 (N·mm); and δ150 = deflection of L/150 (=2.0 mm).

Figure 1.

Figure 1

Typical load-deflection responses of FRC.

Figure 2.

Figure 2

(a) Specimen geometry for bending test; (b) test set-up picture of bending test; (c) slump test; (d) compressive test; (e) direct tensile test; (f) fracture test.

Based on the deflection (δ1) at the first-peak load, three additional points were investigated at 3δ1, 5.5δ1, and 10.5δ1 as per ASTM C1018-97 [22]. The current ASTM standard [21] specifies δ1, δp (deflection at the peak load regardless of the first-peak or second-peak), L/600 and L/150. However, PAFRS occasionally exhibits a larger second peak than the first peak depending on the PA fiber volume content. Thus, this study clearly stipulated pre-(1st peak) and post(2nd peak)-cracking strengths. Also, PAFRS displays yielding after cracking before the PA fiber reaches its ultimate strength, similar to hyper-elastic materials. Thus, additional points at 3δ1, 5.5δ1, and 10.5δ1 were used in this study.

3. PA Fiber Volume Content Influence on PAFRS Mechanical Properties

The PAFRS specimens were prepared with varying PA fiber content ratios from 0.0% to 1.5%. Detailed shotcrete mix design of water to cement ratio (W/C), sand to aggregate ratio (S/a), water (W), cement (C), fly ash (FA), sand (S), gravel (G), and water-reducing admixture (AD) is presented in Table 1. The PAFRS was tested for slump, bending strength, direct tensile strength, and fracture energy, as shown in Figure 2. A bending test was performed in accordance with ASTM C1609/C1609M-12 [21]. A rectangular beam was saw-cut to dimensions of 100 mm × 100 mm × 400 mm. To carry out compressive tests, a φ 100 mm × 200 mm cylindrical specimen was used. A direct tensile test was conducted used a dog-bone shaped specimen. For a fracture energy test, a rectangular specimen of 100 mm × 100 mm × 400 mm, which is the same as to the specimen employed in the bending strength test, was used and the test procedure followed RILEM TCS [23]. The obtained test results with respect to varying PA fiber contents are tabulated in Table 2.

Table 1.

Shotcrete mix design.

Types Fiber Content (vol %) W/C (%) S/a (%) Unit Weight (kg/m3) AD (B * %)
W C FA S G
Plain - 40 44.4 163 326 82 749 938 0.3
PA-0.50 0.50 40 44.4 163 326 82 749 938 1.0
PA-0.75 0.75 40 55.0 180 360 90 904 740 1.0
PA-1.00 1.00 40 55.0 180 360 90 904 740 1.2
PA-1.25 1.25 40 55.0 188 376 94 883 722 1.6
PA-1.50 1.50 40 55.0 188 418 104 857 701 1.7

* weight percentage to binder.

Table 2.

PAFRS mechanical properties.

Specimen Slump (mm) Compressive Strength (MPa) Elastic Modulus (MPa) Direct Tensile Test (MPa) Bending Strength (MPa) Equivalent Bending Strength (MPa) Fracture Energy (N·m/m2)
Plain 150 44.94 30,119 - 6.42 - 908.45
PA-0.50 155 42.86 28,930 2.00 6.38 4.22 4010.66
PA-0.75 140 43.69 25,784 1.60 7.76 5.94 5674.95
PA-1.00 130 47.44 28,783 2.30 7.13 7.05 7286.54
PA-1.25 140 49.82 23,194 2.48 8.64 6.57 8750.07
PA-1.50 130 50.35 23,357 2.63 8.85 7.22 10,132.19

3.1. Compressive Strength and Elastic Modulus

As presented in Figure 3, compressive strength tests were performed for PAFRS specimens with varying PA fiber content from 0.0% to 1.5%. It was clearly observed that the slope or elastic modulus of PAFRS decreased as the PA fiber content increased. Obtained maximum compressive strengths with respect to PA fiber content from 0.0% to 1.5% are shown in Table 2. However, the maximum compressive strengths of PA-0.5 and PA-0.75 (42.86 and 43.69 MPa) were less than that of Plain (44.94 MPa), but those of PA-1.00, PA-1.25 and PA-1.50 (47.44, 49.82 and 50.35 MPa) were larger than that of Plain. This phenomenon is commonly encountered in fiber-reinforced concrete.

Figure 3.

Figure 3

Compressive stress–strain curves of PAFRSs with varying PA contents.

The elastic moduli of the PAFRS specimens slightly decreased compared to those of the plain specimen. The elastic modulus of the plain shotcrete mix was larger than those of PAFRSs. The elastic moduli of PAFRSs were not proportional to the PA fiber content. The order of magnitude of the PAFRS elastic modulus was 0.5% > 1.0% > 0.75% >1.5% > 1.25% in terms of PA fiber content.

3.2. Direct Tensile Strength Test

Direct tensile strength test results are presented in Figure 4. It was observed that the shotcrete toughness was significantly improved by inclusion of PA fibers. The tensile strength tended to linearly increase as the PA fiber content increased, except for the PA-0.75 specimen. The maximum tensile strength is shown in Table 2. In Figure 4, the 1st peak tensile strengths were 2.00, 1.60, 2.48, 2.30, and 2.08 MPa for PA-0.5, 0.75, 1.25, 1.0, and 1.5. The 2nd peak tensile strengths were 0.82, 1.16, 2.26, 0.73, and 2.63 MPa for PA-0.5, 0.75, 1.25, 1.0, and 1.5. All specimens exhibited larger first peak tensile strengths than the second peak strengths except for the PA-1.5 specimen. The PA-1.5 specimen exhibited a larger second peak tensile strength than the first peak tensile strength. It was expected that the PA fiber content generally increased the second peak strength.

Figure 4.

Figure 4

Direct tensile test results.

3.3. Flexural Bending Test Results

Flexural bending test results are presented in Figure 5. Similar to the direct tensile test results, the flexural bending strengths were significantly improved by PA fibers. As aforementioned, the PAFRS exhibited two distinct peaks: (1) the first peak was induced by the initiation of the crack; and (2) the second peak was reached as the fiber reached its ultimate strength.

Figure 5.

Figure 5

Load-deflection curves of flexural bending tests.

Detailed flexural responses at various points are presented in Figure 6 and Table 3. As shown in Figure 6, it was clearly observed that the bending strength and toughness increased as the PA fiber content increased. Also, the second peak tended to increase as the PA fiber content increased.

Figure 6.

Figure 6

Figure 6. (a) Bending strength (first and second peaks); (b) toughness (first and second peaks); (c) bending strength (3δ, 5.5δ, 10.5δ); (d) toughness (3δ, 5.5δ, 10.5δ); (e) bending strength (L/600, L/150, L/100); (f) toughness (L/600, L/150, L/100).

Table 3.

Average value of flexural responses of PAFRS.

Specimen First-Peak 1 5.5δ1 10.5δ1
P1(N) δ1 (mm) f1 (MPa) T1 (Joule) P3δ(N) δ3δ (mm) f3δ (MPa) T3δ (Joule) P5.5δ(N) δ5.5δ (mm) f5.5δ(MPa) T5.5δ(Joule) P10.5δ(N) δ10.5δ (mm) f10.5δ(MPa) T10.5δ(Joule)
Plain 21,391 0.072 6.42 0.793 - 0.215 - - - 0.394 - - - 0.751 - -
PA-0.50 21,251 0.057 6.38 0.664 14,415 0.170 4.32 2.735 13,069 0.312 3.92 4.547 13,594 0.595 4.19 8.275
PA-0.75 25,872 0.079 7.76 1.028 15,918 0.237 4.78 4.281 15,817 0.435 4.75 7.221 19,429 0.830 5.83 14.231
PA-1.00 23,769 0.042 7.13 0.514 17,824 0.126 5.35 2.297 15,952 0.230 4.79 3.973 18,566 0.440 5.57 7.581
PA-1.25 28,789 0.069 8.64 0.992 18,908 0.206 5.67 4.040 17,783 0.377 5.34 6.993 22,545 0.720 6.76 14.020
PA-1.50 29,506 0.087 8.85 1.285 22,914 0.260 6.87 5.550 20,503 0.476 6.15 10.257 24,445 0.909 7.33 19.860
Specimen Second-Peak L /600 (=0.5 mm) L /150 (=2.00 mm) L/100 (=3.00 mm)
P2 (N) δ2 (mm) f2 (MPa) T2 (Joule) P600100 (N) f600100 (MPa) T600 (Joule) P150100 (N) f150100 (MPa) T150 (Joule) RT,150100 (%) P100100 (N) f100100 (MPa) T100 (Joule)
Plain - - - - - - - - - - - - - -
PA-0.50 15,928 1.117 4.78 16.180 13,129 3.94 6.975 11,035 3.31 28.126 66.2 7686 2.31 37.100
PA-0.75 23,102 1.788 6.93 34.725 16,534 4.96 8.276 22,564 6.77 39.575 76.5 16,959 5.09 59.614
PA-1.00 28,022 1.535 8.41 34.313 19,409 5.82 8.738 25,887 7.77 46.979 98.8 13,045 3.91 66.477
PA-1.25 25,697 1.273 7.71 27.564 19,805 5.94 9.342 18,226 5.47 43.712 75.9 12,113 3.63 58.539
PA-1.50 26,886 1.428 8.07 33.347 20,246 6.07 10.683 24,553 7.37 48.141 81.6 15,527 4.66 68.313

4. Field and Laboratory Fabricated PAFRS

For tunnel application of PAFRS, field and laboratory specimens were fabricated according to the approach discussed earlier, and the flexural performance was evaluated in accordance with ASTM C1609/C1609M-12 [21] and the Morgan level [14]. First, appropriate PA fiber content was determined based on the bending strength in Equation (1) and equivalent bending strength in Equation (2), since compressive strengths of PAFRS in Figure 3 were far higher than the minimum limit in Table 4. There are four applicable Korean tunnel design guidelines for fiber-reinforced shotcrete, listed in Table 4. All four design guidelines specify the minimum compressive strength, bending strength, and equivalent bending strength. For this study, 0.6%~0.8% of PA fiber content was determined to be the optimal content based on Table 3, and both laboratory and field specimens were then prepared. Shotcrete mix design such as the maximum gravel size (Gmax), ratio of water to cement (W/C) and sand to aggregate (S/a), unit weight of water (W), cement (C), crushed sand (CS), gravel (G), polyamide fiber (PA). and water-reducing admixture (AD) is presented in Table 5. The test specimens were fabricated from tunnel lining shotcrete during construction as in Figure 7a and dimensions of specimens and the test setup were slightly modified to meet the Korean standard and are presented in Figure 7b. For each shotcrete mix design, three specimens were prepared and tested.

Table 4.

Korean design guidelines for tunnel shotcrete.

Property Unit Korean Highway Design Specifications (2012) [24] Korean Railroad Design Specifications (2011) [25] Korean High Speed Railroad Design Specifications (2005) [26] Korean Tunnel Design Specifications (2007) [27]
Compressive Strength MPa >10 (1 day) >10 (1 day) >10 (1 day) >10 (1 day)
>21 (28 days) >21 (28 days) >21 (28 days) >21 (28 days)
Bending Strength MPa >4.4 (28 days) >4.5 (28 days) >4.5 (28 days) >4.5 (28 days)
Equivalent Bending Strength MPa - >3.0 (28 days) >3.0 (28 days) >3.0 (28 days)

Table 5.

Shotcrete mix design.

Specimen Gmax (mm) W/C (%) S/a (%) Unit Weight (kg/m3) AD (B *** %)
W C S CS G PA
PA-0.6L * 10 43.5 60 211 485 472 463 617 6.84 0.9
PA-0.6F ** 10 43.5 60 211 485 472 463 617 6.84 1.0
PA-0.7L 10 43.5 60 211 485 472 463 617 7.98 1.0
PA-0.7F 10 43.5 60 211 485 472 463 617 7.98 1.1
PA-0.8L 10 43.8 60 211 482 385 578 651 9.12 1.1
PA-0.8F 10 43.8 60 211 482 385 578 651 9.12 1.2

* PA-xxL: mixed in laboratory; ** PA-xxF: mixed in field; *** weight percentage to binder.

Figure 7.

Figure 7

(a) Shotcrete specimen fabrication; (b) specimen geometry and test setup.

Bending and equivalent bending strength test results from the laboratory and field are presented in Table 6. All PAFRS specimens fabricated in both laboratory and field exhibited higher bending and equivalent bending strengths (see Table 7) than the minimum limits in Table 4. Load-deflection relationship of all specimens was also investigated, as in Figure 8. The load-deflection curves of PAFRS specimens were similar to each other due to the small variation of PA fiber content. Detailed PAFRS bending strength and toughness with respect to varying fiber content are presented in Figure 9. The average flexural responses at δ1, 3δ1, 5.5δ1, L/600, 10.5δ1, and L/150 are summarized in Table 7. As shown in the results, the quality and performance of field specimens were similar to those of laboratory specimens.

Table 6.

Bending and equivalent bending strength.

Specimen Bending Strength (MPa) Equivalent Bending Strength (MPa)
SP-1 SP-2 SP-3 Avg. SP-1 SP-2 SP-3 Avg.
PA-0.6L 6.01 6.25 5.70 5.99 3.63 3.72 3.38 3.57
PA-0.6F 6.18 5.97 5.78 5.98 3.33 3.59 3.46 3.46
PA-0.7L 6.02 6.48 5.89 6.13 3.60 3.32 3.93 3.62
PA-0.7F 5.39 4.97 5.13 5.16 3.83 3.32 3.67 3.61
PA-0.8L 6.16 5.98 6.13 6.09 3.41 3.58 3.74 3.57
PA-0.8F 5.49 5.50 5.65 5.55 3.63 3.42 3.76 3.60

PA-xxL: mixed in laboratory; PA-xxF: mixed in field.

Table 7.

Average value of flexural responses of PAFRS.

Specimen First Peak 1 5.5δ1
P1 (N) δ1 (mm) f1 (MPa) T1 (Joule) P3δ (N) δ3δ (mm) f3δ (MPa) T3δ (Joule) P5.5δ (N) δ5.5δ (mm) f5.5δ (MPa) T5.5δ (Joule)
PA-0.6L 44,921 0.073 5.99 1.757 32,854 0.218 4.38 7.382 24,467 0.399 3.26 12.275
PA-0.6F 44,816 0.070 5.98 1.710 35,242 0.210 4.70 7.275 24,408 0.385 3.25 12.522
PA-0.7L 45,985 0.071 6.13 1.753 34,171 0.214 4.56 7.428 23,599 0.392 3.15 12.532
PA-0.7F 38,719 0.070 5.16 1.411 28,551 0.210 3.81 6.065 23,710 0.384 3.16 10.424
PA-0.8L 45,685 0.087 6.09 2.027 30,923 0.262 4.12 8.493 24,743 0.481 3.30 14.365
PA-0.8F 41,598 0.065 5.55 1.359 28,009 0.195 3.73 5.811 21,249 0.357 2.83 9.681
Specimen L/600 (=0.75 mm) 10.5δ1 Second Peak L/150 (=3.00 mm)
P600100 (N) f600100 (MPa) T600 (Joule) P10.5δ (N) δ10.5δ (mm) f10.5δ (MPa) T10.5δ (Joule) P2 (N) δ2 (mm) f2 (MPa) T2 (Joule) P150100 (N) f150100 (MPa) T150 (Joule) RT,150100 (%)
PA-0.6L 31,106 4.15 22.194 31,266 0.763 4.17 22.622 33,928 1.187 4.52 36.389 15,444 2.06 80.423 59.7
PA-0.6F 26,294 3.51 21.551 26,171 0.735 3.49 21.144 29,159 1.301 3.89 37.141 18,929 2.52 77.813 57.9
PA-0.7L 29,118 3.88 22.041 29,120 0.748 3.88 22.151 32,098 1.084 4.28 32.564 17,093 2.28 81.402 59.3
PA-0.7F 28,809 3.84 19.915 28,582 0.734 3.81 19.711 32,983 1.351 4.40 38.458 17,129 2.28 81.163 69.8
PA-0.8L 28,157 3.75 21.431 29,421 0.918 3.92 26.217 31,179 1.148 4.16 33.159 17,623 2.35 80.382 58.7
PA-0.8F 25,391 3.39 18.639 24,518 0.682 3.27 16.936 30,708 1.629 4.09 43.474 22,904 3.05 81.039 64.9

Figure 8.

Figure 8

(a) PA-0.6L; (b) PA-0.6F; (c) PA-0.7L; (d) PA-0.7F; (e) PA-0.8L; (f) PA-0.8F.

Figure 9.

Figure 9

(a) Bending strength (first and second peaks); (b) toughness (first and second peaks); (c) bending strength (3δ, 5.5δ, 10.5δ); (d) toughness (3δ, 5.5δ, 10.5δ); (e) bending strength (L/600, L/150); (f) toughness (L/600, L/150).

Based on the load-deflection curves in Figure 8, Morgan levels [14] for each specimens were determined to identify the toughness performance level, as presented in Table 8. The Morgan level evaluates the strength of steel fiber reinforced shotcrete at δ1 L/600 and L/150. However, PAFRSs exhibit different load-deflection history compared to SFRCs, although the Morgan level was originally suggested for SFRCs. After the first peak in Figure 8, the load-deflection curve drops until the PA fiber takes the load, then starts to increase up to the second peak or ultimate fiber capacity. Figure 9a shows that the second peaks of all specimens were larger than or equal to the first peak. As shown in Figure 8, some of the load-deflection curves of PAFRS specimens at L/600 after the first peak dropped below the Morgan level IV. However, the load-deflection curves increase again, beyond level IV. Thus, this study evaluated the specimen capacity in terms of toughness. The toughness of each specimen was compared to the toughness specified by Morgan load-deflection curves. The toughness Morgan levels [14] of all specimens were Level IV while the strength Morgan levels of all specimens were Level III.

Table 8.

Morgan level based on strength and toughness.

Method Basis Specimen No. PA-0.6L PA-0.6F PA-0.7L PA-0.7F PA-0.8L PA-0.8F
Strength 1 IV IV IV III III III
2 IV IV III IV IV III
3 III III IV IV IV IV
Min. Level III III III III III III
Toughness 1 IV IV IV IV IV IV
2 IV IV IV IV IV IV
3 IV IV IV IV IV IV
Min. Level IV IV IV IV IV IV

5. PAFRS Shotcrete Application Results

The PAFRS of PA-0.7F in Table 5, Table 6 and Table 7 was conservatively selected and was used in tunnel shotcrete to evaluate shotcrete stresses and rebounding rate for constructability, as presented in Figure 10. For comparison, steel fiber (0.5 mm diameter, 30 mm long and hooked type) reinforced shotcrete was also applied at the same construction site. Also, four sample cores with an average thickness of 168 mm were collected to confirm the shotcrete thickness and contact to the rock. The flexural strength of the specimen was satisfactory compared to the tunnel codes, as presented in Table 7.

Figure 10.

Figure 10

Shotcrete spouting and rebounding test.

Also, the flexural stress limits by Korean Tunnel Design Specifications [27] were checked. The measured shotcrete stresses are presented in Table 9. Both PA and steel fiber reinforced shotcrete satisfied the allowable limits (allowable flexural compressive stress = 8.4 MPa, allowable flexural tensile stress = 0.60 MPa). The maximum compressive and tensile stresses of PA shotcrete were observed at the crown and the East springline, respectively, but the stress was only 2.5% and 10% with respect to the allowable stresses.

Table 9.

Measured shotcrete stresses.

Location Springline (East) Springline (West) Crown
Fiber Max. Flexural Compressive Stress (MPa) Max. Flexural Tensile Stress (MPa) Max. Flexural Compressive Stress (MPa) Max. Flexural Tensile Stress (MPa) Max. Flexural Compressive Stress (MPa) Max. Flexural Tensile Stress (MPa)
PA - 0.06 0.19 0.06 0.21 0.05
Steel - 0.37 0.01 0.23 0.36 0.27

Finally, PA shotcrete rebounding was checked to identify the fiber ratio included and dropped in the final shotcrete. The test procedure is presented in Figure 11. The rebounding test results are presented in Table 10. The average rebounding rate was 8.5%, which is less than the limit of 12.5% designated by Korean Tunnel Design Specifications [27]. The average dropped fiber rate was 63.5%. The average fiber content rate was 103.4%.

Figure 11.

Figure 11

PA shotcrete rebounding test procedure.

Table 10.

PAFRS rebounding test results.

Field Test Spouting Volume (m3) Spouting Weight (kg) Fiber Content (kg/m3) Rebounded Weight (kg) Rebounded Rate (%) Fiber Content * (%) Dropped Fiber ** (%)
1st 0.3 682.2 8.00 59.4 8.71 103.55 62.83
2nd 1.0 2274.0 8.00 188.8 8.30 103.24 64.23

* Fiber Content (%)=Theoretical Number of Fibers in ShotcreteActual Number of Fibers in Shotcrete×100; ** Dropped Fiber (%)=Theoretical Number of Fibers in ReboundedActual Number of Fibers in Rebounded×100

6. Conclusions

This study performed laboratory tests to investigate the influence of PA fiber content and to determine the appropriate PA fiber content for tunnel shotcrete application. As expected, PAFRS flexural performance improved as PA fiber contents increased from 0.5% to 1.5%. Since the experimental results of all specimens exhibited far higher flexural performance than the required levels, 0.6~0.8% of PA fiber content was selected for a field application. In this study, three PAFRS specimens for each PA fiber content were prepared in the laboratory and field to compare the flexural performance and toughness. Finally, PA-0.7 was selected and used in tunnel shotcrete. In the field, steel fiber reinforced shotcrete was also used for comparison. Both PA and steel fiber reinforced shotcrete satisfied the allowable stress limits by Korean Tunnel Design Specifications [27]. Also, fiber rebounding tests exhibited the constructability and quality of PA shotcrete, based on its low rebounding rate (8.5%) and low fiber drop (63.5%). Based on these results, the fiber content in the shotcrete was expected to be 103.4% Therefore, PA shotcrete applied in a tunnel exhibited stability and constructability.

Acknowledgments

This research was supported by a grant from the Construction Technology Research Project (Development of impact/blast resistant HPFRCC (High Performance Fiber Reinforced Cementitious Composites) and evaluation technique thereof (13SCIPS02)) funded by the Ministry of Land, Infrastructure, and Transport and research fund of Chungnam National University.

Author Contributions

Joong Kyu Jeon planned and performed the laboratory and field experimental tests. WooSeok Kim analyzed the experiments, drafted the manuscript, and revised it. Gyu Yong Kim performed laboratory tests. Chan Ki Jeon guided this study and provided valuable comments.

Conflicts of Interest

The authors declare no conflict of interest.

References

  • 1.Kim D.J., Kang S.H., Ahn T. Mechanical characterization of high-performance steel-fiber reinforced cement composites with self-healing effect. Materials. 2014;7:508–526. doi: 10.3390/ma7010508. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 2.Kim D.J., Park S.H., Ryu G.S., Koh K.T. Comparative flexural behavior of hybrid ultra high performance fiber reinforced concrete with different macro fibers. Constr. Build. Mater. 2011;25:4144–4155. doi: 10.1016/j.conbuildmat.2011.04.051. [DOI] [Google Scholar]
  • 3.Mindess S., Chen L., Morgan D.R. Determination of the first-crack strength and flexural toughness of steel fiber-reinforced concrete. Adv. Cem. Based. Mater. 1994;1:201–208. doi: 10.1016/1065-7355(94)90025-6. [DOI] [Google Scholar]
  • 4.Soroushian P., Elyamany H., Tlili A., Ostowari K. Mixed-mode fracture properties of concrete reinforced with low volume fractions of steel and polypropylene fibers. Cem. Concr. Compos. 1998;20:67–78. doi: 10.1016/S0958-9465(97)87390-8. [DOI] [Google Scholar]
  • 5.Song P.S., Hwang S., Sheu B.C. Strength properties of nylon- and polypropylene-fiber-reinforced concretes. Cem. Concr. Res. 2005;35:1546–1550. doi: 10.1016/j.cemconres.2004.06.033. [DOI] [Google Scholar]
  • 6.Bencardino F., Rizzuti L., Spadea G., Swamy R.N. Experimental evaluation of fiber reinforced concrete fracture properties. Compos. B Eng. 2010;41:17–24. doi: 10.1016/j.compositesb.2009.09.002. [DOI] [Google Scholar]
  • 7.Alberti M.G., Enfedaque A., Gavez J.C. On the mechanical properties and fracture behavior of polyolefin fiber-reinforced self-compacting concrete. Constr. Build. Mater. 2014;55:274–288. doi: 10.1016/j.conbuildmat.2014.01.024. [DOI] [Google Scholar]
  • 8.Yap S.P., Alengaram U.J., Jumaat M.Z. Enhancement of mechanical properties in polypropylene- and nylon-fibre reinforced oil palm shell concrete. Mater. Des. 2013;49:1034–1041. doi: 10.1016/j.matdes.2013.02.070. [DOI] [Google Scholar]
  • 9.Zhu J., Zhu M., Han N., Liu W., Xing F. Electrical and mechanical performance of carbon fiber-reinforced polymer used as the impressed current anode material. Materials. 2014;7:5438–5453. doi: 10.3390/ma7085438. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 10.Nishiwaki T., Kwon S., Homma D., Yamada M., Mihashi H. Self-healing capability of fiber-reinforced cementitious composites for recovery of watertightness and mechanical properties. Materials. 2014;7:2141–2154. doi: 10.3390/ma7032141. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 11.Bencardino F., Rizzuti L., Spadea G., Swamy R.N. Implications of test methodology on postcracking and fracture behaviour of steel fibre reinforced concrete. Compos. B Eng. 2013;46:31–38. doi: 10.1016/j.compositesb.2012.10.016. [DOI] [Google Scholar]
  • 12.Kant M., Penumadu D. Dynamic mechanical characterization for nonlinear behavior of single carbon fibers. Compos. A. 2014;66:201–208. doi: 10.1016/j.compositesa.2014.07.019. [DOI] [Google Scholar]
  • 13.Franzen T. Shotcrete for underground support; a state-of-the-art report with focus on steel-fibre reinforcement. Tunn. Undergr. Space Technol. 1992;7:383–391. doi: 10.1016/0886-7798(92)90068-S. [DOI] [Google Scholar]
  • 14.Morgan D.R., Chen L., Beaupre D. Toughness of fibre reinforced shotcrete; Proceedings of the Shotcrete For Underground Support VII; Buchen-Telfs, Telfs-Buchen, Austria. 11–15 June 1995; pp. 66–87. [Google Scholar]
  • 15.Jeng F., Lin M.-L., Yuan S.-C. Performance of toughness indices for steel fiber reinforced shotcrete. Tunn. Undergr. Space Technol. 2002;17:69–82. doi: 10.1016/S0886-7798(01)00065-7. [DOI] [Google Scholar]
  • 16.Cengiz O., Turanli L. Comparative evaluation of steel mesh, steel fibre and high performance polypropylene fibre reinforced shotcrete in panel test. Cem. Concr. Res. 2004;34:1357–1364. doi: 10.1016/j.cemconres.2003.12.024. [DOI] [Google Scholar]
  • 17.Yoon J.H., Jeon J.K., Kim Y.K., Chung J.M. A feasibility study on polyamide fiber reinforced shotcrete for rock support in a tunnel; Proceedings of the World Tunnel Congress 2013; Geneva, Switzerland. 31 May–5 June 2013; pp. 1–8. [Google Scholar]
  • 18.Jeon J.K., Kim W., Jeon C.K., Kim J.C. Processing and mechanical properties of macro polyamide fiber reinforced concrete. Materials. 2015;7:7634–7652. doi: 10.3390/ma7127634. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 19.Elasto Plastic Concrete. [(accessed on 8 January 2014)]. Available online: http://www.elastoplastic.com.
  • 20.Choi E., Kim D., Chung Y., Nam T. Bond-slip characteristics of SMA reinforcing fibers obtained by pull-out test. Mater. Res. Bull. 2014;58:28–31. doi: 10.1016/j.materresbull.2014.04.060. [DOI] [Google Scholar]
  • 21.Structural Test Method for Flexural Performance of Fiber Reinforced Concrete (Using Beam with Third Point Loading) American Society of Testing and Materials; West Conshohocken, PA, USA: 2006. pp. 1–8. ASTM C 1609/C1609M-12. [Google Scholar]
  • 22.Structural Test Method for Flexural Toughness and First Crack Strength of Fiber Reinforced Concrete (Using Beam with Third Point Loading) American Society of Testing and Materials; West Conshohocken, PA, USA: 1998. pp. 514–515. ASTM C1018-97. [Google Scholar]
  • 23.RILEM TCS Determination of the fracture energy of mortar and concrete by means of three-point bend tests on notched beams. Mater. Struct. 1985;18:285–290. [Google Scholar]
  • 24.Tunnel. Ministry of Land, Infrastructure and Transport; Sejoing, Korea: 2012. Korean Highway Design Specifications. [Google Scholar]
  • 25.Tunnel. Korea Rail Network Authority; Daejeon, Korea: 2011. Korean Railroad Design Specifications. [Google Scholar]
  • 26.Tunnel. Korea Rail Network Authority; Daejeon, Korea: 2005. Korean High Speed Railroad Design Specifications. [Google Scholar]
  • 27.Shotcrete. Ministry of Land, Infrastructure and Transport; Sejoing, Korea: 2007. Korean Tunnel Design Specifications. [Google Scholar]

Articles from Materials are provided here courtesy of Multidisciplinary Digital Publishing Institute (MDPI)

RESOURCES