Abstract
We investigated an outbreak of eight Legionnaires’ disease cases among persons living in an urban residential community of 60,000 people. Possible environmental sources included two active cooling towers (air-conditioning units for large buildings) <1 km from patient residences, a market misting system, a community-wide water system used for heating and cooling, and potable water. To support a timely public health response, we used real-time polymerase chain reaction (PCR) to identify Legionella DNA in environmental samples within hours of specimen collection. We detected L. pneumophila serogroup 1 DNA only at a power plant cooling tower, supporting the decision to order remediation before culture results were available. An isolate from a power plant cooling tower sample was indistinguishable from a patient isolate by pulsed-field gel electrophoresis, suggesting the cooling tower was the outbreak source. PCR results were available <1 day after sample collection, and culture results were available as early as 5 days after plating. PCR is a valuable tool for identifying Legionella DNA in environmental samples in outbreak settings.
Introduction
Legionnaires’ disease (LD) is a severe pneumonia that can be accompanied by gastrointestinal and neurologic symptoms. Risk factors include smoking, age >50 years, and comorbidities. Onset occurs 2–10 days after exposure to Legionella, a genus of intracellular gram-negative bacteria found in water and soil. L. pneumophila serogroup 1 (LP1) causes 65–90% of cases for which there is a bacterial isolate (Bennett, Dolin, & Blaser, 2014). The majority of cases are diagnosed by urine antigen test (UAT), a rapid test that is highly sensitive and highly specific for LP1 and is widely available in acute care settings. Identification of the environmental source relies on comparison of patient isolates and environmental isolates by molecular techniques. Culture of respiratory specimens is necessary to obtain patient isolates, but LD patients might not produce sputum, specimens are not routinely cultured on Legionella-specific media, and specimens are less likely to yield positive culture results if they are collected after a patient has begun antibiotic therapy.
LD outbreaks have occurred from exposure to bioaerosols from cooling towers, decorative fountains, hot tubs, market misting systems, and potable water systems in hospitals, hotels, and residential buildings (Cunha, Burillo, & Bouza, 2016; Fraser et al., 1977; Haupt et al., 2012; Mahoney et al., 1992). Cooling towers have caused large community outbreaks including an outbreak with 334 cases in Portugal in 2014 and an outbreak with 449 confirmed cases in Spain in 2001, and likely have caused many sporadic cases (Bhopal & Fallon, 1991; García-Fulgueiras et al., 2003; Shivaji et al., 2014). Bioaerosols from cooling towers can travel substantial distances and have caused illness among persons up to 11.6 km away from a source (White et al., 2013). Recovery of a bacterial isolate by culture is the standard for identification of Legionella in the environment. PCR can detect Legionella DNA, but does not indicate the presence of viable bacteria or provide a quantitative measure of the degree of contamination.
An estimated 8,000–18,000 cases of LD requiring hospitalization occur annually in the U.S. (Marston et al., 1997). Approximately 200–300 cases are reported annually in New York City; the age-adjusted incidence rate rose from 0.6/100,000 population during 2000 to 2.5/100,000 population during 2014, peaking at 3.4/100,000 population during 2013 (New York City Department of Health and Mental Hygiene [DOHMH], 2015a). This rise might be due to increased use of UAT by healthcare providers, an increase in the population at risk, or changes in the number and maintenance of cooling towers and their colonization by Legionella (Farnham, Alleyne, Cimini, & Balter, 2014). During 2000–2013, Bronx County had between 7–72 cases/year (crude rate 0.5–5.2 cases/100,000 population/year).
Clinical laboratories in New York City report positive Legionella test results to the New York City Department of Health and Mental Hygiene (DOHMH). For each case, DOHMH personnel review medical records to confirm illness and interview the patient or a close relative to determine possible Legionella exposure sources at home, work, healthcare settings, or associated with travel. Identification of a cluster of cases in space and time without a common building exposure indicates an outdoor exposure to a cooling tower or other outdoor aerosol source. An epidemiologist reviews all cases for common exposures and we also detect clusters at the city-, county-, and neighborhood- (multiple ZIP code) levels with a weekly automated system that compares the number of cases diagnosed in the past 4 weeks with that period and the prior and following 4-week periods in the previous 5 years, a modified historical limits method (Levin-Rector, Wilson, Fine, & Greene, 2015).
In December 2014 we identified a cluster of LD cases through a combination of epidemiologist review and automated cluster detection. All cases were located in Co-op City, a 1.3-square-kilometer residential neighborhood in northeastern Bronx County that is home to 60,000 persons, many retired, living in 15,372 residential units, including 14,900 apartments in 35 high-rise towers (24–33 floors) and 472 townhouses in 7 groups. All of Co-op City is contained within ZIP code 10475.
On December 1, 2014, the automated system reported nine cases among persons living in Bronx County (a larger area surrounding Co-op City) over the prior 4 weeks. Review of the four completed interviews found no common building exposures but found that two patients resided in Co-op City. On December 22, the automated system reported 12 cases among persons living in Bronx County over the prior 4 weeks, including four cases in Co-op City. We investigated to determine the magnitude and source, and to prevent further illness.
Methods
Case Surveillance
We defined an outbreak-associated case as LD diagnosed by UAT or culture and radiographic evidence of pneumonia in a person who lived in Co-op City with illness onset during November 2014–January 2015. Initial investigations found no common buildings visited by five patients.
On January 6, 2015, we alerted healthcare providers in New York City about the increase in cases in Bronx County and asked them to collect respiratory tract specimens to culture for Legionella from patients with respiratory symptoms, consider treating those patients for LD, and send isolates to the New York City Public Health Laboratory (PHL) (DOHMH, 2015b). We asked hospital infection control staff to identify stored respiratory tract specimens from recent patients with respiratory symptoms and to culture these specimens for Legionella. DOHMH held a community meeting in Co-op City on January 13 and issued a press release to inform the community about this investigation.
Environmental Investigation
At the time, there was no definitive source of information on the locations of cooling towers in New York City. We identified possible environmental sources in Co-op City— including cooling towers, markets with misting systems, and decorative fountains—by using environmental assessments, patient interviews, review of satellite imagery, and field visits. We also identified cooling towers in city administrative data for building owners who had requested a financial credit for wastewater reduction.
We collected samples at all identified environmental sources. Water and swab samples were collected at multiple points in cooling towers and the other suspected sources; pH, chlorine, and temperature were also tested. At cooling towers, we sampled from the surface of the cooling tower water pool, which could reflect aerosol content, and from stagnant water and biofilm, which are thought most likely to harbor bacterial overgrowth. Water samples were stored in 500 mL sterile containers treated with sodium thiosulfate (0.5 mL of a 0.1 N solution). We reviewed cooling tower maintenance practices for any deficiencies.
Samples were split between PHL and the New York State Department of Health Wadsworth Center (WC). Health department security staff transported samples by car overnight to WC for next-day testing. Environmental samples were screened for Legionella DNA at WC by a previously described real-time PCR assay to detect and differenti-ate Legionella species, L. pneumophila, and L. pneumophila serogroups 1–16; the assay includes an internal control for inhibitory substances. Validation testing suggested that a negative PCR result does not need to be confirmed with bacterial culture (Mérault et al., 2011; Nazarian, Bopp, Saylors, Limberger, & Musser, 2008).
Samples in which Legionella DNA was detected were processed and cultured starting on the same day, at WC and PHL, to obtain Legionella isolates. Environmental isolates and patient isolates were serogrouped by direct fluorescent antibody testing and typed by pulsed-field gel electrophoresis (PFGE) by Sfi1 digest (Sabrià et al., 2001). PFGE patterns of patient isolates and environmental LP1 isolates were compared using BioNumerics software.
Results
Case Surveillance
We identified eight cases in Co-op City through routine surveillance. Illness onset ranged from November 4–December 28, 2014, and diagnosis ranged from November 9, 2014–January 6, 2015. New cases were reported to the health department in every week of December; the last case was reported on January 8. All patients were male. Seven (88%) were smokers. Four (50%) had underlying comorbidities including diabetes, cardiovascular disease, chronic hepatitis C, chronic kidney disease, asthma, hypertension, and HIV. The mean age was 57.5 years (range 29–69 years). All were hospitalized, and none died. Sputum from one patient grew Legionella and an isolate was sent to PHL. Two (25%) lived in the same building.
Surveillance is ongoing in New York City and no additional cases have been subsequently reported in residents of Co-op City in the following 6 months after the last case described here.
Environmental Investigation
We located two active cooling towers in Co-op City, both within 1 km of all case patient homes. One cooling tower was located at a 40-megawatt power plant and had five cells, including two that ran year round and three that ran during April–October each year. A second cooling tower was located on top of a shopping mall and had one cell that ran year round. We also identified an inactive cooling tower.
Environmental assessment of the residential complexes revealed a community-wide closed-loop water system that ran to all Co-op City housing units and passed hot or cold water over coils for heating or cooling, resupplied by municipal water. One market had a vegetable misting system, but no patients had visited that market. We sampled all of these sites, apartments where two patients lived, and the municipal water supply. We found no decorative fountains or whirlpool spas in Co-op City.
PCR screening detected LP1 at the power plant cooling tower and L. pneumophila serogroup 6 (LP6) at the power plant cooling tower and at the mall cooling tower. The community-wide closed-loop water system, market misting system, residential housing, and municipal water had no detectable Legionella DNA, with all results received <1 day after specimen collection (Table 1).
TABLE 1.
Detection of Legionella pneumophila in Environmental Samples, New York City, 2014–2015
| Sampling Location | PCR* | Culture* | Serogroup |
|---|---|---|---|
| Power plant cooling towers | 29/30 | 27/30 | LP1, LP6 |
| Shopping mall cooling tower | 8/10 | 1/8 | LP6 |
| Residential housing (two apartments) | 0/23 | – | – |
| Community-wide closed-loop water system | 0/4 | – | – |
| Vegetable misting system in market | 0/5 | – | – |
| Public potable water supply | 0/2 | – | – |
PCR = polymerase chain reaction; LP1 = L. pneumophila serogroup 1; LP6 = L. pneumophila serogroup 6.
Results are number of positive samples divided by total samples tested. Only specimens positive or inconclusive for L. pneumophila by PCR were cultured; negative specimens were not cultured.
After PCR detected LP1 at the power plant cooling tower, which was also the only known source with a wide aerosol distribution that could account for all cases, we proceeded to require its shutdown and remediation. On January 9, the same day LP1 DNA was detected by PCR, a health commissioner order was sent to power plant staff and the cooling tower was shut down; remediation began January 12 after development of a remediation plan. After three rounds of shock disinfection, no further LP1 grew in samples collected on January 26. The power plant cooling tower resumed operation on January 26 during extreme cold weather, as the plant power was needed to provide power and heat to the community.
Culture, isolation, and typing were completed later: LP1 grew in samples from the power plant cooling tower and LP6 grew in samples from the power plant cooling tower and the mall cooling tower, with results received on January 14, 5 days after PCR results. Samples from other locations were not placed in culture after testing negative by PCR. LP1 from the power plant cooling tower was indistinguishable from the patient isolate by PFGE (Figure 1, lanes 3–5).
FIGURE 1. Legionella pneumophila.

Pulsed-Field Gel Electrophoresis Patterns (Sfi1 Digestion)
From left to right: lane 1, molecular weight standard H9812; lane 2, historic case (clinical specimen); lane 3, outbreak case (clinical specimen); lane 4, power plant cooling tower (environmental sample 1); and lane 5, power plant cooling tower (environmental sample 2).
Legionella testing at the power plant cooling tower occurred once per year in the summer, most recently in July 2014, with no Legionella detected in 7 years of operation. Review of maintenance records from August–December 2014 revealed that staff had changed the disinfection biocide in August 2014 from a bromine-based pellet to a chlorine-based liquid, added over a 1-hr period daily with a target total chlorine level of 2–4 ppm. Samples collected 2 hr after the biocide was added were tested for total chlorine; however, the target range was not adjusted for the new biocide formulation and free chlorine was not routinely measured.
Following shutdown and remediation, no Legionella grew in follow-up samples collected from the power plant cooling tower every 2 weeks through March 18. Follow-up testing included monthly testing for Legionella; for counts >1,000 CFU/mL, remedial action was to be performed by dosing water with a chlorine-based compound equivalent to 5 mg/L of free residual chlorine for at least 1 hr, and then Legionella culture was to be performed every 3–7 days until two consecutive negative samples were obtained. DOHMH also recommended that the cooling tower at the mall be shut down and remediated out of an abundance of caution.
Discussion
We investigated an outbreak of eight Legionnaires’ disease cases linked by environmental and laboratory data to an industrial cooling tower at a power plant. This investigation was notable for the use of PCR screening of environmental samples to implicate one cooling tower and support shutting it down for remediation, several days before culture results were available. The implicated cooling tower had a recent change in biocide formulation that might have allowed lower biocide levels and more favorable conditions for Legionella growth. Review of cooling tower maintenance plans found deficits; testing identified viable Legionella bacteria, both common findings in other cooling tower assessments in New York City and elsewhere (Mouchtouri, Goutziana, Kremastinou, & Hadjichristodoulou, 2010).
Industry guidelines illustrate best practices for testing and maintenance to prevent Legionella overgrowth; these interventions, however, might not remove Legionella (American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2015; Cooling Technology Institute, 2008). Remediation at this cooling tower required shutdown for multiple days and implementation of a water safety plan with more monitoring and data collection to guide improvements in process control. We recommend that all cooling towers should have a written water safety plan and should test regularly to ensure adequate disinfection.
Multiple limitations to this investigation are noted. PCR detects DNA and does not indicate the presence of viable bacteria. Limited sampling from each environmental site might have led to a false negative result when other strains of Legionella were present. For patients, UAT primarily detects LP1 but has cross-reactivity for other serogroups; mixed infections are also possible. For seven (88%) cases, we did not have respiratory tract cultures or isolates, which means we do not have information on their strains or serogroups. We also might have missed cases of illness among persons who were not tested for Legionella infection or who did not live in Co-op City but were exposed there or nearby.
An increase in cases might reflect increased clinician awareness and testing practices following our health alert; however, only one case was diagnosed after that alert. Finally, during this investigation we were limited to testing those cooling towers that we were able to identify in administrative data or aerial imagery. In August 2015, after a large LD outbreak elsewhere in Bronx County caused by a cooling tower, the New York City Council enacted comprehensive rules for cooling tower registration, testing, and maintenance (City of New York, 2015). That registry identified four additional cooling towers in Co-op City that had not been identified through our initial source-finding methods, highlighting the need for registration systems or other investigative approaches to facilitate public health investigations.
Conclusion
While this outbreak progressed, we were identifying new cases weekly. We were concerned that deaths and more cases might occur before we could identify the source and take public health action. The power plant cooling tower was the most likely source of aerosol that could expose the entire community and we were prepared to require remediation there, but we wanted laboratory evidence of Legionella contamination before taking action. Waiting for culture results would have delayed action by several days.
We balanced the importance of rapid source control and remediation with the practical implications of shutting down, cleaning, and testing the power plant that was the sole power source for 60,000 persons, on short notice during a period of extreme cold weather. These actions were also expensive, as the cooling tower operators spent approximately $750,000/week for backup power during the shutdown period.
We were able to obtain PCR results <1 day after sample collection and the cooling tower was shut down 1 day later. Culture results, received as early as 5 days after plating, confirmed the PCR findings. The Legionella PCR assay used by WC has an analytic sensitivity of <1 CFU and a specificity of 100%; prior use found substantial agreement with culture (Nazarian et al., 2008). This PCR assay contains a target for inhibitory growth that makes it a valuable tool for screening before culture, because a negative result indicates culture is not needed. Negative PCR results at other possible sources strengthened the evidence for the power plant cooling tower as the source. Since this outbreak, we have incorporated PCR testing for environmental Legionella DNA into our protocol for LD investigations to more rapidly identify potential sources. We recommend that other jurisdictions also consider its use in outbreak settings.
Acknowledgments
We thank DOHMH staff who investigated cases, inspected cooling towers, collected environmental samples at cooling towers and elsewhere, and performed typing and PFGE of isolates. We thank WC staff who performed PCR and culture. We express gratitude to the laboratory staff at Montefiore Medical Center who invested substantial time to culture a patient’s leftover respiratory specimen, originally collected to test for Mycobacterium tuberculosis, and to isolate Legionella and send it to PHL. We also thank DOHMH Health Police for their timely transport of environmental samples to WC.
This work was supported by CDC’s Epidemiology and Laboratory Capacity for Infectious Diseases grant (5U50CK000407). The findings and conclusions in this report are those of the authors and do not necessarily represent the official position of CDC.
Footnotes
Note: Isaac Benowitz is now a medical officer with the Division of Healthcare Quality Promotion, Centers for Disease Control and Prevention, Atlanta, Georgia. Christopher Boyd is now general manager of the North America Building Water Health Program, NSF International, Ann Arbor, Michigan.
Contributor Information
Isaac Benowitz, Epidemic Intelligence Service, Centers for Disease Control and Prevention.
Robert Fitzhenry, New York City Department of Health and Mental Hygiene.
Christopher Boyd, New York City Department of Health and Mental Hygiene.
Michelle Dickinson, New York State Department of Health.
Michael Levy, Montefiore Medical Center.
Ying Lin, New York City Department of Health and Mental Hygiene.
Elizabeth Nazarian, New York State Department of Health.
Belinda Ostrowsky, Montefiore Medical Center.
Teresa Passaretti, New York State Department of Health.
Jennifer Rakeman, New York City Department of Health and Mental Hygiene.
Amy Saylors, New York State Department of Health.
Elena Shamoonian, Montefiore Medical Center.
Terry-Ann Smith, New York City Department of Health and Mental Hygiene.
Sharon Balter, New York City Department of Health and Mental Hygiene.
References
- American Society of Heating, Refrigerating and Air-Conditioning Engineers. ANSI/ASHRAE standard 188-2015. Legionellosis: Risk management for building water systems. 2015 Retrieved from https://ashrae.iwrapper.com/ViewOnline/Standard_188-2015.
- Bennett JE, Dolin R, Blaser MJ. Mandell, Douglas, and Bennett’s principles and practice of infectious diseases. 8. Philadelphia, PA: Elsevier Saunders; 2014. [Google Scholar]
- Bhopal RS, Fallon RJ. Variation in time and space of non-outbreak Legionnaires’ disease in Scotland. Epidemiology and Infection. 1991;106(1):45–61. doi: 10.1017/s0950268800056430. [DOI] [PMC free article] [PubMed] [Google Scholar]
- City of New York. Local laws of the city of New York for the year 2015 (no 77) 2015 Retrieved from https://www1.nyc.gov/assets/buildings/pdf/ll77of2015.pdf.
- Cooling Technology Institute. Legionellosis guideline: Best practices for control of Legionella. CTI guidelines WTB-148 (08) 2008 Retrieved from http://www.cti.org/downloads/WTP-148.pdf.
- Cunha BA, Burillo A, Bouza E. Legionnaires’ disease. Lancet. 2016;387(10016):376–385. doi: 10.1016/S0140-6736(15)60078-2. [DOI] [PubMed] [Google Scholar]
- Farnham A, Alleyne L, Cimini D, Balter S. Legionnaires’ disease incidence and risk factors, New York, New York, USA, 2002–2011. Emerging Infectious Diseases. 2014;20(11):1795–1802. doi: 10.3201/eid2011.131872. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Fraser DW, Tsai TR, Orenstein W, Parkin WE, Beecham HJ, Sharrar RG, Brachman PS. Legionnaires’ disease: Description of an epidemic of pneumonia. New England Journal of Medicine. 1977;297(22):1189–1197. doi: 10.1056/NEJM197712012972201. [DOI] [PubMed] [Google Scholar]
- García-Fulgueiras A, Navarro C, Fenoll D, García J, González-Diego P, Jiménez-Buñuales T, Pelaz C. Legionnaires’ disease outbreak in Murcia, Spain. Emerging Infectious Diseases. 2003;9(8):915–921. doi: 10.3201/eid0908.030337. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Haupt TE, Heffernan RT, Kazmierczak JJ, Nehls-Lowe H, Rheineck B, Powell C, Davis JP. An outbreak of Legionnaires disease associated with a decorative water wall fountain in a hospital. Infection Control and Hospital Epidemiology. 2012;33(2):185–191. doi: 10.1086/663711. [DOI] [PubMed] [Google Scholar]
- Levin-Rector A, Wilson EL, Fine AD, Greene SK. Refining historical limits method to improve disease cluster detection, New York City, New York, USA. Emerging Infectious Diseases. 2015;21(2):265–272. doi: 10.3201/eid2102.140098. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Mahoney FJ, Hoge CW, Farley TA, Barbaree JM, Breiman RF, Benson RF, McFarland LM. Communitywide outbreak of Legionnaires’ disease associated with a grocery store mist machine. Journal of Infectious Diseases. 1992;165(4):736–739. doi: 10.1093/infdis/165.4.xxxx. [DOI] [PubMed] [Google Scholar]
- Marston BJ, Plouffe JF, File TM, Jr, Hackman BA, Salstrom SJ, Lipman HB, Breiman RF. Incidence of community-acquired pneumonia requiring hospitalization. Results of a population-based active surveillance study in Ohio. The Community-Based Pneumonia Incidence Study Group. Archives of Internal Medicine. 1997;157(15):1709–1718. [PubMed] [Google Scholar]
- Mérault N, Rusniok C, Jarraud S, Gomez-Valero L, Cazalet C, Marin M, Buchrieser C. Specific real-time PCR for simultaneous detection and identification of Legionella pneumophila serogroup 1 in water and clinical samples. Applied and Environmental Microbiology. 2011;77(5):1708–1717. doi: 10.1128/AEM.02261-10. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Mouchtouri VA, Goutziana G, Kremastinou J, Hadjichristodoulou C. Legionella species colonization in cooling towers: Risk factors and assessment of control measures. American Journal of Infection Control. 2010;38(1):50–55. doi: 10.1016/j.ajic.2009.04.285. [DOI] [PubMed] [Google Scholar]
- Nazarian EJ, Bopp DJ, Saylors A, Limberger RJ, Musser KA. Design and implementation of a protocol for the detection of Legionella in clinical and environmental samples. Diagnostic Microbiology and Infectious Disease. 2008;62(2):125–132. doi: 10.1016/j.diagmicrobio.2008.05.004. [DOI] [PubMed] [Google Scholar]
- New York City Department of Health and Mental Hygiene. 2015 alert # 1: Possible increase in Legionnaire’s disease in the Bronx. 2015a Retrieved from https://www1.nyc.gov/assets/doh/downloads/pdf/han/alert/legionella-in-bronx.pdf.
- New York City Department of Health and Mental Hygiene. Legionellosis, 2000–2014. 2015b Retrieved from EpiQuery: NYC interactive health data system—communicable disease surveillance data (CDSD), https://a816-healthpsi.nyc.gov/epiquery/CDSS/index.html.
- Sabrià M, García-Nuñez M, Pedro-Botet ML, Sopena N, Gimeno JM, Reynaga E, Rey-Joly C. Presence and chromosomal subtyping of Legionella species in potable water systems in 20 hospitals of Catalonia, Spain. Infection Control and Hospital Epidemiology. 2001;22(11):673–676. doi: 10.1086/501843. [DOI] [PubMed] [Google Scholar]
- Shivaji T, Sousa Pinto C, San-Bento A, Oliveira Serra LA, Valente J, Machado J, Vasconcelos P. A large community outbreak of Legionnaires disease in Vila Franca de Xira, Portugal, October to November 2014. Euro Surveillance. 2014;19(50):20991. doi: 10.2807/1560-7917.es2014.19.50.20991. [DOI] [PubMed] [Google Scholar]
- White PS, Graham FF, Harte DJ, Baker MG, Ambrose CD, Humphrey AR. Epidemiological investigation of a Legionnaires’ disease outbreak in Christchurch, New Zealand: The value of spatial methods for practical public health. Epidemiology and Infection. 2013;141(4):789–799. doi: 10.1017/S0950268812000994. [DOI] [PMC free article] [PubMed] [Google Scholar]