Integration of PV floating with hydroelectric power plants

Raniero Cazzaniga b, Marco Rosa-Clot b, Paolo Rosa-Clot b, Giuseppe Marco Tina a,
PMCID: PMC6595280  PMID: 31294100

Abstract

The integration of floating a PV plant (FPV) with a Hydroelectric Power plant (HPP) is studied and it is shown that several advantages come from this hybridization. The FPV power potential is analysed for the first 20 largest HPPs in the world and it is shown that when covering 10% of the HPP basin surfaces the HPP energy production is increased by 65%. The experience of China Longyangxa basin and of its connected PV power plant is examined together with the suggestion to install a FPV whose rated power is equal to HPP rated power. This hypothesis is applied to an analysis of the geographic potential worldwide and it is shown that covering 2.4% of the existing HPP basin surfaces the energy produced by HPP will be increased by 35.9%. The advantages of the coupling of the two power production technologies are discussed.

Keywords: Electrical engineering, Energy, Photovoltaic, Floating systems, Hydroelectric power plant

1. Introduction

Renewable Energy Sources (RES) are rapidly evolving and their cumulated installed power in the last few years has been continuously increasing as shown in Fig. 1, based on data reported in [1], where total installed power is given together for the three main RES technologies: hydroelectric, wind and photovoltaic. Biomass technology (waste, wood, etc.) covers only 5% of the installed power in 2017 and so is not reported in Fig. 1. One of the most noticeable pieces of information that comes from a first view of the graph is the significant rapid increase of the PV plants installed, which in less than 10 years have reached a cumulated power about 75% of the wind capacity. .

Fig. 1.

Fig. 1

Worldwide installed power in GW for the main RES [1].

Due to the different nature (e.g. variability, availability, programmability) of the renewable sources reported in Fig. 1, the installed power is not sufficient to evaluate the real impact of the different RES on worldwide electric energy production. In fact, the hydroelectric power plants (HPP) have a more important role with respect to wind and PV technologies; at the end of 2017, HPP accounted for 16.4 % of the worldwide electric energy production with increasing investments especially in China and the equatorial regions (see Fig. 2). PV and Wind energy production reached 1564 TWh in 2017, which is just 37.6% of the energy produced by hydro which is 4185 TWh.

Fig. 2.

Fig. 2

Worldwide energy production in GWh for the main RES [1].

So, the contribution of HPP to worldwide electricity production is overwhelming. This is due to the different energy output over a period of time of Hydro power plants compared with PV or Wind power plants. To characterize the difference between hydro and PV or Wind plants we can adopt the Full Load Hours (FLH), the electric energy output of the power plant over one year divided by its rated power (in hours), or the Capacity Factor which is the FLH normalized to the yearly hours, 8760, in %.

In Table 1 there is a comparison of FLH and CF for the main renewable technologies considering the global worldwide data ([2] [3],).

Table 1.

Full Load Hours and Capacity Factor for the main renewable energy sources.

Year
2013
2014
2015
2016
2017
Technology FLH (hrs) CF(%) FLH (hrs) CF(%) FLH (hrs) CF(%) FLH (hrs) CF(%) FLH (hrs) CF(%)
Biomass 4987 56,9% 4988 56,9% 4943 56,4% 4454 50,8% 5046 57,6%
HPP 3671 41,9% 3652 41,7% 3549 40,5% 3347 38,2% 3539 40,4%
Wind 2122 24,2% 2051 23,4% 1981 22,6% 2051 23,4% 2118 24,2%
PV 1008 11,5% 1102 12,6% 1109 12,7% 1086 12,4% 1164 13,3%

Currently the average value of FLH for HPP is 3652 h and this value should be compared with solar PV (1102 h) and wind farms (2051 h); the only higher value is that of biomass whose FLH reaches almost 5000 h.

Therefore, if we look at the renewable energy sector, there has been a strong increase of PV, which covers 17.7% of the renewable energy power; however, its contribution to the production of energy is only 7.1%. Conversely, energy produced by biomass, which covers only 5% of the installed electrical power, reaches 8.3% of the energy production thanks to the larger CF value.

Notwithstanding this limit, PV is still expanding and companies in the electricity energy sector are looking for new areas where to install utility scale PV plants. There is a strong interest in installing the PV plants coupled to HPP thanks to the easy integration of the two technologies. A further improvement in the integration of solar and hydro energy is constituted by the floating PV plants (FPV) [4]. See also [5] for a specific analysis of the “virtual battery” storage potential.

In this paper a detailed analysis is given of the advantages of coupling FPV plants with HPP. The possibilities of doubling the power of a HPP using FPV is analysed and we show that with a coverage of only 2.4% on average of the water basins surface this target can be achieved thus increasing the energy production of the HPP by about 34%.

2. Main Text

2.1. Advantages of coupling FPV and HPP

Several factors suggest the advantages of coupling PV plants with hydroelectric power stations, as analysed by several authors [6, 7, 8]. In short, we can summarize the benefits gained by a hybrid PV-Hydro coupling as follows.

  • 1.

    Grid connection. Artificial and non-artificial hydroelectric basins are equipped with power generators and are grid connected, so it is possible to exploit the existing infrastructure reducing the cost of a floating PV plant.

  • 2.

    Reduction of power fluctuation. In temperate regions, Italy for example, PV panels give the maximum energy yield during the hot season when the HPP registers a reduction of power due to the seasonal water cycle. This partial anticorrelation allows an important reduction in the yearly fluctuations of electrical energy production. Furthermore, an active control system could be used where the HPP is decreased during the day when the PV plant is operational and increased during the night, cloudy conditions or at times of peak demand to ensure power is produced to match demand without the need for battery or other storage equipment often associated with PV plants.

  • 3.

    No land occupancy. The main advantage of floating or submerged PV plants is that they do not take up any land, except the small area necessary for electrical cabinets. Floating PV plants are not merely more economical than land-based plants, but they provide a crucial way to avoid competing with agricultural or green zones [9]. Also, unlike land-based PV plants, floating or submerged plants have a limited impact on the landscape as the surface occupancy is reduced.

  • 4.

    Installation and decommissioning. Floating PV plants are more compact than land-based plants, their management is simpler and their construction and decommissioning straightforward. The main point is that no fixed structures exist, and the mooring of floating systems can be installed and removed in a totally reversible way, unlike the foundations used for a land-based plant which are far more intrusive and permanent.

  • 5.

    Water saving and water quality. The partial coverage of HPP water basins has additional benefits such as the reduction of water evaporation. This result depends on climate conditions and on the percentage of the covered surface. A parallel advantage is the containment of the problem of algae bloom, which is especially serious in industrialized countries [10]. The partial coverage of the basins and the corresponding reduction of light on biological fouling just below the surface can solve the problem of algae blooms.

  • 6.

    Cooling and Tracking. The floating structure allows the implementation of a simple and cheap cooling and tracking mechanism. As is well known, one of the limits of PV plants is that they lose efficiency during the hot season because of the thermal drift effect. In the case of a floating or submerged PV plant, this effect can be substantially reduced by the presence of water cooling, thus gaining 10% or more in yearly energy harvesting [11]. Moreover, a floating PV plant equipped with a tracking system has a limited additional cost, whilst the gain in energy can range from 15 to 25%. In several cases the technical effort necessary to implement this solution gives a sizeable reduction of the final kWh cost.

  • 7.

    Radiation balance. Land-based PV plants strongly modify the land albedo. Land albedo ranges from 20% for grassland to 20–30% for roofs to 40%–50% for desert land [12]. Instead, PV modules are built in a way to reduce as much as possible the radiation reflection and so they absorb about 95% of solar radiation. This imbalance can give rise to local temperature modifications and microclimate changes and modifies the mean radiation balance. This effect is not present for the floating plants since the water albedo is on average about 5%, approximately equal to the PV modules albedo, thus leaving the energy balance unchanged [13].

2.2. Hybrid FPV-HPP and geographic potential

Hydroelectric power is mainly based on the construction of dams and on the creation of large basins. Run-of-the-river systems (ROR) cover only a small part of hydroelectric production and are important mainly in the mini and micro-installations. In general most hydroelectric power comes from the potential energy of artificial water reservoirs created by a dam, which in several cases are equipped with a pumping system which enables pumped storage for use during high peak demands [14].

2.2.1. Power and energy density

We want to compare the power and energy density for HPP and FPV. To do this we define the quantities ρP,H and ρE,H (power density and energy density for hydro power plant) and correspondingly the same densities for FPV, specifically ρP, FPV and ρE,FPV.

  • ρP,H = PH/SB, where PH in GW is the peak power of the hydroelectric plant and SB in km2 is the basin surface. The unit measure is GW/km2 or kW/m2.

  • ρE,H = EH/SB where EH is the yearly energy production in GWh. The unit measure is GWh/km2/y or kWh/m2/y

The ratio of the two densities allows us to calculate the factor FLHH = EH/PH (hours) which for HPP has values ranging from 2000 to 5000 depending on the basin characteristics.

The corresponding quantities for FPV are ρP,FPV and ρE,FPV which depend on the geometrical structure of the FPV plant and on the local radiation. The FLHPV ranges typically from 800 to 1800 h depending mainly on the latitude and on the mean weather conditions.

The quantity ρE,FPV depends also on the geometry of the plant (panels pitch and tilt) and has been discussed in reference [15] with the result that, for an optimal floating structure, the solar energy produced by modules in horizontal position should be increased for modules with optimal tilt and pitch. In the following, data is taken from PVGIS or the NASA data base, and evaluated with the program PVsyst.

For the purpose of this analysis, we define a typical FPV plant as having 16 PV modules are installed on a raft of 12 m × 4 m and we assume that the power of each module is 0.36 kWp. This corresponds to a typical value for the standard PV modules of 2 m2 which in today's market have powers ranging from 300 to 440 kWp. So the power available on a 1 km2 floating plant would be: ρP,FPV=106/(4.3×12.3)×24×0.44=199.6MWp/km2(200Wp/m2)

This value can change due to an increase of the power density of the PV modules (recently modules of 2 m2 have been proposed with a power of 0.44 kW) and to a change in the raft geometry (see ref. [16], where a “gable” solution, suitable for equatorial regions, allows us to put 24 PV modules on a double raft of surface 4.3 × 12.3 m, catwalk included). In this case, using a high efficiency PV module of 0.44 kW the peak power density for a km2 rises to ρP,FPV = 106/(4.3 × 12.3) × 24 × 0.44 = 199.6 MWp/km2 (200 Wp/m2).

This possibility is very attractive since the compactness of the power PV plant is a positive factor, however in the following we will use the more conservative value of ρP,FPV equal to 120 Wp/m2.

In Table 2 typical values are collected for HPP and FPV plants.

Table 2.

Typical values of power and energy density for the first 20 HPP and the corresponding possible FPV plants (Elaboration of data from [17]).

Units Average value
HPP ρ P,H MWp/km2 or Wp/m2 14,40
ρ E,H GWh/y/km2 or kWh/y/m2 65,70
FLH H hours 4545
FPV ρ P,FPV MWp/km2 or Wp/m2 120
ρ E,FPV GWh/y/km2 or kWh/y/m2 135,4
FLH PV hours 1128

We want to stress that the higher power density of FPV plants is reduced by the low CF value. However the FPV energy density remains higher than the HPP value by a factor 2 and the power density by a factor 9. This is because of the relatively large basin size required by the HPP; this area is also relatively unused and presents an ideal location for a FPV plant as discussed below.

2.2.2. Data for the first 20 largest HPPs

Data for the first 20 largest HPP in the world are shown in Table 3.

Table 3.

The first 20 largest HPP in the world [17].

Name PH
EH
FLHH
SB
Hydro ρE,H
FPV ρE,FPV
EFPV (SFPV = 0,1SB)
MW TWh h km2 GWh/y/km2 GWh/y/km2 TWh
Three Gorges Dam 22500 98,8 4391 1084 91,1 112,7 12,2
Itaipu Dam 14000 103,1 7364 1350 76,4 153,8 20,8
Guri 10235 53,4 5218 4250 12,6 185,6 78,9
Tucuruí 8370 41,4 4950 3014 13,7 180,6 54,4
Belo Monte 7333 39,5 5387 441 89,6 139,5 6,2
Grand Coulee 6809 20,0 2937 324 61,7 84,8 2,7
Xiangjiaba 6448 30,7 4761 95,6 321,1 97,4 0,9
Sayano–Shushensk 6400 26,8 4188 621 43,2 92,4 5,7
Krasnoyarsk 6000 15,0 2500 2000 7,5 154,8 31,0
Nuozhadu 5850 23,9 4085 320 74,7 105,7 3,4
Robert-Bourassa 5616 26,5 4719 2385 11,1 109,6 26,1
Churchill Falls 5428 35,0 6448 6988 5,0 100,6 70,3
Tarbela Dam 4888 13,0 2660 250 52,0 145,2 3,6
Bratsk 4515 22,6 5006 5470 4,1 92,5 50,6
Xiaowan Dam 4200 19,0 4524 190 100,0 121,2 2,3
Ust Ilimskaya 3840 21,7 5651 1922 11,3 165,6 31,8
Jirau 3750 19,1 5093 258 74,0 176,6 4,6
Jinping-I 3600 17,0 4722 82,5 206,1 159,6 1,3
Santo Antonio 3580 21,2 5922 490 43,3 181,5 8,9
Ilha Solteira Dam 3444 17,9 5197 1195 15,0 148,8 17,8
Total/Aver 136806 665,6 4866 32730 65,7 135,4 433,5

After the basic information about power and energy production we give the CF value, the flooded area and the energy production for km2, defined above as ρE,H.

The last two columns give the energy yearly production per km2 (which depends on the irradiation data) and the produced energy under the hypothesis that 10% of the basin is covered by a floating plant.

As evident, even limiting the coverage to 10%, the increase in energy production is sizeable and in some cases is more than the production of the HPP itself.

In Table 3 we can see also that large HPP generate power for more than 50% of the time which are on average 4,866 hours (55% of the hours in the year) if we exclude the flow river contribution. We remark that the value found for FLH is larger than the FLH quoted in Table 1. This is due to the storage capacity of the very large basins and to the fact that small basins have a lower FLH factor ranging from 2000 to 3000 h.

Another interesting parameter for our purpose is the power generated per m2. Its value is on average 4.2 W/m2 with large fluctuations; in fact, the power density ranges from 1 to 70 W/m2 but in many cases it is below 5 W/m2.

This value should be compared with the one obtained using PV plants and floating PVs. The installed power for a fixed land-based plant is about 70 W/m2 whereas for a floating plant depending on the technical solution (fixed plants, plants with tracking, gable solution, etc.) this value rises in the range of 100–200 W/m2. In conclusion we gain on average a factor of 30 in the power density per m2.

The energy harvesting however is reduced and, averaging on the 20 PV plants, we get an FLHPV value of 1128 MWh/MWp which is about 4 times lower than the FLH for HPP.

Using these values, we can see that the energy production, using a coverage of 10% of the basin, is 433.5 TWh, about 65% of that due to the hydroelectric power. This value is larger in the equatorial zone where solar energy yield is larger, and smaller at high latitudes but eitherways we can conclude that with a coverage of 10% the energy harvesting is substantially increased.

This result is very important and for this reason the possibility of coupling floating PV plants to HPP plants is quite natural and has been analyzed from the very beginning of the research in this sector [18].

2.2.3. Optimization

Since the factor ρE,FPV is much larger than ρE,H it is quite evident that the coverage with FPV of part of the hydroelectric basins can strongly improve the energy production. Advantages are remarkable:

  • Grid connection already exists and this of course reduces the costs

  • Integration with a pumping system or simply a balance with the water turbines of the HPP is simple and allows us to exploit the solar energy without the problem of discontinuity since turbines of the HPP can supply the energy necessary to face the intermittent behavior of the PV plant.

  • FPV uses the otherwise under utilized water basin of the HPP

  • Installation is quick and can be done at a cost which is lower than 1000 $ per kWp

About this last point we have registered in the last few years a remarkable reduction in the cost of land based PV plants which is now around 700 $/kWp; in parallel several efforts have been made to reduce the cost of floating structures and up to now the suggested minimum cost is 800 $/kWp: see [19].

From reference [20] we can learn how profitable the coupling of HPP and FPV is. The authors present an analysis of the Longyangxia hydro–PV power plant. This plant consists of a large HPP (power 1280 MW) and by a large land-based PV plant (850 MWp). See Fig. 3. Main parameters of the plant are given in Table 4.

Fig. 3.

Fig. 3

Google earth map of the Longyangxa basin with the PV power plant.

Table 4.

Relevant parameters for the Longyangxia hydro–PV power plant [20].

Hydropower reservoir Normal pool level 2600 m
Minimum outflow of a hydro unit 50 m3/s
Maximum outflow of a hydro unit 292 m3/s
Average hydraulic head 100 m
Installed power capacity 1280 MW
Average annual energy production 5940 GWh
FLHH 4640 h
Basin surface 300 km2
PV array installed capacity (land based) 850 MW
Average annual energy production 1494 GWh
FLHPV 1756 h
Occupied area 20.4 km2

If we summarize data using our parameters we can say that ρE,H = 19.8 GWh/km2/y and that the PV plant occupies a surface which is 6.7% of the basin surface. Of course, for an equivalent FPV plant the surface would be much less and should not exceed 8 km2, that is 2.7% of the flooded area.

The managing of this hybrid power station is very interesting. The power produced by the PV plant is fully used and the power of HPP is tuned gently to match the grid requirement. This can be easily done since the power peak and the energy production are considerably less than that of the HPP. Following reference [20], we remark that the hydroelectric power of the HPP can be tuned in a coarse way and can follow the variation of the PV plant. In this way the total output can match the grid requirements and the use of water resources is proportionally reduced.

In the specific case of the Longyangxia plant we illustrate in Fig. 4 the behaviour of the two components of energy production during a sunny summer day where the PV production reaches its maximum. In this case the PV produces 6680 MWh to be compared to the HPP production of 24350 MWh. So PV supplies 21.5% of the total energy production of 31.030 MWh.

Fig. 4.

Fig. 4

HPP and PV power in MW during a sunny summer day for Longyangxia plant.

This result should be averaged along the year, considering also winter and cloudy day, but the global result is that the energy production of the HPP is increased and that PV plant generates 1494 GWh/y to be compared with 5940 GWh coming from the HPP, that is 20% more energy without any changes in the grid connections or to the basic infrastructure.

The question now is: what is the optimum choice for the coupling of a PV plant (possibly an FPV) with a large HPP?

In order to minimize costs and exploit as far as possible the advantages of this hybrid system we suggest installing a FPV able to supply, at its best, the power of the HPP itself. In the typical situation for a Mediterranean latitude (Catania for example), the daily average energy yield can be calculated for different months assuming that for 1 MW HPP an equivalent FPV of 1 MWp has been installed: averaging on the different months we find that the contribution to the energy production of the FPV for the month of July, April and January is of 33%, 26% and 17% respectively. These three months have been chosen as a typical example and a calculation throughout the whole year gives an average yearly contribution of 27%.

However this result underestimates the FPV contribution. In fact the large basins quoted in Table 3 have an average FLH value of 4,896 h whereas the FLH factor is much lower for Sicily HPP (approximately 2,500 h) so that the FPV contribution is actually much more important.

In conclusion, we list in Table 5 what would happen if the 20 largest HPP basins in the world were equipped with FPV plants of the same power. The first column gives the energy production of the HPP plant, the second gives the surface of an FPV plant with the same peak power, and the third column the energy produced by the FPV plant. The last three columns show the relative weight of FPV results over HPP and the final LFH value resulting from this hybrid system.

Table 5.

Comparison between larger HPP and FPV plants of equivalent power.

Name EH
SFPV
EFPV
SFPV/SB
EFPV/EH
FLHFPV,H
TWh km2 TWh % % h
Three Gorges Dam 98,8 188 21,1 17,3% 21% 5330
Itaipu Dam 103,1 117 17,9 8,6% 17% 8646
Guri 53,4 85 15,8 2,0% 30% 6765
Tucuruí 41,4 70 12,6 2,3% 30% 6455
Belo Monte 39,5 61 8,5 13,9% 22% 6549
Grand Coulee 20,0 57 4,8 17,5% 24% 3644
Xiangjiaba 30,7 54 5,2 56,2% 17% 5573
Sayano–Shushenskaya 26,8 53 4,9 8,6% 18% 4958
Krasnoyarsk 15,0 50 7,7 2,5% 52% 3790
Nuozhadu 23,9 49 5,2 15,2% 22% 4966
Robert-Bourassa 26,5 47 5,1 2,0% 19% 5632
Churchill Falls 35,0 45 4,5 0,6% 13% 7286
Tarbela Dam 13,0 41 5,9 16,3% 45% 3870
Bratsk 22,6 38 3,5 0,7% 15% 5777
Xiaowan Dam 19,0 35 4,2 18,4% 22% 5534
Ust Ilimskaya 21,7 32 5,3 1,7% 24% 7031
Jirau 19,1 31 5,5 12,1% 29% 6565
Jinping-I 17,0 30 4,8 36,4% 28% 6052
Santo Antonio 21,2 30 5,4 6,1% 26% 7435
Ilha Solteira Dam 17,9 29 4,3 2,4% 24% 6437
Total/average 665,6 1140 152,5 3,5% 23% 5994

It is impressive to see that the surface occupied by the FPV plant (of equal power to HPP) is only a small fraction (3.5%) of the hydroelectric basin surface. The energy produced ranges between 15% and 52% of the energy produced by HPP, with an average contribution of 23%.

We further remark that for small HPP plants with low FPH factor (in the range of 2000–3000 h) the average contribution of the FPV plants should rise to about 45%.

2.3. A worldwide analysis

A similar but more detailed analysis can be done for the USA. We use the data published by [21] about 100 HPP in USA.

In this case the main results are synthesized in Table 6.

Table 6.

Data for 100 USA HPP (total values and average data).

Power MW Basin surface km2 ρP,H MW/km2 ρE,H GWh/km2 ρP,FPV MW/km2 ρE,FPV GWh/km2
32574 22736 1.43 5.02 120 191

As evident the high value of ρE,FPVE,FPVE,H = 191/5.02 = 38) implies that covering on average 1/38 = 2.5% of the hydroelectric basins we can double the produced energy.

However, we simply want to install FPV of power equal to that of the HPP. In this case the surface of the basin occupied by FPV would be 1.19% of the whole basin surface (32574/120 = 271 km2 i.e. 1.19 % of 22736 km2) and the energy produced would be 40.5% of the hydroelectric energy production (191/5.02*1.19% = 40.5%).

A more general analysis can be made using a world wide database for water resources. We refer to [22] for the free fresh water surface and to the AQUASTAT database [23] for information about manmade reservoirs and hydroelectric basin surfaces. See also [ [24] for the Digital Water Atlas database. The main results are collected in Table 7.

Table 7.

Worldwide analysis of water reservoirs.

Fresh Water
ManMade reservoirs
HPP surfaces
ManMade/all
HPP-Surfaces/ManMade res.
km2 km2 km2 % %
Africa 540,030 46,499 24,197 8.6% 52%
America Central 58,801 4,161 2,899 7.1% 70%
America South 381,710 65,000 53,863 17.0% 83%
Asia South East 153,490 32,231 22,929 21.0% 71%
Asia South without India 48,320 1,283 1,081 2.7% 84%
Australia + New Zealand 58,920 4,965 1,216 8.4% 24%
Canada 891,163 97,914 95,224 11.0% 97%
China 270,550 12,979 7,454 4.8% 57%
Europe (North) 178,156 30,267 24,724 17.0% 82%
Europe (South) 19,612 3,091 2,066 15.8% 67%
India 314,000 102,775 13,361 32.7% 13%
Japan 13,430 1,394 130 10.4% 9%
Middle East 140,190 26,259 10,775 18.7% 41%
Russia 720,500 85,408 84,761 11.9% 99%
Turkestan 76,110 17,247 14,582 22.7% 85%
USA 685,924 43,904 21,686 6.4% 49%
Total 4,550,906 575,377 380,948 12.6% 66.2%

We start from the analysis done in reference [4] and [25]: the fresh water surfaces are taken from ref. [22] and the data are collected for large geographic areas. Man-made reservoirs and HPP basin surfaces are taken from Aquastat database. A careful analysis has been completed and some small corrections have been made to the Aquastat data, the key conclusions are as follows:

  • The Man-made water reservoirs represent 12.6% of the entire fresh water surfaces, and the surface of HPP basins represent 66% of the man-made total. This last percentage depends on orographic configuration and a specific case is Japan where the presence of many HPP basins at high altitude and with small surface areas pushes this ratio below 10%.

  • 380,948 km2 of water basins originated by dams for HPP power plant are available around the world.

Now the question is: how large is the FPV surface necessary to install an equivalent power? And how much is the energy produced?

Table 8 answers these questions under the hypothesis discussed in section 3.

Table 8.

Worldwide analysis of hydroelectric basins.

HPP
FPV
SH
PH
EH
SFPV
EFPV
SFPV/SB
EFPV/EH
km2 GW TWh km2 TWh % %
Africa 24,197 34.4 114.1 287 41.28 1.2% 36.2%
America Central 2,899 7.7 23.0 64 9.24 2.2% 40.2%
America South 53,863 161 589.8 1342 193.2 2.5% 32.8%
Asia South East 22,929 44.8 143.4 373 53.76 1.6% 37.5%
Asia South without India 1,081 17.6 65.5 147 21.12 13.6% 32.2%
Australia 1,216 14 43.9 117 16.8 9.6% 38.3%
Canada 95,224 81 388.2 675 97.2 0.7% 25.0%
China 7,454 333 1,162.8 2775 399.6 37.2% 34.4%
Europe (North) 24,724 68 196.7 567 81.6 2.3% 41.5%
Europe (South) 2,066 85.9 175.3 716 103.08 34.6% 58.8%
India 13,361 47.6 128.8 397 57.12 3.0% 44.3%
Japan 130 12 91.3 100 14.4 76.9% 15.8%
Middle East 10,775 15.87 19.8 132 19.044 1.2% 96.2%
Russia 84,761 51 186.6 425 61.2 0.5% 32.8%
Turkestan 14,582 12.7 51.7 106 15.24 0.7% 29.5%
USA 21,686 103 261.8 858 123.6 4.0% 47.2%
Total 380,948 1089.57 3,642.7 9,079.8 1307.5 2.4% 35.9%

It is remarkable that the surface necessary to install an FPV power equivalent to that of the HPP is only on average 2.38% of the basin surfaces and that in only three cases it is larger than 10%, for example in the case of Japan.

Even more important is the fact that the rise in energy yield is on average 36%. This result is related to the fact that the FLH factor of FPV ranges between 900 and 1200 h with an average value of 1060, whereas the FLHH is on average 2950 h.

2.3.1. Evaporation reduction

A byproduct of the FPV plant consists in a strong reduction of evaporation from the water surface covered by rafts supporting the PV modules. The floating PV array can have features (e.g. floating structures and geometry of the deployment of the PV modules) that determine a different impact on the water evaporation and on the energy balance of the covered part of the basin [25]. The results of this study show that by covering only 10% of water surface it is possible to reduce evaporation from 6 to 18%. Floating systems, with modules anchored to a tubular buoyancy system, allow a greater ventilation of the modules and therefore a good evaporative cooling [26]. In [16] the evaporation reduction is approximately 80% respect with the uncovered water basin.

As an example, we take the parameters of Longyangxia hydro–PV power plant. Let's imagine that the full PV plant was an FPV plant occupying a surface of approximately 10 km2 and that we save 2 m3 of water per m2 because of the reduction of the evaporation rate [25]. The amount of water saved in one year would be 20 million m3 which with an average head of 100 m gives rise to a production of 5.4 GWh.

This reduction is very relevant if we are in arid zones or for example for waste water basins where an adequate water coverage can save from 10,000 to 20,000 m3 per ha. Several calculations have been done using Penman model [19] and experimental findings of several authors (see for example [27] and [28]) support this rough estimate. However, in the case of HPP, saving water is not the main concern so this is mentioned for completeness but not a major factor compared to the potential increase in energy production from FPV.

3. Conclusions

Coupling of FPV and hydroelectric power plant allows a considerable increase in RES energy production.

The cost of FPV is comparable to that of a land-based PV plants and is further reduced because of the presence of infrastructure and the existence of a grid connection for existing HPP. There are major potential advantages combining the natural energy storage system of HPP with the relatively high power but sporadic power production of FPV.

The strategy suggested consists in installing a FPV power plant equal to the existing HPP power plant and to reduce the hydro turbines energy production during the sunny hours maintaining the energy fed into the grid at an approximately constant level, this could also be fine tuned to match peaks in demand.

Using this approach, the worldwide HPP basins surface covered by FPV would only be 2.4 % but the increase in energy production would be 35.9% raising the FLH value from 3,539 to 4,800 h.

This analysis can be extended to other situations and to smaller HPP basins where the FLH factor is lower, i.e. around 2000. In this case the benefits of the hybrid FPV-HPP coupling are even greater and the increase in energy can reach 50%.

Declarations

Author contribution statement

All authors listed have significantly contributed to the development and the writing of this article.

Funding statement

This research did not receive any specific grant from funding agencies in the public, commercial, or not-for-profit sectors.

Competing interest statement

The authors declare no conflict of interest.

Additional information

No additional information is available for this paper.

Acknowledgements

The University of Catania within the “Plan for research 2016/2018 - DIEEI”, has funded this research, project title: “Exploitation of innovative approaches for the estimation of the energy needs of urban neighbourhoods and for the assessment of sustainable optimisation and mitigation strategies ”. We thank both Eamon Howlin and Jon Hancock, Solarmarine Energy Ltd, for critical reading of the manuscript and for helpful suggestions.

References

  • 1.IRENA . International Renewable Energy Agency; Abu Dhabi: 2018. Renewable Capacity Statistics 2018. [Google Scholar]
  • 2.BP Statistical Review of World Energy. BP Energy Outlook; London: 2017. [Google Scholar]
  • 3.Renewables 2016 Global Status Report. REN21 Steering Committee; 2016. [Google Scholar]
  • 4.Rosa-Clot M., Tina G.M. Elseveir, Academic Press; London: 2017. Submerged and Floating Photovoltaic Systems, Modelling, Design, Case Studies. [Google Scholar]
  • 5.Farfan J., Breyer C. Combining floating solar photovoltaic power plants and hydropower reservoir: a virtual battery of great power potential. Energy Procedia. 2018;155:403–411. [Google Scholar]
  • 6.Nordmann T., Vontobel T., Clavadetscher L., Boström T., Remlo H. In 24th European Photovoltaic Solar Energy Conference, Hamburg. 2009. Large Scale Hybrid PV Hydroelectricity Production in Floating Devices on Water. [Google Scholar]
  • 7.Glasnovic Z., Margeta J. The features of sustainable solar hydroelectric power plant. Renew. Energy. 2009;34:1742–1751. [Google Scholar]
  • 8.Sahu A., Yadav N., Sudhakar K. Floating photovoltaic power plant: a review. Renw. Sust. Energy Rev. 2016;66:815. [Google Scholar]
  • 9.Martín-Chivelet N. Photovoltaic potential and land-use estimation methodology. Energy. 2016;94:233–242. [Google Scholar]
  • 10.Sanseverino I., Conduto D., Pozzoli L., Dobricic S., Lettieri T. European Commission JRC; 2016. Algal Bloom and its Economic Impact. [Google Scholar]
  • 11.Grubišić F., Nižetić S., Tina G. Transactions of Famena XL; 2016. Photovoltaic Panels: A Review of the Cooling Techniques; pp. 63–74. [Google Scholar]
  • 12.Andrews R.W., Pearce J.M. Michigan Technological University; 2013. The Effect of Spectral Albedo on Amorphous Silicon and Crystalline Silicon Solar Photovoltaic and Device Performance. [Google Scholar]
  • 13.Séférian R., Baek S., Boucher O., Dufresne J., Decharme B., Saint-Martin D., Roehrig R. «An interactive ocean surface albedo scheme (OSAv1.0): formulation and evaluation in ARPEGE-Climat (V6.1) and LMDZ (V5A),» Geosci. Model Dev. 2018;11:321–338. [Google Scholar]
  • 14.Rehman S., Al-Hadhrami L.M., Alam M.M. Pumped hydro energy storage system: a technological review. Renew. Sustain. Energy Rev. 2015;44:586–598. [Google Scholar]
  • 15.Tina G.M., Cazzaniga R., Rosa-Clot M., Rosa-Clot P. Geographic and technical floating photovoltaic potential. Therm. Sci. 2018;22(Suppl. 3):S831–S841. [Google Scholar]
  • 16.Cazzaniga R., Cicu M., Rosa-Clot M., Rosa-Clot P., Tina G.M., Ventura C. Floating Photovoltaic plants: performance analysis and design solutions. Renew. Sustain. Energy Rev. 2018;81:1730–1741. [Google Scholar]
  • 17.Wikipedia, «List of Largest Hydroelectric Power Stations,» [Online]. Available: https://en.wikipedia.org/wiki/List_of_largest_hydroelectric_power_stations. [Accessed November 2018].
  • 18.Cazzaniga R., Rosa-Clot M., Rosa-Clot P., Tina G.M. In 38th IEEE Photovoltaic Specialists Conference. PVSC); Austin (USA): 2012. Floating tracking cooling concentrating (FTCC) systems. [Google Scholar]
  • 19.Group W.B. SERIS; Singapore: 2018. Where Sun Meets Water: Floating Solar Market Report. [Google Scholar]
  • 20.Ming B., Liu P., Cheng L., Zhou Y., Wang X. Optimal daily generation scheduling of large hydro–photovoltaic hybrid. Energy Convers. Manag. 2018;171:528–540. [Google Scholar]
  • 21.Perez M., Perez R., Ferguson C.R., Schlemmer J. Deploying effectively dispatchable floating PV on reservoirs:comparing floating PV to other renewable technologies. Sol. Energy. 2018;174:837–847. [Google Scholar]
  • 22.C.I.A., «The World Factbook,» [Online]. Available: https://www.cia.gov/library/publications/the-world-factbook/. [Accessed October 2018].
  • 23.AQUASTAT, «Dams: Geo-Referenced Database,» Food and Agricoltural Organization of United Nations, [Online]. Available: http://www.fao.org/nr/water/aquastat/dams/index.stm. [Accessed November 2018].
  • 24.Digital Water Atlas,» [Online]. Available: http://www.gwsp.org/products/digital-water-atlas.html. [Accessed November 2018].
  • 25.Rosa-Clot M., Tina G.M., Nizetic S. Floating photovoltaic plants and wastewater basins: an Australian project. Energy Procedia. 2017;134:664–674. [Google Scholar]
  • 26.Bontempo F., Tina G.M., Gagliano A. In Splitech, Spalato Croatia. 2019. Study of evaporation reduction in water basins with floating photovoltaic plants. [Google Scholar]
  • 27.Penman H. Natural evaporation from open water, bare soil and grass. Proc. R. Soc. London, Ser. A. 1948;193:120–145. doi: 10.1098/rspa.1948.0037. [DOI] [PubMed] [Google Scholar]
  • 28.Aminzadeh M., Lehmann P., Or D. Evaporation suppression and energy balance of water reservoirs covered with selfassembling floating elements. Hydrol. Earth Syst. Sci. 2018;22:4015–4032. [Google Scholar]

Articles from Heliyon are provided here courtesy of Elsevier

RESOURCES