Skip to main content
NIST Author Manuscripts logoLink to NIST Author Manuscripts
. Author manuscript; available in PMC: 2018 Aug 1.
Published in final edited form as: Int J Refrig. 2017 May 19;80:52–65. doi: 10.1016/j.ijrefrig.2017.05.014

Refrigerant Performance Evaluation Including Effects of Transport Properties and Optimized Heat Exchangers

Riccardo Brignoli a, J Steven Brown b, H Skye a, Piotr A Domanski a,*
PMCID: PMC5600208  NIHMSID: NIHMS899060  PMID: 28924306

Abstract

Preliminary refrigerant screenings typically rely on using cycle simulation models involving thermodynamic properties alone. This approach has two shortcomings. First, it neglects transport properties, whose influence on system performance is particularly strong through their impact on the performance of the heat exchangers. Second, the refrigerant temperatures in the evaporator and condenser are specified as input, while real-life equipment operates at imposed heat sink and heat source temperatures; the temperatures in the evaporator and condensers are established based on overall heat transfer resistances of these heat exchangers and the balance of the system.

The paper discusses a simulation methodology and model that addresses the above shortcomings. This model simulates the thermodynamic cycle operating at specified heat sink and heat source temperature profiles, and includes the ability to account for the effects of thermophysical properties and refrigerant mass flux on refrigerant heat transfer and pressure drop in the air-to-refrigerant evaporator and condenser. Additionally, the model can optimize the refrigerant mass flux in the heat exchangers to maximize the Coefficient of Performance. The new model is validated with experimental data and its predictions are contrasted to those of a model based on thermodynamic properties alone.

1. Introduction

Since the mid-1980s, the refrigeration and air-conditioning sector has devoted a significant effort to identify and implement refrigerants that address environmental problems of stratospheric ozone depletion and global warming. The process of selecting the best refrigerants involves consideration of several criteria (McLinden and Didion, 1987) with the Coefficient of Performance (COP) being of dominant importance once other ‘gate’ attributes (e.g., chemical stability or lack of toxicity) have been accepted.

Domanski and McLinden (1992) discussed the merits and shortcomings of various methods for predicting the performance of refrigerants operating in vapor compression cycles. They placed these methods in five categories from theoretical analysis to laboratory equipment testing: (1) Carnot cycle analysis, (2) simple methods based on fundamental observations and principles, (3) theoretical and semi-theoretical cycle analysis, (4) detailed equipment simulation models, and (5) laboratory tests of the vapor compression equipment. In the refrigerant selection process, great reliance is placed on methods of category (3) for selecting best candidate fluids for further examination either by more sophisticated models or tests in actual equipment.

The evaluation methods of category (3) range from idealized thermodynamic cycle analysis to simulations including some forms of representation of a practical cycle, e.g., non-isentropic compression, refrigerant pressure drops in the heat exchangers and connecting tubing, or the temperature difference between fluids exchanging heat. Most often, category (3) methods employ the refrigerant’s thermodynamic properties alone and perform simulations based on specified evaporator saturation temperature and superheat, condenser saturation temperature and subcooling, and compressor isentropic efficiency [e.g., CYCLE_D model (Brown et al., 2012)]. These models are very popular among refrigeration practitioners because they are simple and easy to use.

The CYCLE11 model (Domanski and McLinden, 1992) is more advanced conceptually than CYCLE_D-type models; instead of using evaporator and condenser saturation temperatures specified as input, CYCLE11 establishes the thermodynamic cycle–including the saturation temperatures–using temperature profiles of heat-transfer fluids (HTFs) in the evaporator and condenser and respective mean effective temperature differences between these fluids and the refrigerant, ΔThx. This approach allows for accounting for the effect of non-linear temperature glides of zeotropic mixtures during the evaporation and condensation processes. A simulation example with a high-glide R22/123 mixture showed a COP difference as high as 8.7 % when the nonlinearity is neglected during simulation.

The cycle simulation can be further advanced by accounting for effects of refrigerant mass flux on the heat transfer and pressure drop. These effects take place in conventional equipment (air conditioners, refrigeration systems) employing air-to-refrigerant, fined-tube evaporators and condensers, which rely on refrigerant forced-convection heat transfer. In these heat exchangers the refrigerant flows through circuits formed by tubes connected in a serpentine pattern. The designer must choose the number of parallel circuits, which determines the refrigerant mass flux in these circuits. A higher mass flux improves the refrigerant heat-transfer coefficient but also increases the refrigerant pressure drop. These two phenomena have opposite effects on the system COP; the highest COP is achieved with the mass flux that provides the best balance between the benefit of improved heat transfer and the penalty related to pressure drop.

The effect of refrigerant mass flux on two-phase heat transfer and pressure drop has been noted in the literature. Domanski and Yashar (2006) compared the performance of five different refrigerants in a vapor compression system with evaporator and condenser circuitries optimized by a learnable evolution model. They found that the COP difference between low-pressure and high-pressure fluids changes in favor of high-pressure fluids when the performance comparison is done using optimized heat exchangers as opposed to the theoretical cycle evaluation at fixed saturation temperatures in the evaporator and condenser. A related study showed high-pressure refrigerants to be the best performing fluids in condensers with optimized refrigerant circuitries (Domanski and Yashar, 2007).

Cavallini et al. (2010) introduced the ‘penalty factor’ and the ‘total temperature penalization’ (TTP) parameters that combine exergy losses due to heat transfer and pressure drop. They showed that these parameters can be used either to select the optimum number of circuits in a finned-tube condenser of fixed overall geometry and number of tubes, or to compare the refrigerants’ heat transfer performance in condensation. Brown et al. (2012) applied this approach to finned-tube evaporators. Further, Brown et al. (2014) used the ‘penalty factor’ and TTP to compare the evaporation and condensation performance of several low-GWP refrigerants. Recently, Zilio et al. (2015) compared the seasonal performance of an air-to-water heat pump working with R410A and R32. They found that a system with an optimized refrigerant circuitry in the air-to-refrigerant heat exchanger had a 5 % improved seasonal efficiency over a system with a ‘non-optimal’ circuitry design.

The present paper discusses in detail the effects of refrigerant thermophysical properties and refrigerant mass flux on refrigerant two-phase heat transfer and pressure drop. Also, the paper discusses a new cycle model, referred to as CYCLE_D-HX, which accounts for these effects and can select the optimal refrigerant heat exchanger circuity for maximizing system COP. Examples of CYCLE_D and CYCLE_D-HX simulations results are presented and contrasted.

2. Effect of Refrigerant Mass Flux on Two-Phase Heat Transfer and Pressure Drop

A pressure drop in the evaporator or condenser causes a saturation temperature drop and results in an increased mean effective temperature difference, ΔThx, between the refrigerant and the external heat transfer fluid (HTF). The refrigerant heat-transfer coefficient h also affects ΔThx; a higher h yields lower ΔThx. A decrease in condenser and evaporator ΔThx lowers the temperature lift seen by the compressor and subsequently lowers the compressor work, which improves the COP.

The functional dependencies of the refrigerant heat-transfer coefficient h and pressure drop Δp are given in Eqs. 1 and 2.

h=f(D,RSF,TPP,G,Tsat,x,q) (1)
Δp=f(D,L,RSF,TPP,G,Tsat,q) (2)

RSF stands for ‘refrigerant-side feature’ such as an in-tube insert or microfin surface, and TPP stands for ‘thermophysical property’. The heat-transfer coefficient h and pressure drop Δp are both a function of the refrigerant mass flux G, where h approximately increases proportionally to G0.8, while Δp increases approximately to G2. There is an optimum value of G that best compromises between the two opposite effects that h and Δp have on the system COP. This optimum G depends on thermodynamic and transport properties of the refrigerant, tube diameter, and refrigerant-surface features (RSF in Eqs. 2 and 3).

Figure 1 shows the dependency of h and Δp on the mass flux in evaporation for R32, a high-pressure fluid, and R1234yf, a medium-pressure fluid, at Tsat = 0 °C. We used correlations by Wojtan et al. (2005a and 2005b) and Muller-Steinhagen and Heck (1986) for generating data for h and Δp, respectively. The showed results are normalized by nominal h and Δp values for R32 at G=100 kg·m−2·s−1, hnom=3.16 kW·m−2·K−1 and Δpnom =1.26 kPa, respectively. All values are average values calculated by Eq. 3:

F=1xEnd-xStartxStartxEndf(x) (3)

where f(x) is h or Δp, xStart is the quality corresponding to the isenthalpic expansion from a condenser saturation temperature of 45 °C and 3 K subcooling to evaporator conditions of Tsat=0 °C and xEnd=1.

Figure 1.

Figure 1

Normalized forced-convection evaporation heat-transfer coefficient and pressure drop for R32 and R1234yf as a function of mass flux (D=7 mm, smooth tube, Tsat = 0 °C, q=10 kW·m−2)

Figure 1 shows an important trend of exponentially increasing pressure drop and asymptotically increasing heat-transfer coefficient with increasing mass flux. R1234yf has a lower heat-transfer coefficient and a higher pressure drop than R32 at the same mass flux, and the rate of increase of heat-transfer coefficient in relation to pressure drop is less favorable for R1234yf than for R32. Also, the drop of saturation temperature of R1234yf is greater than that of R32 for the same pressure drop. For example, at Tsat=0 °C, dT/dp=0.0934 K·kPa−1 for R1234yf and dT/dp=0.0384 K·kPa−1 for R32, which leads to a 2.4 times greater decrease in saturation temperature for R1234yf than for R32 at the same pressure drop. Similar trends take place in condensing flows.

The optimum refrigerant mass flux G is different for each refrigerant and depends on refrigerant thermodynamic and transport properties. Ammonia, for example, which has a very high thermal conductivity and moderate saturation temperature drop due to its low vapor density, realizes the best compromise between heat-transfer coefficient and pressure drop at a low mass flux, i.e., at a high number of tube circuits. On the other hand, R32 being a higher-pressure fluid (higher vapor density) and having lower liquid conductivity than ammonia, realizes the best compromise between heat transfer and temperature drop penalization at a higher mass flux, i.e., at a lower number of circuits.

3. Effect of Thermophysical Properties on Two-Phase Heat Transfer and Pressure Drop

The thermodynamic and transport properties that affect the heat-transfer coefficient, h, and pressure drop, Δp, in two-phase flow are:

  • liquid thermal conductivity, λl

  • liquid and vapor density, ρl and ρv

  • liquid and vapor viscosity, νl and νv

  • liquid specific heat at constant pressure, cp,l

  • surface tension, σ (only for evaporation).

The liquid conductivity is the most influential parameter affecting the heat-transfer coefficient, while the pressure drop is independent of both the liquid and the vapor thermal conductivity. Literature correlations for h include a term proportional to λla, where a is an exponent in the neighborhood of 0.6; a higher liquid conductivity results in better two-phase heat transfer. The effect of vapor thermal conductivity is negligible because of the high flow turbulence; it only slightly modifies the heat-transfer coefficient component for a dry surface when the evaporation flow is stratified.

The liquid and vapor density also affect the two-phase heat-transfer coefficient: higher ρl yields a larger h, while higher ρv yields a lower h (for correlations including ρv). The effect of vapor density is greater on the pressure drop than on the heat-transfer coefficient. The vapor quality strongly affects the two-phase flow density, and subsequently the pressure drop. Furthermore, a high vapor density corresponds to a small saturation temperature drop associated with the pressure drop, as shown by the Clapeyron relation (Borgnakke and Sonntag, 2012):

dTdp=Tsathfg(1ρv-1ρ1) (4)

The effect of liquid viscosity on two-phase heat transfer varies depending on the refrigerant and operating conditions, whereas the effect of vapor viscosity is small. The pressure drop increases as liquid and vapor viscosities increase. The liquid specific heat affects the heat-transfer coefficient, since it affects the liquid heat transport capacity. In most correlations h is proportional to cp,la, where ‘a’ is an exponent in the neighborhood of 0.8. Pressure drop is not a function of cp. The surface tension affects the nucleate boiling component of the evaporation heat-transfer coefficient; a low surface tension enhances h, but its effect is small compared with other transport properties.

In summary, the most important refrigerant properties for the forced-convection heat transfer are the liquid conductivity and the vapor density: the higher their values, the higher the two-phase heat-transfer coefficient is. The dominant property affecting pressure drop is the vapor density, where a high value results in low pressure drop, Δp, and low saturation temperature drop, dT/dp. Properties of refrigerants differ significantly (Table 1) so there is a spectrum of refrigerant performance relative to heat transfer and pressure drop. For example, R32 has both favorable liquid conductivity and vapor density in comparison to most fluids, whereas ammonia has a low vapor density, which is compensated for by an outstanding liquid conductivity.

Table 1.

Thermophysical properties of common refrigerants at 0 °C dew-point temperature (Lemmon et al., 2013)

Fluid Tc Pc λl ρl νl cp,l ρv νv dT/dp

°C MPa W·m−1·K−1 kg·m−3 mPa·s kJ·kg−1·K−1 kg·m−3 mPa·s K·kPa−1
R410A 71.4 4.90 0.103 1170.0 0.161 1.52 30.6 0.012 0.039
R32 78.1 5.78 0.145 1055.3 0.150 1.75 22.1 0.012 0.038
R1234yf 94.7 3.38 0.071 1176.3 0.208 1.29 17.7 0.010 0.093
R134a 101.1 4.06 0.092 1294.8 0.267 1.34 14.4 0.011 0.094
R717 (1) 132.3 11.3 0.559 638.6 0.170 4.62 3.5 0.009 0.062
R600a (2) 134.7 3.63 0.099 580.6 0.199 2.28 4.3 0.007 0.180
(1)

ammonia;

(2)

isobutane

4. Description of CYCLE_D-HX Model

4.1 Overall modeling approach

The CYCLE_D-HX1 model builds on the concept of using of temperature profiles of the heat sink and heat source, and ΔThx for the evaporator and condenser (Domanski and McLinden, 1992), which facilitates the accounting for refrigerant thermophysical properties, pressure drop, and heat-transfer coefficient on the cycle performance on a relative basis (Brown at al., 2002a and 2002b). This section provides a brief presentation of the CYCLE_D_HX modeling approach with a reference to the source publications. For simplicity of presentation, we will only discuss the basic vapor compression cycle although the simulation capabilities of CYCLE_D-HX include enhanced cycle options such as a liquid-line/suction-line heat exchanger, economizer, and intercooler.

In its simplest form, the simulated system consists of a compressor, condenser, adiabatic expansion device, and evaporator. The cycle and key thermodynamic states for this system are shown on a temperature-entropy (T-s) diagram (Figure 2). The compressor is represented by the isentropic efficiency, volumetric efficiency, and the electric motor efficiency. The evaporator and condenser can be either counter-flow, cross-flow or parallel-flow, and are represented by their ΔThx. The solution sequence starts with estimated values of saturation temperatures in the evaporator and condenser. Based on the established thermodynamic cycle with refrigerant temperature profiles and HTF temperature profiles, the model calculates ΔThx and compares them to the values specified as input. The model iterates evaporator and condenser saturation temperatures until it achieves the specified ΔThx values within a convergence parameter.

Figure 2.

Figure 2

Basic vapor compression cycle

For each iteration step of saturation temperatures, CYCLE_D-HX calculates heat exchangers’ ΔThx using Eq. 5 (Domanski and McLinden, 1992).

1ΔThx=Q1QhxΔT1+Q2QhxΔT2=1QhxQiΔTi (5)

In this equation, ΔThx is a harmonic mean weighted with the fraction of heat transferred in individual sections of the heat exchanger, based on the assumption of a constant overall heat-transfer coefficient throughout the heat exchanger. Each term represents the contribution of a heat exchanger section. At the outset of each saturation temperature iteration, the model calculates ΔThx based on sections corresponding to the subcooled liquid, two-phase, and superheated regions. Then, the model bisects each section and uses Eq. 5 to calculate a new value of ΔThx. The model repeatedly bisects each subsection until the ΔThx obtained from two consecutive evaluations agree within a convergence parameter.

As an alternative to specifying ΔThx, the heat exchangers can be characterized by the overall heat conductance UAhx. If this input option is used, the model calculates the specified ΔThx from the basic heat-transfer relation, ΔThx = Qhx/UAhx, where Qhx is the product of refrigerant mass flow rate and enthalpy change in the evaporator or condenser, as appropriate.

Representation of heat exchangers by their UAhx allows for inclusion of heat transfer and pressure drop characteristics in comparable evaluations of different refrigerants. For this purpose, CYCLE_D-HX considers that the total resistance to heat transfer in a heat exchanger, Rhx, consists of the resistance on the refrigerant side Rr, and combined resistances of the heat exchanger material and HTF [Rtube + RHTF]:

Rhx=1/UAhx=Rr+[Rtube+RHTF] (6)
whereRr=1/(hr·Ahx) (7)

The resistances [Rtube + RHTF] are independent of the refrigerant, and are assumed to be independent of operating conditions. Their combined value can be calculated from UAhx and hr values using performance measurements obtained in a laboratory on a system of interest. CYCLE_D-HX calculates [Rtube + RHTF] within its ‘reference run’ and stores its value for use in subsequent simulation runs for calculation of UAhx characterizing the heat exchanger with a new refrigerant or operating conditions.

CYCLE_D-HX requires the following operational input data for the ‘reference run’: HTF inlet and outlet temperatures for the evaporator and condenser; ΔThx for the evaporator and condenser (to achieve the measured evaporator and condenser saturation temperatures); evaporator superheat and pressure drop; and condenser subcooling and pressure drop. Additional ‘reference run’ inputs include compressor isentropic and volumetric efficiencies, and electric motor efficiency. Heat exchanger geometry inputs include the tube inner diameter and length, the number of refrigerant circuits, and the number of tubes per circuit. By user’s choice, CYCLE_D-HX can optimize evaporator and condenser circuitries (number of parallel circuits) to maximize the system’s COP. (This represents a design environment where the HTF and number of refrigerant tubes remains constant, but the refrigerant flow and tube circuitry can be adjusted.) Using this option, the model provides information on the relative performance potentials of refrigerants operating in systems with serpentine air-to-refrigerant heat exchangers.

For smooth tubes, CYCLE_D-HX uses correlations by Wojtan et al., (2005a and 2005b) and Shah (2009) for calculating the forced-convection heat-transfer coefficient for evaporation and condensation, respectively. For enhanced tubes, the model applies hr correction presented by Shlager et al. (1989). The modeling of evaporator and condenser refrigerant pressure drop relies on a similar concept to that for the heat-transfer process. For smooth tubes, the model determines a pressure multiplication factor by dividing the ‘reference run’ pressure drop by the predicted value (Eq. 8).

factorΔp=ΔprefΔppred (8)

where Δppred is calculated by the Muller-Steinhangen and Heck (MSH) (1986) correlation for smooth tubes. For enhanced tubes the MSH value is corrected according to Choi et al. (2001).

Regarding the compressor isentropic efficiency, CYCLE_D-HX offers the option of accounting for its dependence on the compression ratio, as it was postulated by several researchers (Brown et al., 2002b). When screening different refrigerants, the model uses Eq. 9 to take into account the change in isentropic efficiency with the pressure ratio in a consistent way.

ηs=C-0.05θ (9)

Equation (9) has the same slope as the relation derived from experimental data by Brown et al. (2002b); C is a constant calculated within the ‘reference run’ using the isentropic efficiency and the pressure ratio obtained from the test data.

4.2 Optimization of refrigerant circuitry

The refrigerant circuitry optimization algorithm identifies the number of condenser and evaporator circuits that maximize COP. The evaporator is optimized before the condenser because the system is much more sensitive to the number of evaporator circuits (Zilio et al., 2015); the heat-transfer coefficient and pressure drop are more sensitive to G in the evaporator because the refrigerant density is lower and the viscosity is higher. Optimizing the evaporator before the condenser enables more rapid identification of the multivariate optimum.

The COP optimization algorithm is a modified Golden Section Search, which takes into account the values and trend. The Golden Section algorithm has been modified because it normally requires a non-flat and continuous function, but the computed COP function often does not satisfy these criteria. The function may be flat, for example, when varying the number of tube circuits in the condenser. Discontinuities can occur from numerical approximations or from the semi-empirical correlations used to evaluate the heat-transfer coefficient and the pressure drop. For example, Figure 1 shows a discontinuity in the correlation for heat transfer coefficient in the neighborhood of G=150 kg·m−2·s−1, where the transition from a stratified-wavy to an annular flow takes place according to the flow-pattern map of Wojtan et al. (2005a). The algorithm starts searching in the direction of ascent until an inflection point is found and the maximum resides between the last two iterations. Then the algorithm makes at least two more iterations and stops when the absolute difference between the maximum and its two adjacent values is less than the convergence parameter.

The processing times for a simulation with optimization on personal computer (3.5 GHz processor) are on the order of 10 s, 150 s, and 350 s respectively for one-, two-, and three-component working fluids.

5. CYCLE_D-HX Validation

5.1 Experimental apparatus and test conditions

A laboratory liquid-to-liquid heat pump apparatus was used to generate data to verify the model. The apparatus (Figure A.1, in Appendix) is described briefly here; a more comprehensive description is provided in Skye (2015). The system was equipped with a variable-speed reciprocating compressor, variably-sized evaporator and condenser, manually adjusted throttling valve, and a liquid-line/suction-line heat exchanger, which could be included or bypassed. The evaporator and condenser were of the annular design arranged in the counter-current configuration; the refrigerant flowed in the enhanced inner tube (copper), while the HTF flowed in the smooth annular space. The heat exchangers’ size could be adjusted by changing the number of active refrigerant tubes; this feature enabled control of the heat flux.

The apparatus was set to achieve evaporation and condensation saturation temperatures nominal to air-source heat pumps operating at the Cooling A, Cooling B, and Heating H1 rating tests (AHRI, 2008). Table 2 shows the HTF inlet and outlet temperatures used to obtain these evaporation and condensation temperatures using R134a and a mid-range compressor speed, 1800 rev·min−1. Four additional data sets at each rating test (total of 12) were generated by holding the HTF inlet temperature constant as the system capacity was varied via compressor speed, (1400 to 2200) rev·min−1; these additional data sets are listed in the Appendix (Table A1(a), (b), and (c)). Note that the heat exchanger sizes were fixed for the data presented here.

Table 2.

Test operating conditions for R134a tests with 1800 rev·min−1 compressor speed

Rating test Capacity Condenser Evaporator



kW Tsat,ave
°C
THTF,in
°C
THTF,out
°C
Tsat,ave
°C
THTF,in
°C
THTF,out
°C



Cooling A* 1.69 43.6 33.9 39.0 8.1 20.2 15.4
Cooling B 1.95 35.8 24.9 30.9 5.5 19.8 14.2
Heating H1 1.88 39.6 32.0 36.3 0.3 10.2 6.5
*

‘reference run’ for CYCLE_D-HX model

Care was taken to configure other evaporator and condenser operating conditions (beyond refrigerant saturation temperature) to closely resemble those of a typical air-to-air heat pump. Specifically, the heat fluxes were within (5 to 9) kW·m−2 and (5 to 10) kW·m−2 for the evaporator and the condenser, respectively. Additionally, the ratios of HTF thermal resistance to total heat exchanger thermal resistance were nominally 0.8 and 0.6 for the evaporator and condenser, respectively; these values are representative of air-to-air heat pumps where the air-side (i.e. HTF side) thermal resistance dominates. The thermal resistance ratios were enforced by the selection of HTF mass flow rates; the HTF mass flow rates were held constant for all tests at 0.098 kg·s−1 for the condenser and 0.131 kg·s−1 for the evaporator. The subcooling and superheat were controlled to (2 to 3) K and (3 to 6) K, respectively. More details about these tests, including the uncertainty calculation (95 % confidence level) for the COP (0.35 %), capacity (0.2 %), and the Qvol (1.5 %) are presented in Skye (2015).

5.2 Experimental data vs. simulation results

We used the data from the Cooling A R134a test (Table 2) to carry out the CYCLE_D-HX ‘reference run’. The ‘reference run’ inputs included the 1.69 kW capacity, the evaporator ΔThx=8.8 K, the condenser ΔThx = 9.02 K, and pressure drops of 33 kPa and 45 kPa for the condenser and evaporator, respectively. We then executed simulations of the remaining Cooling A, Cooling B and Heating H1 ratings tests. The capacities, compressor isentropic and volumetric efficiencies, superheat and subcooling, discharge and suction line pressure drops, and HTF inlet and outlet temperatures were input based on measurements from each test.

We evaluated the percentage deviation between the simulation and the experimental results using Eq. 10.

E=ΠExperimental-ΠSimulationΠExperimental·100% (10)

where Π is any parameter of interest.

Figure 3 reports the deviations for COP, Qvol, pevap, and pcond. Most of the deviations are within 4 %. The largest deviation (7.4 %) is for the Cooling B test at the highest (2200 rev·min−1) compressor speed; this operating condition yielded about 20 % increase in refrigerant mass flow rate and capacity over the ‘reference run’. The model inputs (Table A2(a), (b)) and results (Table A3(a) and (b)) are tabulated in the Appendix.

Figure 3.

Figure 3

Deviations between experimental and CYCLE_D-HX simulations results

6. Comparison of Refrigerant Performance Evaluation Using CYCLE_D and CYCLE_D-HX

For performance evaluation we selected R134a, R600a, and R32 because they have significantly different thermophysical properties (Table 1). R600a is the lowest-pressure refrigerant of the three, and has a low vapor density and liquid conductivity. R32 is the highest-pressure refrigerant and has a high liquid conductivity and vapor density. The operating pressure, vapor density and liquid conductivity of R134a are between those of R600a and R32. We simulated the cycle performance of the three fluids at the Cooling A test operating condition (Section 5.1). The CYCLE_D-HX simulations (without and with the optimization option) were based on the CYCLE_D-HX ‘reference run’, which applied no optimization and used the R134a Cooling A test data. We conducted these simulations at the same evaporator capacity that was specified for the ‘reference run’ (1.69 kW). For all CYCLE_D simulations we used the evaporator and condenser saturation temperatures and saturation temperature drops from the ‘reference run’.

Figure 4 presents COP results normalized by the ‘reference run’ COP. CYCLE_D predictions correlate inversely with refrigerants’ Pc: the low-pressure R600a has the highest COP, followed by the medium-pressure R134a, and the high-pressure R32, which has the lowest COP. The CYCLE_D-HX simulation results display the opposite trend: the low-pressure R600a shows the lowest COP, and the high-pressure R32 has the highest COP. The R134a COPs for CYCLE_D-HX without optimization (‘reference run’) and for CYCLE_D are identical because CYCLE_D simulations used the saturation temperatures and pressure drop from the ‘reference run’. All three refrigerants benefitted from the refrigerant circuitry optimization. The COP increased for R600a and R32 by about 5 % and 9 %, respectively. R134a benefitted least, which suggests that the original refrigerant circuitry was reasonably well designed for R134a.

Figure 4.

Figure 4

COP from CYCLE_D and CYCLE_D-HX simulations normalized by COPref = 2.85 (R134a Cooling A test condition, no optimization)

It is important to recognize the disparity in the COP trends between CYCLE_D and CYCLE_D_HX simulations, which affects the suitability of these simulation tools for rating competing refrigerants. With the same (imposed) saturation temperatures in the evaporator and condenser, CYCLE_D simulations tend to yield higher COPs for low-pressure refrigerants compared to high-pressure refrigerants because low-pressure fluids operate far below their critical point and tend to exhibit less irreversibilities due to the superheated vapor horn and throttling process (Domanski and Didion, 1993). However, as shown in the CYCLE_D-HX simulations, this thermodynamic advantage of low-pressure fluids may be erased in systems using heat exchangers that implement refrigerant forced-convection evaporation and condensation (e.g., air-to-refrigerant coils). Low-pressure fluids have low vapor density and therefore exhibit relatively large pressure and saturation temperature drops in forced-convection coils. These irreversibilities may render high-pressure refrigerants more efficient, particularly when refrigerant circuitries (and therefore mass fluxes) in these heat exchangers are optimized.

The COP trends discussed here are consistent with a prior study, which used a detailed air-to-air heat pump model with R600a, R134a, R290, R22, R410A, and R32 (Domanski and Yashar, 2006). These performance trends are also reflected in the engineering practice of selecting low-pressure refrigerants for water chillers with shell-and tube heat exchangers, which have low pressure drop, and applying higher-pressure refrigerants in systems with forced-convection heat exchangers. Consequently, we can conclude that the simulation methodology used by CYCLE_D-HX is preferable for screening refrigerants for systems with forced-convection heat exchangers over CYCLE_D-type simulation models using imposed saturation temperatures in the evaporator and condenser, which may provide incorrect ranking of the evaluated fluids. For systems with insignificant pressure drop, CYCLE_D-type models are likely to produce correct ranking unless liquid conductivity of the considered fluids differ substantially.

7. Conclusions

Preliminary refrigerant evaluations using theoretical models should consider the type of vapor compression equipment for which the refrigerant screening is performed. The key aspect differentiating system types is the type of evaporators and condensers used. For systems with heat exchangers relying on refrigerant pool boiling, falling film evaporation, or space condensation, cycle models based on thermodynamic properties alone may provide adequate ‘first estimate’ of relative performance merits of refrigerants of interest. However, for systems with heat exchangers relying on refrigerant forced-convection evaporation and condensation heat transfer, more appropriate simulation models are those which also involve refrigerant transport properties and can account for the effect of refrigerant mass flux on heat transfer and pressure drop.

NOMENCLATURE

A

area (m2)

cp

specific heat at constant pressure (kJ·kg−1·K−1)

COP

coefficient of performance

D

diameter (mm)

E

deviation (%)

F

heat-transfer coefficient or pressure drop

factorΔp

pressure drop multiplication factor (dimensionless)

G

mass flux (kg·m−2·s−1)

h

heat-transfer coefficient (W·m−2·K−1)

hfg

enthalpy of vaporization (kJ·kg−1)

HTF

heat-transfer fluid

L

length (m)

p

pressure (kPa)

q

heat flux (kW·m−2)

Q

cooling or heating capacity (kW)

Qvol

volumetric capacity (kJ·m−3)

R

heat transfer resistance (K·W−1)

RSF

refrigerant side feature (e.g., microfins, insert)

T

temperature (K, °C)

TPP

thermophysical properties

TTP

total temperature penalization (K)

UA

heat exchanger conductance (W·K−1)

x

vapor quality (decimal fraction)

Δp

pressure drop (kPa)

ΔThx

mean effective temperature difference (K)

ΔT

temperature drop (K)

Greek letters

ηs

isentropic efficiency (decimal fraction)

θ

pressure ratio (dimensionless)

λ

thermal conductivity (W·m−1·K−1)

ν

kinematic viscosity (mPa·s)

Π

any parameter of interest

ρ

density (kg·m−3)

σ

surface tension (N·m−1)

Subscripts

ave

average

c

critical

cond

condensation

evap

evaporation

hx

heat exchanger

in

inlet

l

liquid

nom

nominal

out

outlet

pred

predicted

r

refrigerant

ref

reference

sat

saturation

tube

tube separating refrigerant and HTF

v

vapor

Appendix: Experimental Data

This Appendix presents a schematic of the test rig and experimental data discussed in Section 5.1, and CYCLE_D-HX inputs and simulation results discussed in Section 5.2. Symbols used in the figures and tables are listed in the Nomenclature at the end of the Appendix.

Figure A1.

Figure A1

Schematic of the experimental apparatus

Table A1(a).

Experimental data–refrigerant-side measurements

r Ncomp P1 P4 P7 P8 P9 P11 ΔPc ΔPe ΔPsuc T1 T3 T4 T7 T8 T9 T11 τcomp
kg·s−1 rev·min−1 kPa kPa kPa kPa kPa kPa kPa kPa kPa °C °C °C °C °C °C °C N·m
* ±0.000016 ±1 ±3.5 ±3.5 ±3.5 ±3.5 ±3.5 ±3.5 ±1.3 ±0.8 ±0.3 ±0.09 ±0.09 ±0.09 ±0.09 ±0.09 ±0.09 ±0.09 ±0.33
Cooling A 0.01037 1426 362.8 1105 1076 1076 412.3 373.7 29.7 38.6 10.9 11.74 72.79 70.04 38.70 37.87 9.76 10.81 4.72
0.01011 1609 370.6 1104 1075 1075 418.4 381.8 29.7 36.7 11.2 14.24 79.15 74.46 38.79 37.91 10.14 13.47 4.08
0.01101 1810 353.2 1136 1103 1103 412.0 367.4 33.0 44.6 14.2 12.11 81.92 77.06 38.70 37.83 9.70 11.41 4.25
0.01153 2005 337.5 1145 1108 1108 405.8 353.9 37.2 51.9 16.4 12.79 86.52 81.77 39.77 39.12 9.21 12.16 4.27
0.01270 2231 307.8 1170 1127 1127 395.5 329.4 42.3 66.2 21.5 10.47 90.44 87.38 40.99 40.80 8.44 9.66 4.99

Cooling B 0.01094 1429 340 896.9 856.3 856.3 396.3 353.3 40.6 43.1 13.2 9.57 63.49 61.21 31.02 30.73 8.58 8.59 4.72
0.01154 1628 323.8 915.3 869.6 869.6 390.6 340.5 45.8 50.2 16.6 10.51 69.35 66.91 31.56 31.37 8.08 9.64 4.08
0.01206 1829 308 932.7 883.9 883.9 384.1 327.1 48.9 57.1 19.1 9.63 73.64 71.12 31.78 31.53 7.62 8.78 4.25
0.01246 2032 295.6 946 894.6 894.6 379.8 317 51.4 62.9 21.4 9.79 77.91 75.27 31.91 31.65 7.28 9.02 4.27
0.01291 2234 284.9 958 903.7 903.7 377.6 308.9 54.2 68.7 24.0 8.15 81.12 78.46 32.45 32.27 7.11 7.32 4.99

Heating H1 0.008001 1430 293.1 990.8 968 968 329 300.6 22.7 28.4 7.6 8.02 74.28 70.73 36.38 35.42 3.24 6.46 4.72
0.008433 1628 273.8 1005 979.7 979.7 317.5 284.1 24.9 33.4 10.3 6.80 78.40 74.70 36.66 35.82 2.23 4.98 4.08
0.009067 1832 264.3 1021 992.8 992.8 315.7 276.5 28.1 39.1 12.3 3.65 81.03 77.40 37.11 36.39 2.05 1.70 4.25
0.009384 2032 253.7 1032 1002 1002 311.2 267.6 29.9 43.6 13.9 4.19 85.69 81.90 37.33 36.63 1.63 2.40 4.27
0.009811 2233 246.9 1046 1014 1014 310.5 262.4 31.9 48.1 15.5 2.28 88.75 84.93 37.45 36.76 1.55 0.37 4.99
*

k=2, 95% confidence interval

Table A1(b).

Experimental data–refrigerant-side computed metrics

COPcool COPheat ΔPdis ηs ηv cool.r heat.r SC SH Qvol,cool Qvol,heat comp.r
-- -- kPa -- -- kW kW °C °C kJ·m−3 kJ·m−3 kW
* ±0.01 ±0.01 ±0.1 ±0.006 ±0.006 ±0.0035 ±0.004 ±0.2 ±0.3 ±30 ±40 ±0.002
Cooling A 3.33 4.26 1.5 0.520 0.562 1.587 2.032 3.39 3.90 2637 3377 0.477
3.07 3.96 1.5 0.468 0.481 1.569 2.027 3.27 5.93 2704 3494 0.512
2.82 3.72 1.7 0.463 0.486 1.693 2.235 4.36 5.00 2567 3388 0.601
2.62 3.54 1.9 0.457 0.484 1.763 2.378 3.44 6.83 2419 3263 0.673
2.34 3.31 2.3 0.460 0.524 1.889 2.666 3.39 3.90 2152 3038 0.806

Cooling B 3.95 4.92 2.1 0.508 0.629 1.771 2.202 2.69 3.31 2626 3266 0.448
3.57 4.54 2.3 0.497 0.618 1.873 2.38 2.71 5.42 2482 3153 0.524
3.24 4.20 2.5 0.483 0.605 1.949 2.532 3.08 5.70 2349 3051 0.602
3.02 3.98 2.7 0.475 0.589 2.017 2.663 3.38 6.82 2248 2968 0.669
2.75 3.72 2.8 0.457 0.573 2.061 2.789 3.21 5.86 2147 2906 0.749

Heating H1 3.04 3.97 1.1 0.521 0.538 1.236 1.615 1.79 5.75 2144 2801 0.407
2.76 3.70 1.2 0.511 0.533 1.291 1.732 1.95 5.83 1984 2662 0.468
2.47 3.43 1.4 0.482 0.521 1.356 1.879 1.99 3.29 1893 2624 0.549
2.33 3.28 1.5 0.473 0.510 1.408 1.985 2.12 4.87 1813 2555 0.605
2.15 3.11 1.6 0.452 0.495 1.454 2.103 2.42 3.38 1755 2537 0.677
*

k=2, 95% confidence interval

Table A1(c).

Experimental data–HTF-side measurements

HTF,c HTF,e THTF,c,in ΔTHTF,c THTF,e,in ΔTHTF,e
kg·s−1 kg·s−1 K C °C K
* ±0.00026 ±0.00026 ±0.6 ±0.015 ±0.6 ±0.015
Cooling A 0.09928 0.1300 33.86 4.625 19.64 4.547
0.09800 0.1317 33.84 4.713 20.20 4.432
0.09871 0.1312 33.89 5.158 20.22 4.818
0.09801 0.1317 33.88 5.572 20.32 4.976
0.09920 0.1299 33.84 6.092 19.98 5.419

Cooling B 0.09852 0.1300 24.92 5.212 19.72 5.071
0.09861 0.1300 24.82 5.645 19.86 5.356
0.09859 0.1299 24.86 6.007 19.81 5.579
0.09859 0.1299 24.79 6.311 19.90 5.779
0.09846 0.1299 24.88 6.607 19.89 5.922

Heating H1 0.09941 0.1318 32.00 3.643 11.28 3.377
0.09875 0.1317 31.94 3.951 10.37 3.510
0.09878 0.1317 31.97 4.293 10.23 3.688
0.09872 0.1316 31.91 4.545 10.18 3.847
0.09873 0.1316 31.90 4.831 10.13 3.976
*

k=2, 95% confidence interval

Table A1(d).

Experimental data–HTF-side computed metrics

cp,HTF,c cp,HTF,e cool,HTF heat,HTF ins,HTF,c ins,HTF,e
kJ·kg−1·K−1 kJ·kg−1·K−1 kW kW kW kW
* ±3 % ±3 % ±0.05 ±0.05 ±10 % ±10 %
Cooling A 4.18 2.59 1.56 2.002 0.081 0.030
4.18 2.59 1.538 2.013 0.081 0.026
4.18 2.59 1.660 2.213 0.083 0.023
4.18 2.59 1.724 2.366 0.082 0.027
4.18 2.59 1.853 2.613 0.085 0.031

Cooling B 4.18 2.59 1.737 2.178 0.030 0.030
4.18 2.59 1.838 2.353 0.025 0.036
4.18 2.59 1.915 2.502 0.024 0.040
4.18 2.59 1.978 2.631 0.029 0.035
4.18 2.59 2.025 2.754 0.033 0.034

Heating H1 4.18 2.58 1.218 1.584 0.069 0.071
4.18 2.58 1.27 1.699 0.067 0.079
4.18 2.58 1.331 1.842 0.069 0.080
4.18 2.58 1.385 1.945 0.068 0.082
4.18 2.57 1.430 2.063 0.069 0.083
*

k=2, 95% confidence interval

Table A2(a).

CYCLE_D-HX simulations–reference run inputs

Heat Exchangers
Type RSF THTF,c,in THTF,c,out THTF,c,in THTF,c,out LMTDc LMTDe ΔPc ΔPe SC SH IDtube Ltube #tube,c #tube,e #cir
-- -- °C °C °C °C K K kPa kPa K K m m -- -- --
Counter Enhanced 33.89 39.04 20.22 15.41 8.46 9.08 32.96 44.64 4.36 5.00 0.00846 0.5588 12 10 1
Compressor Vapor Lines Auxiliary Power
ηs ηv ηm cool ΔTdew,suc ΔTdew,dis fan,indoor fan,outdoor controls
-- -- -- kW °C °C kW kW kW
0.46 0.49 1.00 1.69 1.14 0.06 0.00 0.00 0.00

Table A2(b).

CYCLE_D-HX–reference run results

COPcool Rtube + RHTF factorΔP
-- K·kW−1 --
Condenser 2.794 2.1686 4.329
Evaporator 3.07 4.3507 2.187

Table A3(a).

CYCLED-HX simulations–inputs

Heat Exchangers Compressor Vapor lines Auxiliary Power
Ncomp* THTF,c,in THTF,c,out THTF,e,in THTF,e,out SC SH ηs ηv ηm cool ΔTdew,s ΔTdew,d fan,indoor fan,outdoor controls
rev·min−1 °C °C °C °C K K -- -- -- kW °C °C kW kW kW
Cooling A 1426 33.86 38.49 19.64 15.09 3.39 3.90 0.520 0.562 1.00 1.587 0.86 0.05 0 0 0
1609 33.84 38.56 20.2 15.77 3.27 5.93 0.468 0.481 1.00 1.569 0.88 0.05 0 0 0
1810 33.89 39.04 20.22 15.41 4.36 5.00 0.463 0.486 1.00 1.693 1.14 0.06 0 0 0
2005 33.88 39.46 20.32 15.35 3.44 6.83 0.457 0.484 1.00 1.763 1.36 0.06 0 0 0
2231 33.84 39.93 19.98 14.56 3.39 3.90 0.460 0.524 1.00 1.889 1.90 0.08 0 0 0

Cooling B 1429 24.92 30.13 19.72 14.65 2.69 3.31 0.508 0.629 1.00 1.771 1.10 0.08 0 0 0
1628 24.82 30.47 19.86 14.51 2.71 5.42 0.497 0.618 1.00 1.873 1.42 0.09 0 0 0
1829 24.86 30.87 19.81 14.23 3.08 5.70 0.483 0.605 1.00 1.949 1.69 0.10 0 0 0
2032 24.79 31.11 19.90 14.13 3.38 6.82 0.475 0.589 1.00 2.017 1.95 0.10 0 0 0
2234 24.88 31.48 19.89 13.97 3.21 5.86 0.457 0.573 1.00 2.061 2.24 0.11 0 0 0

Heating H1 1430 32.00 35.64 11.28 7.902 1.79 5.75 0.521 0.538 1.00 1.236 0.70 0.04 0 0 0
1628 31.94 35.89 10.37 6.861 1.95 5.83 0.511 0.533 1.00 1.291 1.01 0.05 0 0 0
1832 31.97 36.26 10.23 6.546 1.99 3.29 0.482 0.521 1.00 1.356 1.23 0.05 0 0 0
2032 31.91 36.46 10.18 6.336 2.12 4.87 0.473 0.510 1.00 1.408 1.43 0.05 0 0 0
2233 31.90 36.73 10.13 6.158 2.42 3.38 0.452 0.495 1.00 1.454 1.63 0.06 0 0 0
*

Compressor speed is not an input to the model, but is listed here to help the reader correlate model inputs to experimental data

Table A3(b).

CYCLED-HX simulations–results

Ncomp* COPcool COPheat Pc,in1 ΔPc Pe,out2 ΔPe cool heat Qvol,cool Qvol,heat comp,r
rev·min−1 -- -- kPa kPa kPa kPa kW kW kJ·m−3 kJ·m−3 kW
Cooling A 1426 3.238 4.238 1118 30.64 369.6 40.92 1.59 2.081 2589 3389 0.4911
1609 3.025 4.025 1113 29.29 380.0 37.96 1.57 2.089 2673 3557 0.5189
1810 2.794 3.794 1136 32.96 367.4 44.65 1.69 2.295 2560 3476 0.6049
2005 2.674 3.674 1146 35.25 360.4 49.24 1.76 2.419 2462 3383 0.6583
2231 2.414 3.414 1168 40.69 338.4 61.07 1.89 2.672 2227 3149 0.7828

Cooling B 1429 3.967 4.967 901.7 41.32 353.5 43.14 1.764 2.208 2634 3298 0.4446
1628 3.678 4.678 911.8 44.4 344.2 48.25 1.867 2.375 2526 3212 0.5077
1829 3.339 4.339 925.1 47.29 334.3 53.34 1.947 2.53 2422 3147 0.5831
2032 3.151 4.151 932.9 49.49 327.6 57.11 2.017 2.657 2349 3095 0.6402
2234 2.954 3.954 943.7 51.71 322.1 61.24 2.057 2.753 2269 3037 0.6963

Heating H1 1430 2.924 3.924 1016 21.67 298.0 32.93 1.24 1.664 2103 2822 0.4241
1628 2.691 3.691 1024 23.29 282.8 37.36 1.29 1.769 1962 2692 0.4795
1832 2.409 3.409 1038 26.22 274.1 43.61 1.36 1.925 1869 2645 0.5646
2032 2.295 3.295 1044 27.46 268.2 46.65 1.41 2.024 1814 2605 0.6143
2233 2.135 3.135 1053 29.14 263.1 50.53 1.45 2.129 1760 2585 0.6792
*

Compressor speed is not an input to the model, but is listed here to help the reader correlate model inputs to experimental data

1

corresponds to P4 in Figure A.1

2

corresponds to P11 in Figure A.1

NOMENCLATURE (APPENDIX)

cp

specific heat at constant pressure (kJ·kg−1·K−1)

COP

coefficient of performance

factorΔp

pressure drop multiplication factor (dimensionless)

ID

inner diameter of tube (m)

LMTD

log-mean temperature difference (K)

mass flow (kg·s−1)

N

speed (rev·min−1)

P

pressure (kPa)

cooling or heating capacity (kW)

Qvol

volumetric capacity (kJ·m−3)

R

heat transfer resistance (K·W−1)

RSF

refrigerant side feature (e.g., microfins, insert)

SC

condenser outlet subcooling (°C)

SH

evaporator outlet superheat (°C)

T

temperature (K, °C)

ΔP

pressure drop (kPa)

ΔT

temperature difference (K)

power (kW)

comp.r

compressor power, computed using the refrigerant mass flow and enthalpy change across compressor (kW)

#

number of (tubes, tube circuits, etc.)

1 to 11

thermodynamic states, see Figure A.1

Greek letters

η

efficiency (decimal fraction)

τ

torque (N·m)

Subscripts

c

condenser

comp

compressor

cool

cooling

controls

heat pump controls

dew

dew-point (saturated vapor point)

dis

discharge line

e

evaporator

fan

fan for indoor/outdoor heat exchanger

heat

heating

HTF

heat transfer fluid, or calculated/measured on the HTF side

in

inlet

indoor

inside the building

ins

heat leak to ambient air through HTF outer tube and insulation

m

compressor motor efficiency

outdoor

outside the building

r

refrigerant, or calculated/measured on the refrigerant-side

s

compressor isentropic efficiency

suc

suction line

tube

tube separating refrigerant and HTF

v

compressor volumetric efficiency

1 to 11

thermodynamic states, see Figure A.1

Footnotes

1

The program will be publically available packaged with a graphical user’s interface and user’s guide.

References

  1. AHRI. 2008 Standard for Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment. Air-Conditioning, Heating, and Refrigeration Institute; Arlington, VA, United States: 2008. Retrieved from www.ahrinet.org. [Google Scholar]
  2. Borgnakke C, Sonntag RE. Fundamentals of Thermodynamics. 8. Wiley; New York: 2012. [Google Scholar]
  3. Brown JS, Domanski PA, Lemmon EW. NIST Standard Reference Database. Vol. 49. National Institute of Standards and Technology; Gaithersburg, MD: 2012. CYCLE_D: NIST Vapor Compression Cycle Design Program, Version 5.0. http://www.nist.gov/srd/nist49.cfm. [Google Scholar]
  4. Brown JS, Kim Y, Domanski PA. Evaluation of Carbon Dioxide as R22 Substitute for Residential Conditioning. ASHRAE Transactions. 2002a;108(2):954–963. [Google Scholar]
  5. Brown JS, Yana-Motta SF, Domanski PA. Comparative analysis of an automotive air conditioning system operating with CO2 and R134a, Int. J Refrig. 2002b;25(1):19–32. [Google Scholar]
  6. Brown JS, Zilio C, Brignoli R, Cavallini A. Heat transfer and pressure drop penalization terms (exergy losses) during flow boiling of refrigerants, Int. J of Energy Research. 2012;37(13):1669–1679. [Google Scholar]
  7. Brown JS, Zilio C, Brignoli R, Cavallini A. Thermophysical properties and heat transfer and pressure drop performance potentials of hydrofluoro-olefins, hydrochlorofluoro-olefins, and their blends. HVAC&R Research. 2014;20:203–220. [Google Scholar]
  8. Cavallini A, Brown JS, Del Col D, Zilio C. In-tube condensation performance of refrigerants considering penalization terms (exergy losses) for heat transfer and pressure drop, Int. J of Heat and Mass Transfer. 2010;53:2885–2896. [Google Scholar]
  9. Choi JY, Kedzierski MA, Domanski PA. Generalized pressure drop correlation for evaporation and condensation in smooth and micro-fin tube. IIR commission B1 conference, thermophysical properties and transfer processes of new refrigerants; Paderborn, Germany. 2001. [Google Scholar]
  10. Domanski PA, McLinden MO. A Simplified Cycle Simulation Model for the Performance Rating of Refrigerants and Refrigerant Mixtures, Int. J Refrig. 1992;15(2):81–88. [Google Scholar]
  11. Domanski PA, Didion DA. Thermodynamic Evaluation of R-22 Alternative Refrigerants and Refrigerant Mixtures. ASHRAE Transactions. 1993;99(2):636–648. [Google Scholar]
  12. Domanski PA, Yashar D. Comparable Performance Evaluation of HC and HFC Refrigerants in an Optimized System. 7th IIR Gustav Lorentzen Conference on Natural Working Fluids; Trondheim, Norway. 2006. [Google Scholar]
  13. Domanski PA, Yashar DA. Optimization of Finned-Tube Condensers Using an Intelligent System. Int J Refrig. 2007;30(3):482–488. [Google Scholar]
  14. Lemmon EW, Huber ML, McLinden MO. NIST Standard Reference Database. Vol. 23. National Institute of Standards and Technology; Gaithersburg, MD: 2013. NIST reference fluid thermodynamic and transport properties-REFPROP, Version 9.1. http://www.nist.gov/srd/nist73.cfm. [Google Scholar]
  15. McLinden MO, Didion AD. CFCs: Quest for Alternatives. ASHRAE J. 1987;29(12):32–42. [Google Scholar]
  16. Muller-Steinhangen H, Heck K. A simple pressure drop correlation for two-phase flow in pipes, Chem. Eng and Process. 1986;20:297–308. [Google Scholar]
  17. Shah MM. An improved and extended general correlation for heat transfer during condensation in plain tubes. HVAC&R. 2009;15(5):889–913. [Google Scholar]
  18. Shlager LM, Pate MB, Bergles AE. Heat transfer and pressure drop during evaporation and condensation of R22 in horizontal micro-fin tubes, Int. J Refrig. 1989;12(1):6–14. [Google Scholar]
  19. Skye H. Technical Note. Vol. 1895. National Institute of Standards and Technology; Gaithersburg, MD, USA: 2015. Heat Pump Test Apparatus for the Evaluation of Low Global Warming Potential Refrigerants. http://dx.doi.org/10.6028/NIST.TN.1895. [Google Scholar]
  20. Wojtan L, Ursenbacher T, Thome JR. Investigation of flow boiling in horizontal tubes: Part I - A new diabatic two-phase flow pattern map, Int. J Heat and Mass Transfer. 2005a;48:2955–2969. [Google Scholar]
  21. Wojtan L, Ursenbacher T, Thome JR. Investigation of flow boiling in horizontal tubes: Part II - Development of a new heat transfer model for stratified-wavy, dryout and mist flow regimes, Int. J Heat and Mass Transfer. 2005b;48:2970–2985. [Google Scholar]
  22. Zilio C, Brignoli R, Kaemmer N, Bella B. Energy efficiency of a reversible refrigeration unit using R410A or R32. Science and Technology for the Built Environment. 2015;21:502–514. [Google Scholar]

RESOURCES