Abstract
An industrial refuse incinerator was tested to determine minimal operating temperatures required to prevent release of viable microorganisms into the atmosphere. A liquid suspension of Bacillus subtilis var. niger spores was disseminated into the firebox as an aerosol, and dry spores mixed with animal bedding were dumped into the firebox. The minimal requirement for wet spores was 575 F (302 C) for the firebox air temperature and 385 F (196 C) for the firebrick refractory lining. When dry spores were used, these temperatures were 700 and 385 F (371 and 196 C), respectively.
Full text
PDF




Images in this article
Selected References
These references are in PubMed. This may not be the complete list of references from this article.
- Barbeito M. S. Emergency disinfection of operating room and patient ward with beta-propiolactone. Hospitals. 1966 Mar 16;40(6):100–106. doi: 10.21236/ad0640342. [DOI] [PubMed] [Google Scholar]
- MILLER W. S., SCHERFF R. A., PIEPOLI C. R., IDOINE L. S. Physical tracers for bacterial aerosols. Appl Microbiol. 1961 May;9:248–251. doi: 10.1128/am.9.3.248-251.1961. [DOI] [PMC free article] [PubMed] [Google Scholar]
- REITMAN M., FRANK M. A., Sr, ALG R., MILLER W. S. Modifications of the high-speed safety blendor. Appl Microbiol. 1954 May;2(3):173–173. doi: 10.1128/am.2.3.173-173.1954. [DOI] [PMC free article] [PubMed] [Google Scholar]
- WEDUM A. G. LABORATORY SAFETY IN RESEARCH WITH INFECTIOUS AEROSOLS. Public Health Rep. 1964 Jul;79:619–633. [PMC free article] [PubMed] [Google Scholar]