Abstract
Efficient ventilation in hospital airborne isolation rooms is important vis-à-vis decreasing the risk of cross infection and reducing energy consumption. This paper analyses the suitability of using a displacement ventilation strategy in airborne infection isolation rooms, focusing on health care worker exposure to pathogens exhaled by infected patients. The analysis is mainly based on numerical simulation results obtained with the support of a 3-D transient numerical model validated using experimental data. A thermal breathing manikin lying on a bed represents the source patient and another thermal breathing manikin represents the exposed individual standing beside the bed and facing the patient. A radiant wall represents an external wall exposed to solar radiation. The air change efficiency index and contaminant removal effectiveness indices and inhalation by the health care worker of contaminants exhaled by the patient are considered in a typical airborne infection isolation room set up with three air renewal rates (6 h-1, 9 h-1 and 12 h-1), two exhaust opening positions and two health care worker positions. Results show that the radiant wall significantly affects the air flow pattern and contaminant dispersion. The lockup phenomenon occurs at the inhalation height of the standing manikin. Displacement ventilation renews the air of the airborne isolation room and eliminates the exhaled pollutants efficiently, but is at a disadvantage compared to other ventilation strategies when the risk of exposure is taken into account.
Introduction
Hospital facilities are places with a high risk of cross infection between their occupants. Studies in European hospitals [1] indicate that nosocomial infections contribute significantly to morbidity and mortality rates and that many of these infections are transmitted by airborne pathogens [2]. Everyday pulmonary activities, like breathing [3], coughing [4,5], sneezing [6], talking [3], are sources of bio-aerosols [7] that may be laden with the pathogens responsible for infectious disease transmission. Once the bio-aerosols leave the infected person their fate depends on multiple and complex factors [7–10]. One of the most important factors is undoubtedly the airflow pattern, both in the room as a whole as well as in the microenvironment around the source patient and the vulnerable individual.
Airborne infection isolation room
If the appropriate measures are not taken, the bio-aerosols emitted by patients hospitalized with an airborne disease may be dispersed uncontrollably around the airborne infection isolation room (AIIR) or the rest of the hospital [11]. Different methods and technologies are available to provide adequate protection to people who pass through a hospital [12]. One of the recommended measures is to maintain a negative pressure with respect to the surrounding area so that air flows into the room and not in the opposite direction when doors are open. Unfortunately, negative pressure briefly disappears during door operation and air leakage is virtually inevitable [13]. Many guidelines and regulations [14–18] related to airborne isolation rooms (AIIR) advise or require that access to the room should be through an anteroom in order to minimize escape of contaminated air [19,20]. Yet neither the negative pressure nor the anteroom prevents the risk for the person entering the AIIR. Only personal self-protection measures and a suitable ventilation strategy reduce the possibility of contagion [21].
With regard to ventilation, one common recommendation is to use high renewal rates to dilute and remove pathogens [22]. However, this does not prevent the appearance of stagnant zones and short-circuiting, resulting in “clean” and “polluted” areas of exhaled pathogens with the subsequent risk of high cross-infection rates. Several studies indicate that the design of a ventilation system and the resulting airflow patterns play a more important role than just air renewal rates alone [23,24]. Airflow patterns generated by ventilation systems can be controlled, and recent research has focused on providing good air distribution rather than on maintaining high rates of air renewal as a strategy to reduce the risk of airborne contagion [25–30].
Displacement ventilation
Various ventilation strategies such as mixing ventilation (MV) and displacement ventilation (DV) offer different possibilities to protect people from airborne cross infection [10,31]. MV is the most widely applied strategy in hospital patient rooms. However, in recent years DV has emerged as an alternative. Some studies have shown that DV is more energy efficient [32]. Standardisation associations have developed DV guidelines and recommendations for designers.
DV systems were initially developed to remove thermal loads in industrial warehouses due to their ability to concentrate heat and pollutants above the occupied zone. DV systems are characterized by thermal and mass stratification such that they cannot be modelled with the fully mixed room air approach [33]. In DV, cool air is supplied into the lower part of the room using low impulse diffusers. This slow moving fresh air fills the room from below, is heated and rises to the ceiling, where the exhaust is located. There must be heat sources for DV to work. As breathing is also a heat and pollutant source, contaminants might be transported directly to the upper part of the room. DV offers the possibility of working with two zones, a low zone with clean air, and an upper zone with pollutants. Some authors report that it is possible to design DV hospital patient rooms that have low human exposure to bio-aerosols that containing pathogens [32,34], although in certain situations high exposure may also exist in rooms with DV [35–37].
Objective and methodology
The aim of this work is to evaluate the suitability of applying the DV strategy in AIIRs. The analysis is mainly based on numerical simulation results obtained with the support of computational fluid dynamics (CFD). The interaction between the different air flows -breathing flows [38], convective flows around human bodies [39], thermal plumes above heat sources, rising boundary layer flow at the warm wall together with large-scale air movements due to room air flow instabilities- is so complex that it is difficult to approach the problem directly. Initially, dispersion of contaminants exhaled by a single person standing in an indoor environment was studied [40]. Later, a second person facing the first was added to analyse the interaction between the respiration flows of both people [41]. These two previous studies have enabled an adequate procedure to be established for analysing the role of ventilation in the risk of cross-infection between patient and susceptible health care worker caused by the airborne pathogens exhaled during breathing in an AIIR with DV. Using the validated model, twelve different numerical tests are carried out to analyse how air renewal rates, the position of the health care worker, and the position of air exhaust openings affect the risk of cross infection.
Test room and experimental setup
The experimental study of a patient (P) lying on a hospital bed and a health care worker (HCW) standing close to the bed in a typical AIIR room (Fig 1) [14,15,42,43] was carried out in a test room at Cordoba University, 4.5 m (long), 3.3 m (wide), and 2.8 m (high). The two thermal breathing manikins have the same geometry. The total sensible heat emitted for each manikin corresponds to a metabolic rate of 1 met for the HCW and 0.7 met for the patient, 80 W and 70 W, respectively. There is an external heat gain of 500 W in the 4.5 m wall opposite the HCW, which represents an external wall exposed to solar radiation. The remaining walls as well as the floor and ceiling are adiabatic as the chamber is inside a lab at the same temperature.
A displacement flow diffuser (QLV-180-200-800, Trox, Germany) are used as supply air unit for the hospital room, and two exhaust openings were located on the opposite wall, just below the ceiling. The ventilation system was set at three different air change rates of 12, 9 and 6 ACH, supplying air at 21.8°C, 20.6°C and 18.2°C, respectively to maintain the same mean room temperature. Part of the effective area of the displacement diffuser is partially covered during the 9 ACH and 6 ACH tests in order to maintain the same supply velocity. Information about breathing manikins, measuring instruments and others details of these experiments can be found in [44].
Numerical simulation
Indices for quantifying the ventilation and infection risk
The ventilation system of a room can pursue different aims: thermal comfort, air renewal, elimination of gaseous or suspended contaminants, avoiding risk of infection, etc. Depending on the activities carried out in the room, one aim or another will prevail. Specific indices exist to quantify the extent to which each aim is achieved.
The most basic index is air changes per hour (ACH). To calculate ACH, only the air volume of the room and the air flow rate need to be known. This index is commonly used in guidelines and recommendations.
The air change efficiency index (εa) is defined as the ratio between the minimum and the actual mean replacement times and can be calculated from the expression:
(1) |
where τn = V/Q, V is the room volume and Q is the flow rate of fresh air, i.e. τn is the inverse of the number of air changes per second, and is the average age of the air in the room. Air change efficiency only depends on the overall air flow pattern in the room, and takes values between 0 and 1.
If, in addition to knowing the ACH and the air flow pattern, the characteristics of the contaminant and the point of emission are also known, then the contaminant removal effectiveness index (εc) can be used. This index can take any positive value. Assuming that the air supplied to the room is contaminant free and that the flow is steady, εc is calculated by dividing the concentration of pollutant in the exhaust air ce by the average concentration in room :
(2) |
Finally, if the area to be protected is known -the surface of a printed circuit during manufacture, the instrument table during a surgical operation or the lungs of a person sharing a room with another infected person- the intake fraction (IF) index may be used. This index is the flow rate of contaminant that crosses the surface to be protected divided by the flow rate of contaminant that enters or is generated inside the room (Bennett et al., 2002). In order to assess the risk of cross-infection, the intake fraction is defined as the proportion of the cumulative mass of contaminant inhaled by the HCW to the mass of contaminant emitted in the patient's exhalation during the same period of time.
(3) |
Where QHCW, and QP are the instantaneous breathing flow rate of HCW and P, respectively, YHCW is the instantaneous mass fraction of N2O in the HCW inhalation air, and YP is the instantaneous mass fraction of N2O in the patient’s exhalation air.
Governing equations
Airborne cross infection between occupants is unsteady, non-isothermal and is a three-dimensional problem involving two species: air and contaminant. As modelling tool, CFD has been applied to simulate the unsteady airflow using the URANS method together with the RNG k–e turbulence model equations, mean age of air equation, the N2O mass fraction equation and includes the effect of thermal radiation using commercial software Ansys Fluent.
The local mean age of air τ in the whole fluid field is calculated solving the following conservation equation:
(4) |
where is the air velocity and Da is the mass diffusion coefficient [45]. A subroutine solving Eq (4) numerically is written, and the subroutine is built into the CFD-program. Once the average age of the air in the whole room is calculated, it is possible to directly evaluate εa according to Eq (1). is the average of τ in the whole room and τn can be calculated as the inverse of the number of air changes per second or as the average of τ in the air extractions. The two values coincide.
The CFD-program models the mixing and transport of two chemical species, air and N2O, by solving equations describing convection and diffusion for each component species without reactions. εc and IF can be calculated directly from their definitions. Since the model is transient, the time evolution of εc and IF can be calculated.
Radiation is introduced into the CFD model using the surface-to-surface radiation model [46]. The importance of thermal radiation in airflow with DV was examined experimentally in [47]. The RNG k–ε model that takes into account the low Reynolds-number effects in conjunction with enhanced wall treatment that combines a two-layer model with enhanced wall functions are used in these simulations. Pressure-velocity coupling was resolved using the PISO scheme. A second-order implicit transient formulation is chosen which is unconditionally stable with respect to time-step size. A second-order upwind discretization scheme is used for all equations [46].
In transient simulations (also in experiments) an error might occur during start-up and when letting simulations run sufficient time to achieve characteristic large eddy turnover time [48]. The initial conditions for non-steady computations are obtained for a steady simulation. The first 30 minutes of the transient simulation are discarded. Large eddy turnover time is a characteristic timescale for the domain l0/v0 where l0 is the largest scale of the room and v0 is the characteristic velocity. An estimation of v0 can be made by dividing the ventilation flow rate by a half section of the test chamber, which gives a large eddy turnover time of five minutes for 6 ACH. A large eddy turnover time is inversely proportional to ACH if the remaining parameters remain unchanged. In order to obtain a suitable temporal average, total times of 20, 15 and 10 minutes are simulated for 6, 9 and 12 ACH, respectively (Table 1). To capture the effects of the smaller time scales related to the breathing process, a time step of 0.02 s is selected.
Table 1. Conditions of the CFD test performed.
Simulation nomenclature |
Exhaust openings wall | Radiant wall | ACH | Supply air flow (m3/h) | Supply air temperature (°C) | Simulation time (min) |
---|---|---|---|---|---|---|
EN_12* | East | North | 12 | 500 | 21.8 | 10 |
ES_12 | East | South | ||||
WN_12 | West | North | ||||
WS_12 | West | South | ||||
EN_09* | East | North | 9 | 375 | 20.6 | 15 |
ES_09 | East | South | ||||
WN_09 | West | North | ||||
WS_09 | West | South | ||||
EN_06* | East | North | 6 | 250 | 18.2 | 20 |
ES_06 | East | South | ||||
WN_06 | West | North | ||||
WS_06 | West | South |
(*) Experimental test
Computational domain
The domain of the computational model mimics in detail the experimental geometry of the life-size hospital isolation room. Most of the domain is built with a hexahedron mesh. A tetrahedral mesh has been employed near the diffuser and near to the manikin’s surface due to their geometry complexity. Mesh refinement was performed around the manikins, the exhausts, the walls, and the displacement diffuser since high velocity and temperature gradients are expected. The high concentration, velocity and temperature gradients require a very fine local grid system at the manikins’ faces and in the exhalation zones [49]. The shape of the manikins for the numerical simulations reproduces a thermal breathing manikin used by others authors [50,51]. Detailed information about the manikins’ shape and mesh can be found in [41]. A sensitivity study was carried out with successive refinements of the exhalation zones and around the displacement diffuser. A final mesh of nearly one and a half million cells is used.
Boundary conditions
The CFD model of a patient and a HCW in AIIR faithfully reproduces the experimental conditions [44]. The lying manikin (also known as the patient or source manikin, SM) exhales through the mouth and inhales through the nose. The standing manikin (also known as the HCW or target manikin, TM) exhales and inhales through the nose. Breathing functions are a very important point in these simulations [52]. The two manikins breathe following a sinusoidal function. For the patient manikin, the tidal volume is 0.57 litres and the breathing frequency is 20 breaths/minute. For the HCW manikin, the tidal volume is 0.66 litres and the breathing frequency is 15 breaths/minute. The patient manikin thus performs four full breaths in a 12-second period and the HCW manikin three full breaths during the same period. Velocity is normal and uniform in the HCW’s nostrils and in the patient’s mouth. The temperature of expired air in the two manikins is 34°C. The mass fraction of N2O in the exhaled air of the patient manikin is YP = 0.027.
The boundary condition for the displacement diffuser is a uniform velocity of 0.926 m/s, which is normal for vertical diffuser surfaces. For the 12 ACH simulations, the entire front area of the displacement diffuser is used as an inlet. The upper quarter and upper half of the displacement diffuser front area are considered as walls for the 9 and 6 ACH simulations, respectively, in order to maintain the same inlet velocity [53]. The effective area of the displacement diffuser is taken into account adding the corresponding momentum/volume source in a sub-domain in front of the diffuser [54].
The air leaves the room through two exhaust openings located in the same wall as the displacement diffuser (west) or in the opposite wall (east). A pressure-outlet boundary condition is imposed in the exhaust openings.
In order to maintain the same mean indoor temperature for all tests, the air is supplied at a temperature of 21.8°C, 20.6°C, and 18.2°C for 12, 9 and 6 ACH, respectively. The ceiling, floor and all the walls except one 4.5 m × 2.8 m wall (north or south wall) are considered adiabatic. In this non-adiabatic wall a heat flow of 39.7 W/m2 is imposed as the boundary condition. This represents a glazed wall with a transmission coefficient of 4 Wm-2K-1 with 10°C temperature difference between indoor and outdoor air. The lying and standing manikins have a thermal load of 70 W and 80 W, respectively.
Validation of numerical results with experimental data
In rooms with displacement ventilation, thermal stratification is generated. The temperature of the exhaled air is higher than the temperature of the ambient air. The effects of buoyancy will play an important role in both the evolution of exhaled air and the dispersion of the associated pathogens. It is therefore crucial to correctly predict the room’s temperature field. This numerical model was previously used to study the dispersion of exhaled contaminants by the mouth of a person standing in a room with DV. The numerical results were compared to data from experiments performed in a full-scale laboratory at the University of Aalborg [55]. It was found that the numerical model was able to accurately reproduce both the thermal stratification in the room and the deflection of the exhaled air jet. Details on the validation of the temperature field are shown in [40].
Exhaled pathogens do not disperse in the same way when expired through the nose or mouth. How the vulnerable individual breathes also affects the microenvironment near the face and, therefore, the risk of inhaling pathogens. This CFD model was used in a previous study to analyse how the way of breathing influences the risk of cross-infection between two people standing facing each other at different distances in a room with DV. The results of the CFD simulations were compared to experimental data obtained in the Alborg laboratory with two manikins at different distances and exhaling through the mouth and inhaling through the nose. Details of this new validation are shown in [41].
The numerical model is now validated again with the experimental results obtained in a real-scale laboratory at the University of Córdoba [44]. Comparing the results of two global ventilation efficiency indices, the air change efficiency εa and the contaminant removal effectiveness εc clearly evidences how the numerical model is able to capture the experimental tendencies and to reproduce the values to a reasonable degree of concurrence (Fig 2). The experimental values of contaminant removal effectiveness are slightly higher than the numerical values. The possibility that these differences are due to difficulties that emerge when measuring these indexes using photoacoustic spectroscopy cannot be ruled out.
Results and discussion
Temporal evolution of contaminant inhaled
The exhalation, dispersion and inhalation of contaminants are transient phenomenon. Numerical data provide a detailed temporal evolution of the amount of contaminant inhaled by the HCW. A breathing cycle (inhalation and exhalation) lasts three seconds for the P and four seconds for the HCW. Each 12 seconds both start at the same time, although the two breaths are out of phase throughout the cycle. This progressive phase displacement might cause the amount of contaminant inhaled by the HCW in each of the three cycle inhalations to differ. The phase-averaged method was used in Fig 3 to show the concentration of N2O inhaled by the HCW in 12-second cycles. It is worth noticing that the average amount of contaminant inhaled in the three inhalations is the same. This is a clear indication that the interaction between the breaths of the two manikins is very weak due to the great distance between the breathing zones of the two manikins [41]. Between the mouth of the patient and the nose of the HCW there is a distance of 0.94 m in a straight line. The nose of the HCW is 0.53 m away from the patient's exhalation axis.
It should also be mentioned that the amount of pollutant inhaled in each 12-second cycle changes significantly. In other words, cyclical dispersion is very noticeable, especially for low ACH. This result shows that the dispersion of exhaled contaminants and their subsequent inhalation are transient phenomena due to the transient nature of the airflow pattern in the area between P and HCW. The overall airflow in the room also exhibits a transient behaviour with room airflow frequencies lower than the manikins’ breathing frequencies. These results are in line with previous works [41,56].
Airflow pattern. Air change efficiency
In a perfect mixing ventilation (PMV) flow, air composition is equal throughout the whole room and no contaminant concentration gradients are present. PMV implies infinitely rapid diffusion and perfect displacement ventilation PDV implies absolute absence of diffusion [45]. PMV and PDV are idealized theoretical flow patterns that never occur in practice but which are, nevertheless, useful concepts for comparative purposes. In a perfect mixing ventilation flow εa = 0.5. In a perfect displacement ventilation flow εa = 1.
As expected, in all the cases analysed, 0.5<εa<1.0, when using the DV strategy. There is a clear correlation between the ventilation efficiency and the position of the air exhaust openings (Fig 4). With the exhaust openings in front of the displacement diffuser, in the wall of the bed, average ventilation efficiency is εa = 0.56. With the exhaust openings in the wall opposite the bed the average efficiency increases significantly, εa = 0.69. The air flow pattern in the room is closer to that of PDV. This behaviour is in line with other authors’ observations.
The air change efficiency index is also correlated with the position of the radiant wall. In all cases, when the radiant wall is behind the HCW (empty symbols) air change efficiency is greater than when it is opposite the HCW (full symbols), probably because thermal loads are more balanced compared to the room’s plane of symmetry. No clear correlation can be established between air change efficiency and ACH.
Dispersion of the contaminant. Contaminant removal effectiveness
DV provides vertical thermal stratification that determines contaminant dispersion in the room. In order to maintain the same mean temperature in the room with less ACH, the difference between the air inlet temperature and the average temperature of the room is increased. Up to a height of 1.1 m, the vertical temperature gradient is greater for low ACH (Fig 5A), whereas from 1.1 m to the ceiling the gradients are almost equal for all ACH. This behaviour can also be seen for the other simulated cases. These numerical results are consistent with experimental observations [57,58].
As the contaminant source is also a source of heat, the contaminant will be transported directly to the top of the room [59]. The pollutant is expected to be distributed according to a two-zone model [35], a clean zone in the lower part (y<yst) of the room and an unclean zone in the upper part (y>yst). The mean concentration of N2O in horizontal planes is shown in Fig 5B. Below the patient exhalation height, z = 0.78 m, N2O concentration is practically negligible. The general airflow pattern in the room, the momentum of the patient's exhalation jet and the convective effects of the exhalation jet and the thermal plume that forms above the patient cause the pollutant to rise. The average N2O concentration in horizontal planes increases rapidly, reaching the maximum at a height between 1.6 m and 1.7 m (Fig 5B). The exhaled air is concentrated at the height of the HCW’s head. This behaviour is the so-called lockup phenomenon and has recently been studied numerically [59] and experimentally [60]. The lockup phenomenon was more intense when the ventilation rate decreased, since a low ventilation rate causes a large temperature gradient [59]. The stratification height increased as the ventilation rate increased.
In a PMV flow, the concentration of contaminant in the room is homogenous, such that the concentration in the exhaust air is the same as the mean concentration in the room, with contaminant removal effectiveness being 1. In all the cases analysed in the present study, contaminant removal effectiveness εc is between 0.73 and 2.0 (Fig 6). Only when the radiant wall is behind the HCW and ACH is 12, is εc below 1.0. No clear correlation could be established between εc or with the position of the radiant wall or the ACH or with the position of the exhaust openings. Moreover, unlike what was observed with εa, it seems that the exhaust positions barely influence εc.
In a room with PMV and steady state conditions, the contaminant concentration, YPMV, would be homogeneous and inversely proportional to ACH:
(5) |
where QP is the patient’s tidal volume by their breathing frequency, QHCW is the HCW tidal volume by their breathing frequency, and Qs is the supply air flow. The YPMV values for 6, 9 and 12 ACH are 0.0028 YP, 0.0018 YP and 0.0014 YP, respectively. Between approximately 1.3 m and 1.9 m in height ˗the HCW inhales at a height of 1.52 m˗ the mean N2O concentration in horizontal planes is higher than the corresponding YPMV (Fig 5B). However, this does not mean that the HCW inhales air with that mean concentration as can be seen by comparing Fig 3 and Fig 5B. Firstly, pollutant distribution in horizontal planes is not even and, secondly, the convective boundary layer around the HCW enters the air from the lower part, leading to the HCW breathing zone. Fig 7 shows the normalised distribution of N2O averaged over time in horizontal planes at the inhalation height.
The distribution of contaminant in z = 1.52 m planes clearly depends on the position of the radiant wall and the ACH number but is barely influenced by the position of the exhaust openings. When the radiant wall is opposite the HCW, the contaminant cloud is deviated towards the radiant wall away from the HCW. This may be due to the convective effects generated by the radiant wall and the horizontal momentum of HCW exhalation. However, when the radiant wall is behind the HCW, the contaminant is distributed more symmetrically with respect to the room’s vertical plane of symmetry. The lack of symmetry in N2O distribution at z = 1.52 m affects N2O concentration in each of the two extractions. This tendency is less pronounced for the 12 ACH cases.
Infection risk. Intake fraction
The intake fraction index was obtained as the ratio between the mass of N2O inhaled by the HCW during the time simulated and the total mass of N2O exhaled by the patient at the same time. In a room with PMV and steady state conditions, the intake fraction index, IFPMV, would be homogeneous and inversely proportional to ACH:
(6) |
If the breathing rate by tidal volume of both manikins were equal then IFPMV = YPMV/YP. The YPMV values for 6, 9 and 12 ACH are 0.0024, 0.016 and 0.0012, respectively. Fig 8 shows the IF values for all the DV cases analysed together with the IF values that would correspond to PMV. As ACH increases, IF values are expected to decrease. However, when the radiant wall is opposite the HCW (Fig 8A) the lowest IF values are for 9 ACH. This unexpected behaviour was also observed in the validation experiments [44].
As with the results shown in Fig 7, the position of the exhaust openings does not have a significant influence on IF. In 8 of the 12 cases analysed IF is clearly higher than IFPMV, the amount of inhaled contaminant, and therefore the risk of infection, is clearly higher than what would correspond to PMV. These results discourage the use of displacement ventilation in AIIRs.
Comparison between indexes
Both εa and εc are global indices and provide valuable information for quantifying the quality of ventilation in the whole room, regardless of the ACH. However, the spatial distribution and temporal evolution of both the contaminant concentration and contaminant age are neither homogeneous nor static. In order to estimate the risk of infection, a local index such as the IF is more appropriate. The drawback, however, is that IF depends on ACH. If the aim is to compare cases with different ACH, it is necessary to normalise. One possible normalisation is with the IF that would correspond to a PMV, IFPMV. The three indices shown in Table 2 are independent of ACH.
Table 2. Indices.
Case | εa | εc | IFIFPMV |
---|---|---|---|
EN_12 | 0.56 | 1.74 | 2.24 |
ES_12 | 0.53 | 0.73 | 0.35 |
WN_12 | 0.70 | 1.65 | 2.52 |
WS_12 | 0.70 | 0.89 | 0.16 |
EN_09 | 0.59 | 1.14 | 0.72 |
ES_09 | 0.56 | 1.23 | 2.70 |
WN_09 | 0.71 | 1.29 | 0.14 |
WS_09 | 0.67 | 1.17 | 2.25 |
EN_06 | 0.56 | 1.61 | 1.89 |
ES_06 | 0.56 | 2.07 | 4.88 |
WN_06 | 0.68 | 1.43 | 2.00 |
WS_06 | 0.62 | 1.47 | 3.67 |
Table 2 shows that air change efficiency is not correlated either with contaminant removal effectiveness or intake fraction. There is also no clear correlation between contaminant removal effectiveness and intake fraction. The position of the HCW and the number of ACH have virtually no influence on air change efficiency The position of the exhaust openings has a greater impact on εc than on εa, whereas changing the position of the HCW has a greater effect on εa than on εc. Only in two of the twelve cases analysed is IF/IFPMV clearly below 1. Therefore, although DV is a suitable strategy to renew the air in the room and to eliminate exhaled contaminants (high values of εa and εc) it is not as effective at decreasing cross-infection risk.
Conclusions
Detailed transient CFD tests have been carried to determine the suitability of a DV strategy in a representative case study of a one-bed hospital room. Two exhaust configurations, two external wall positions and three air renewal rates have been tested. In view of the results, the following conclusions may be drawn:
In most of the DV cases analysed in this paper, the values of air change efficiency and contaminant removal effectiveness are very promising. Nevertheless, analysing AIIR ventilation system performance based exclusively on global indices, such as air change efficiency or contaminant removal effectiveness, entails major limitations that can lead to erroneous decisions. Intake fraction provides more useful information in this type of rooms. This conclusion is supported by the lack of correlation between IF and the rest of the indices.
A priori, it could be assumed that an increase in the number of ACH leads to a decrease in the risk of infection. However, it has been found that an increase in the ventilation rate could not decrease exposure and in certain circumstances may indeed increase it. This conclusion concurs with other works [23,61,62]. The reason for this behaviour is unknown, and further analyses are required to understand the phenomenon. Local airflow pattern plays a crucial role in the transport and dispersion of exhaled pathogens and, consequently, the risk of cross-infection.
Numerous works have studied the impact of the position of the air inlets and exhaust openings or ACH in ventilation efficiency. In most of the works, the room envelope was considered to be well insulated and therefore adiabatic. This work has been shown that the presence of a radiant wall significantly affects the air flow pattern and contaminant dispersion. For the cases analysed, the relative position between the HCW and the radiant wall has a greater impact on the risk of infection than the extraction position or the number of ACH. When the radiant wall is opposite the HCW, the combined convective effect of the wall and the exhaled air drive the pollutant cloud away from the HCW.
In all the DV cases analysed, contaminants exhaled by the patient accumulate at the HCW inhalation height. This is the well-known lockup phenomenon. However, the air inhaled by the HCW comes from lower layers due to the effect of the convective boundary layer around the HCW. This argument has been used previously to recommend the use of DV in this type of room. However, despite this effect, the results obtained in this work do not advocate the use of DV. IF is no better than what may be expected for a PMV air flow pattern. It would be interesting to analyse the suitability of other ventilation strategies, such as downward-directed ventilation, for airborne infection isolation rooms.
Limitations of the work
This work fails to consider either human movement or the movement of opening and closing doors. An analysis of how human movement affects the air flow pattern of displacement ventilation would prove extremely valuable. A further limitation is that the external wall is simulated with only one heat gain value. In a real situation, heat gain changes during the day and during the seasons. In addition, the study only analyses the exhalation of small respiratory bio-aerosols during breathing. Taking into account other pulmonary activities, such as coughing or sneezing, which expel larger droplets with higher initial momentum, would provide further insights.
Microbial survival in the environment is another issue not dealt with as it also lies beyond the scope of this article. The results obtained and discussed in this work are obtained under specific conditions which, whilst representative of the most common situations, do not represent every possible scenario. For instance, if the distance between the people or the height at which the contaminants are exhaled were changed then exposure to the contaminants might change. Despite these limitations, however, the results might prove helpful in the design of AIIRs in order to implement ventilation strategies where the exposure to exhaled contaminants may be reduced in most situations.
Acknowledgments
The authors acknowledge the financial support received from the Ministry of Finance and Competitiveness, State Secretariat for Research, Development and Innovation, Spain, the National R&D project with reference DPI2014-55357-C2-1-R, entitled “Ventilation system influence on airborne transmission of human exhaled bioaerosols. Cross infection risk evaluation”. This project is co-financed by the European Regional Development Fund (ERDF).
Abbreviations
- ACH
Air change per hour, h-1
- AIIR
Airborne infection isolation room
- B
Bed
- CFD
Computational fluid dynamics
- DD
Displacement diffuser
- DV
Displacement ventilation
- E
Exhaust openings located on the upper part of the east wall
- EN
Ventilation system configuration combining E and N
- ES
Ventilation system configuration combining E and S
- HCW
Health care worker
- IF
Intake fraction index
- IFPMV
Intake fraction index with PMV
- MV
Mixing ventilation
- N
External wall heat gain on north wall
- P
Patient
- PMV
Perfect mixing ventilation
- PDV
Perfect displacement ventilation
- Q
Air flow rate in the room, m3/s
- RANS
Reynolds-Averaged Navier-Stokes equations
- S
External wall heat gain on south wall
- SM
Source manikin (P)
- TM
Target manikin (HCW)
- URANS
Unsteady-RANS
- W
Exhaust openings located on the upper part of the west wall
- WN
Ventilation system configuration combining W and N
- WS
Ventilation system configuration combining W and S
- c
Average concentration of contaminant in the room
- ce
Contaminant concentration in the exhaust air
- Da
Mass diffusion coefficient, m2/s
- εa
Air change efficiency index
- εc
Contaminant removal effectiveness
- l0
Largest scale of the room, m
Local mean age of the air, s
- τn
Nominal time constant, s
- V
Room volume, m3
- v0
Characteristic air velocity, m/s
- YP
Mass fraction of N2O in the air exhaled by P
- YPMV
Mass fraction of N2O in a room with PMV
Data Availability
All relevant data are within the manuscript.
Funding Statement
The authors acknowledge the financial support received from the Ministry of Finance and Competitiveness, State Secretariat for Research, Development and Innovation, Spain, the National R&D project with reference DPI2014-55357-C2-1-R, entitled “Ventilation system influence on airborne transmission of human exhaled bioaerosols. Cross infection risk evaluation”. This project is co-financed by the European Regional Development Fund (ERDF). The funders had no role in study design, data collection and analysis, decision to publish, or preparation of the manuscript.
References
- 1.Kaoutar B, Joly C, L’Hériteau F, Barbut F, Robert J, Denis M, et al. Nosocomial infections and hospital mortality: a multicentre epidemiological study. J Hosp Infect. 2004;58: 268–275. 10.1016/j.jhin.2004.06.006 [DOI] [PubMed] [Google Scholar]
- 2.Kowalski W. Hospital Airborne Infection Control. Press C, editor. Taylor & Francis Group; 2012. [Google Scholar]
- 3.Gupta JK, Lin C-H, Chen Q. Characterizing exhaled airflow from breathing and talking. Indoor Air. Blackwell Publishing Ltd; 2010;20: 31–39. 10.1111/j.1600-0668.2009.00623.x [DOI] [PubMed] [Google Scholar]
- 4.Gupta JK, Lin CH, Chen Q. Flow dynamics and characterization of a cough. Indoor Air. Blackwell Publishing Ltd; 2009;19: 517–525. 10.1111/j.1600-0668.2009.00619.x [DOI] [PubMed] [Google Scholar]
- 5.Tang JW, Nicolle A, Pantelic J, Koh GC, Wang LD, Amin M, et al. Airflow Dynamics of Coughing in Healthy Human Volunteers by Shadowgraph Imaging: An Aid to Aerosol Infection Control. PLoS One. Public Library of Science; 2012;7: e34818 10.1371/journal.pone.0034818 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 6.Tang JW, Nicolle AD, Klettner CA, Pantelic J, Wang L, Suhaimi A Bin, et al. Airflow dynamics of human jets: sneezing and breathing—potential sources of infectious aerosols. PLoS One. 2013;8: e59970 10.1371/journal.pone.0059970 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 7.Zhang H, Li D, Xie L, Xiao Y. Documentary Research of Human Respiratory Droplet Characteristics. Procedia Eng. Elsevier; 2015;121: 1365–1374. 10.1016/J.PROENG.2015.09.023 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 8.Xie X, Li Y, Chwang ATY, Ho PL, Seto WH. How far droplets can move in indoor environments; revisiting the Wells evaporation falling curve. Indoor Air. 2007;17: 211–225. 10.1111/j.1600-0668.2007.00469.x [DOI] [PubMed] [Google Scholar]
- 9.Morawska L. Droplet fate in indoor environments, or can we prevent the spread of infection? Indoor Air. Blackwell Publishing Ltd; 2006;16: 335–347. 10.1111/j.1600-0668.2006.00432.x [DOI] [PubMed] [Google Scholar]
- 10.Tang JW, Li Y, Eames I, Chan PKS, Ridgway GL. Factors involved in the aerosol transmission of infection and control of ventilation in healthcare premises. J Hosp Infect. Elsevier; 2006;64: 100–114. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 11.Kao PH, Yang RJ. Virus diffusion in isolation rooms. J Hosp Infect. 2006;62: 338–345. 10.1016/j.jhin.2005.07.019 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 12.Bolashikov ZD, Melikov AK. Methods for air cleaning and protection of building occupants from airborne pathogens. 6th Int Conf Indoor Air Qual Vent &Energy Conserv Build (IAQVEC 2007), Sendai, Japan, 28–31 October, 2007. 2009;44: 1378–1385. 10.1016/j.buildenv.2008.09.001 [DOI] [PMC free article] [PubMed]
- 13.Tang JW, Nicolle A, Pantelic J, Klettner CA, Su R, Kalliomaki P, et al. Different types of door-opening motions as contributing factors to containment failures in hospital isolation rooms. PLoS One. 2013;8: e66663 10.1371/journal.pone.0066663 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 14.CDC. Guidelines for Preventing the Transmission of Mycobacterium tuberculosis in Health-Care Settings [Internet]. Morbidity and Mortality Weekly Report. 2005. p. 142. Available: http://www.cdc.gov/mmwr/preview/mmwrhtml/rr5417a1.htm [PubMed]
- 15.VACIC. Guidelines for the classification and design of isolation rooms in health care facilities [Internet]. Victorian Advisory Committee on Infection Control. Melbourne, Victoria, Australia: Department of Human Services—Victorian Advisory Committee on Infection Control; 2007. Available: http://www.health.vic.gov.au/ideas/regulations [Google Scholar]
- 16.AusHFG. Australasian Health Facility Guidelines [Internet]. 2009. Available: http://www.healthfacilityguidelines.com.au/guidelines.htm
- 17.NORDEN. Best practice in design and testing of isolation rooms in Nordic hospitals Rydock JP, Eian PK, Lindqvist C, Welling I, Welling I, editors. Nordic Innovation Centre. OSLO: Nordic Innovation Centre; 2004. p. 57. [Google Scholar]
- 18.NTC. Tuberculosis Infection Control: A Practical Manual for Preventing TB [Internet]. Francis J. Curry National Tuberculosis Center; 2007. Available: http://www.nationaltbcenter.edu/TB_IC/ [Google Scholar]
- 19.Subhash SS, Baracco G, Fennelly KP, Hodgson M, Radonovich LJ Jr. Isolation anterooms: Important components of airborne infection control. Am J Infect Control. Elsevier; 2013;41: 452–455. 10.1016/j.ajic.2012.06.004 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 20.Saarinen PE, Kalliomäki P, Tang JW, Koskela H. Large Eddy Simulation of Air Escape through a Hospital Isolation Room Single Hinged Doorway—Validation by Using Tracer Gases and Simulated Smoke Videos. Sznitman J, editor. PLoS One. 2015;10: e0130667 10.1371/journal.pone.0130667 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 21.Subhash SS, Baracco G, Fennelly KP, Hodgson M, Radonovich LJ. Isolation anterooms: Important components of airborne infection control. Am J Infect Control. Mosby; 2013;41: 452–455. 10.1016/j.ajic.2012.06.004 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 22.Hyttinen M, Rautio A, Pasanen P, Reponen T, Earnest GS, Streifel A, et al. Airborne Infection Isolation Rooms–A Review of Experimental Studies. Indoor Built Environ. 2011;20: 584–594. 10.1177/1420326X11409452 [DOI] [Google Scholar]
- 23.Pantelic J, Tham KW. Adequacy of air change rate as the sole indicator of an air distribution system’s effectiveness to mitigate airborne infectious disease transmission caused by a cough release in the room with overhead mixing ventilation: A case study. HVAC&R Res. Taylor & Francis; 2013;19: 947–961. 10.1080/10789669.2013.842447 [DOI] [Google Scholar]
- 24.Eames I, Tang JW, Li Y, Wilson P. Airborne transmission of disease in hospitals. J R Soc Interface. 2009;6: S697 10.1098/rsif.2009.0407.focus [DOI] [PMC free article] [PubMed] [Google Scholar]
- 25.Memarzadeh F, Xu W. Role of air changes per hour (ACH) in possible transmission of airborne infections Build Simul. Rockville Pike, Bethesda, Maryland, USA: Tsinghua University Press; 2012;5: 15–28. 10.1007/s12273-011-0053-4 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 26.Méndez C, San José JF, Villafruela JM, Castro F. Optimization of a hospital room by means of CFD for more efficient ventilation. Energy Build. 2008;40: 849–854. 10.1016/j.enbuild.2007.06.003 [DOI] [Google Scholar]
- 27.Villafruela JM, Castro F, San José JF, Saint-Martin J. Comparison of air change efficiency, contaminant removal effectiveness and infection risk as IAQ indices in isolation rooms. Energy Build. Elsevier B.V.; 2013;57: 210–219. 10.1016/j.enbuild.2012.10.053 [DOI] [Google Scholar]
- 28.Khan JA, Feigley CE, Lee E, Ahmed MR, Tamanna S. Effects of inlet and exhaust locations and emitted gas density on indoor air contaminant concentrations. Build Environ. 2006;41: 851–863. 10.1016/j.buildenv.2005.04.002 [DOI] [Google Scholar]
- 29.Hayashi T, Ishizu Y, Kato S, Murakami S. CFD analysis on characteristics of contaminated indoor air ventilation and its application in the evaluation of the effects of contaminant inhalation by a human occupant. Build Environ. 2002;37: 219–230. 10.1016/S0360-1323(01)00029-4 [DOI] [Google Scholar]
- 30.Khankari K. Airflow dynamics of a patient room. REHVA J. 2017;5: 52–58. [Google Scholar]
- 31.Jurelionis A, Gagytė L, Prasauskas T, Čiužas D, Krugly E, Šeduikytė L, et al. The impact of the air distribution method in ventilated rooms on the aerosol particle dispersion and removal: The experimental approach. Energy Build. 2015;86: 305–313. 10.1016/j.enbuild.2014.10.014 [DOI] [Google Scholar]
- 32.Melikov A, Mundt E, Mustakallio P, Nielsen P V. Displacement Ventilation, REHVA Guidebook 23 Kosonen R, editor. REHVA Federation of European Heating, Ventilation and Air Conditioning Associations; 2004. [Google Scholar]
- 33.Mateus NM, Carrilho da Graça G. A validated three-node model for displacement ventilation. Build Environ. 2015;84: 50–59. 10.1016/j.buildenv.2014.10.029 [DOI] [Google Scholar]
- 34.ASHRAE. Standard 170–2017—Ventilation of Health Care Facilitie. 2017.
- 35.Bjørn E, Nielsen P V. Dispersal of exhaled air and personal exposure in displacement ventilated rooms. Indoor Air. 2002;12: 147–164. 10.1034/j.1600-0668.2002.08126.x [DOI] [PubMed] [Google Scholar]
- 36.Li Y, Huang X, Yu ITS, Wong TW, Qian H. Role of air distribution in SARS transmission during the largest nosocomial outbreak in Hong Kong. Indoor Air. Munksgaard International Publishers; 2004;15: 83–95. 10.1111/j.1600-0668.2004.00317.x [DOI] [PubMed] [Google Scholar]
- 37.Qian H, Nielsen P V, Li Y, Hyldgaard CE. Airflow and contaminant distribution in hospital wards with a displacement ventilation system Proceedings of BEPH 2004—The 2nd International Conference on Built Environment and Public Health. Beijing: China Environmental Science Press; 2004. p. 355. [Google Scholar]
- 38.Bivolarova M, Kierat W, Zavrl E, Popiolek Z, Melikov A. Effect of airflow interaction in the breathing zone on exposure to bio-effluents. Build Environ. Pergamon; 2017;125: 216–226. 10.1016/j.buildenv.2017.08.043 [DOI] [Google Scholar]
- 39.Licina D, Melikov A, Sekhar C, Tham KW. Human convective boundary layer and its interaction with room ventilation flow. Indoor Air. 2015;25: 21–35. 10.1111/ina.12120 [DOI] [PubMed] [Google Scholar]
- 40.Villafruela JM, Olmedo I, Ruiz de Adana M, Méndez C, Nielsen PV. CFD analysis of the human exhalation flow using different boundary conditions and ventilation strategies. Build Environ. 2013;62 10.1016/j.buildenv.2013.01.022 [DOI] [Google Scholar]
- 41.Villafruela JM, Olmedo I, San-José JF. Influence of human breathing modes on airborne cross infection risk. Build Environ. 2016; 10.1016/j.buildenv.2016.07.005 [DOI] [Google Scholar]
- 42.Siegel JD, Rhinehart E, Jackson M, Chiarello L, Committee the HICPA. 2007 Guideline for Isolation Precautions: Preventing Transmission of Infectious Agents in Healthcare Settings [Internet]. 2007. Available: http://www.cdc.gov/ncidod/dhqp/pdf/isolation2007.pdf [DOI] [PMC free article] [PubMed] [Google Scholar]
- 43.Sehulster LM, Chinn RYW, Arduino MJ, Carpenter J, Donlan R, Ashford D, et al. Guidelines for environmental infection control in health-care facilities. Atlanta, GA 30333: U.S. Department of Health and Human Services Centers for Disease Control and Prevention (CDC); 2003. p. 249. [Google Scholar]
- 44.Berlanga FA, de Adana MR, Olmedo I, Villafruela JM, San José JF, Castro F. Experimental evaluation of thermal comfort, ventilation performance indices and exposure to airborne contaminant in an airborne infection isolation room equipped with a displacement air distribution system. Energy Build. 2018;158 10.1016/j.enbuild.2017.09.100 [DOI] [Google Scholar]
- 45.Roos A. On the effectiveness of ventilation. Eindhoven University of Technology. 1999. [Google Scholar]
- 46.FLUENT. Fluent 12.0 user’s guide Lebanon NFI, editor. Lebanon, NH: Fluent Inc.; 2009. [Google Scholar]
- 47.Li Y, Sandberg M, Fuchs L. Effects of thermal radiation on airflow with displacement ventilation: an experimental investigation. Energy Build. Elsevier; 1993;19: 263–274. 10.1016/0378-7788(93)90011-I [DOI] [Google Scholar]
- 48.Knight KJ, Debus KK. Practical application of the LES method to mixing in large indoor spaces. ASME 2005 International Mechanical Engineering Congress and Exposition. Orlando, Florida USA; 2005. pp. 587–594. [Google Scholar]
- 49.Liu L, Li Y. Simulation of Interpersonal Transport of Expiratory Droplets and Droplet Nuclei between Two Standing manikins. BuildSim-Nordic. Lillestrøm, Norway; 2012. [Google Scholar]
- 50.Xu C, Nielsen P V, Gong G, Jensen RL, Liu L. Influence of air stability and metabolic rate on exhaled flow. Indoor Air. 2014;25: 198–209. 10.1111/ina.12135 [DOI] [PubMed] [Google Scholar]
- 51.Nielsen P V. Control of airborne infectious diseases in ventilated spaces. J R Soc Interface. 2009;6: S747–S755. 10.1098/rsif.2009.0228.focus [DOI] [PMC free article] [PubMed] [Google Scholar]
- 52.Bulinska A, Bulinski Z. A CFD analysis of different human breathing models and its influence on spatial distribution of indoor air parameters. Comput Assist Methods Eng Sci. 2015;22: 213–227. Available: http://http//cames.ippt.gov.pl/index.php/cames/article/view/23 [Google Scholar]
- 53.Berlanga FA, Olmedo I, de Adana MR, Villafruela JM, José JFS, Castro F. Experimental assessment of different mixing air ventilation systems on ventilation performance and exposure to exhaled contaminants in hospital rooms. Energy Build. Elsevier; 2018;177: 207–219. 10.1016/j.enbuild.2018.07.053 [DOI] [Google Scholar]
- 54.Einberg G, Hagström K, Mustakallio P, Koskela H, Holmberg S. CFD modelling of an industrial air diffuser—predicting velocity and temperature in the near zone. Build Environ. 2005;40: 601–615. 10.1016/j.buildenv.2004.08.020 [DOI] [Google Scholar]
- 55.Olmedo I, Nielsen P V, Ruiz de Adana M, Jensen RL, Grzelecki P. Distribution of exhaled contaminants and personal exposure in a room using three different air distribution strategies. Indoor Air. 2012;22: 64–76. 10.1111/j.1600-0668.2011.00736.x [DOI] [PubMed] [Google Scholar]
- 56.Liu L, Li Y, Nielsen P V, Wei J, Jensen RL. Short-range airborne transmission of expiratory droplets between two people. Indoor Air. 2016; 10.1111/ina.12314 [DOI] [PubMed] [Google Scholar]
- 57.Qian H, Li Y, Nielsen P V, Hyldgaard CE. Dispersion of exhalation pollutants in a two-bed hospital ward with a downward ventilation system. Indoor Air 2005 Model Assessment, Control Indoor Air Qual. 2008;43: 344–354. 10.1016/j.buildenv.2006.03.025 [DOI] [Google Scholar]
- 58.Li Y, Sandberg M, Fuchs L. Vertical Temperature Profiles in Rooms Ventilated by Displacement: Full-Scale Measurement and Nodal Modelling. Indoor Air. 1992;2: 225–243. 10.1111/j.1600-0668.1992.00005.x [DOI] [Google Scholar]
- 59.Gao N, He Q, Niu J. Numerical study of the lock-up phenomenon of human exhaled droplets under a displacement ventilated room. Build Simul. 2012;5: 51–60. 10.1007/s12273-012-0068-5 [DOI] [Google Scholar]
- 60.Zhou Q, Qian H, Ren H, Li Y, Nielsen P V. The lock-up phenomenon of exhaled flow in a stable thermally-stratified indoor environment. Build Environ. 2017; 10.1016/j.buildenv.2017.02.010 [DOI] [Google Scholar]
- 61.Melikov AK, Bolashikov ZD, Kierat W, Popiolek Z, Brand M. Does increased ventilation help reduce cross-infection in isolation hospital wards? Proceedings of CLIMA 2010: Paper R7-TS39-OP02. Antalya, Turkey; 2010.
- 62.Bolashikov ZD, Melikov AK, Kierat W, Popiołek Z, Brand M. Exposure of health care workers and occupants to coughed airborne pathogens in a double-bed hospital patient room with overhead mixing ventilation. HVAC&R Res. Taylor & Francis; 2012;18: 602–615. 10.1080/10789669.2012.682692 [DOI] [Google Scholar]