Skip to main content
Applied Microbiology logoLink to Applied Microbiology
. 1968 Feb;16(2):291–295. doi: 10.1128/am.16.2.291-295.1968

Microbiological Safety Evaluation of an Industrial Refuse Incinerator

Manuel S Barbeito 1, Gardner G Gremillion 1
PMCID: PMC547398  PMID: 4967068

Abstract

An industrial refuse incinerator was tested to determine minimal operating temperatures required to prevent release of viable microorganisms into the atmosphere. A liquid suspension of Bacillus subtilis var. niger spores was disseminated into the firebox as an aerosol, and dry spores mixed with animal bedding were dumped into the firebox. The minimal requirement for wet spores was 575 F (302 C) for the firebox air temperature and 385 F (196 C) for the firebrick refractory lining. When dry spores were used, these temperatures were 700 and 385 F (371 and 196 C), respectively.

Full text

PDF
291

Images in this article

Selected References

These references are in PubMed. This may not be the complete list of references from this article.

  1. Barbeito M. S. Emergency disinfection of operating room and patient ward with beta-propiolactone. Hospitals. 1966 Mar 16;40(6):100–106. doi: 10.21236/ad0640342. [DOI] [PubMed] [Google Scholar]
  2. MILLER W. S., SCHERFF R. A., PIEPOLI C. R., IDOINE L. S. Physical tracers for bacterial aerosols. Appl Microbiol. 1961 May;9:248–251. doi: 10.1128/am.9.3.248-251.1961. [DOI] [PMC free article] [PubMed] [Google Scholar]
  3. REITMAN M., FRANK M. A., Sr, ALG R., MILLER W. S. Modifications of the high-speed safety blendor. Appl Microbiol. 1954 May;2(3):173–173. doi: 10.1128/am.2.3.173-173.1954. [DOI] [PMC free article] [PubMed] [Google Scholar]
  4. WEDUM A. G. LABORATORY SAFETY IN RESEARCH WITH INFECTIOUS AEROSOLS. Public Health Rep. 1964 Jul;79:619–633. [PMC free article] [PubMed] [Google Scholar]

Articles from Applied Microbiology are provided here courtesy of American Society for Microbiology (ASM)