Real time control data for styrene acrylonitrile copolymerization system in a batch reactor for the optimization of molecular weight

Sharanya Suraboyina 1, Saipushpita Vudata 1, Anand Polumati 1,
PMCID: PMC6920341  PMID: 31879697

Abstract

This work describes an approach towards experimental implementation of real time control studies conducted on a batch polymerization reactor. The information is related to the controlling of molecular weight for styrene acrylonitrile copolymer polymerization system in a batch reactor generated under a varied range of temperatures, reactant concentrations and retention times. The operating conditions of 6 hrs and temperature of 343 K for yielding a molecular weight in the range of 39,900–40,000 gmol−1 is established using simulation studies. A real time control facility consisting of a batch reactor, data acquisition software “LabVIEW” and a PC for monitoring and control is used to implement these operating conditions. The resulting product is analyzed by gel permeation chromatography (GPC). The data generated can be used by researchers, academicians and industry for generating control strategies, automation and scale up of polymerization reactors.

Keywords: Real time control, Batch reactor, Co-polymerization, Process optimization, Molecular weight


Specifications Table

Subject Chemical Engineering
Specific subject area Polymerization, Data monitoring, Control theory
Type of data Tables, Graphs, Figures
How data were acquired Experiments were conducted for styrene acrylonitrile polymerization process in a batch reactor. The experiment was carried out for a constant set point of 343 K (70 °C). The total experiment was carried out for six hours. The experimental data was monitored and logged using a data acquisition (DAQ) software “LabVIEW”. This is a commercial software package installed in the personnel computer to acquire, monitor, handle and analyze the data. All the control logics and the programs for data logging were written using functions in the block diagram. All the controls and indicators are displayed in the front panel to have online monitoring of the process in the form of charts during reaction time.
Data format Raw and analyzed
Parameters for data collection Reactor temperature, Jacket temperature, coolant flow rate, molecular weight.
Description of data collection Experiments were conducted for styrene acrylonitrile co-polymerization process in a bench scale reactor under wide range of temperatures, reactant concentrations and retention times. A constant set point temperature in the range of 323–343K is maintained. At the end of the reaction, the sample is analyzed for GPC analyses to determine the molecular weight. A molecular weight of 40,000 is observed for the operating conditions of reaction time for 6hrs and temperature of 343 K. The experiment with optimal operating conditions is repeated in a 2 L batch reactor having a PC for online monitoring with data acquisition software. The product obtained at the end of reaction is given to GPC analysis for molecular weight determination.
Data source location The experimental data collected at Indian Institute of Chemical Technology at Hyderabad, India.
Data accessibility Data is with this article.
Related research article [1] P.Anand, Ch. Venkateswarlu and M. BhagavanthaRao, “Multistage dynamic optimization of a copolymerization reactor using differential evolution”, Asia-Pac. J. Chem.Eng. 8:687–698, 2013
Value of the Data
  • The monitored data can be used by researchers, academicians and industry people for generating control strategies, automation and scale up of polymerization reactors.

  • The dataset covering wide range experimental conditions might be used as a benchmark to validate the findings of other studies.

  • Data standardization provide the opportunity to compare the data acquired under different experimental conditions and highlight the importance of selecting the optimum ranges of conditions.

1. Data

The dataset in this article describes the experimental studies for styrene acrylonitrile copolymer polymerization in a batch reactor with varying temperatures. Real time temperature monitoring using DAQ with desired setpoint is shown in Fig. 1. Experimental conditions with varying temperatures shown in Table 1. GPC analysis results were shown in Table 2. Table 3 describes data acquired during the course of the reaction using DAQ system. Results of GPC calibration at bench scale experiment for optimum molecular weight is shown in Fig. 2. Fig. 3 shows the comparison of temperatures of reactor and jacket. Fig. 4 shows the heat duty and control action during the reaction. Fig. 5. GPC analysis report for the polymer in pilot scale experimentation.

Fig. 1.

Fig. 1

Display of temperature of the reactor and set point during the reaction.

Table 1.

Experimental condition with varying temperatures.

Exp Temp (K) Styrene(g) Acrylonitrile (g) AIBN (g) Xylene (g) Polymer formed (g) Mol. weight
1 323 90.9 81.0 0.1 86.1 0.2989 64,200
2 333 90.9 81.0 0.1 86.1 3.5138 45,300
3 343 90.9 81.0 0.1 86.1 11.576 39,900

Table 2.

GPC analysis.

S.no Elution volume (ml) Retension time (min) Mn Mw MP Mz Mz+1 Mz/Mw
1 16.70 16.72 50,880 64,140 73,800 73,720 81,030 1.15
2 17.10 17.10 31,550 45,270 58,440 55,510 63,570 1.22
3 17.07 17.07 24,100 39,990 59,520 52,650 61,980 1.32

Table 3.

Data acquired during the course of the reaction using DAQ system.

Time (min) Reactor Temperature(K) Jacket inlet temperature(K) Jacket outlet temperature (K) Average temperature (K) set point (K) Control output Duty cycle Coolant Flow
30 343.2373 278.7965 329.610 304.2036 343 −4.1605 0.0000 0.0056
60 339.6759 280.4680 319.048 299.7580 343 12.2869 12.2869 0.0050
90 344.7579 282.1240 321.5317 301.8279 343 2.6171 2.6171 0.0050
120 341.8712 283.6707 320.4821 302.0764 343 9.0822 9.0822 0.0050
150 344.0171 285.1796 321.4157 303.2976 343 4.6150 4.6150 0.0050
180 342.5700 286.5934 320.9544 303.7739 343 7.4371 7.4371 0.0050
210 341.9505 282.6208 321.1993 301.9100 343 10.3653 10.3653 0.0050
240 345.1563 284.2869 327.4002 305.8435 343 −1.4093 0.0000 0.0052
270 341.3274 285.8014 319.9136 302.8575 343 13.8799 13.8799 0.0050
300 345.5229 274.4257 331.2528 302.8392 343 −3.9297 0.0000 0.0055
330 337.3121 274.2209 318.6480 296.4344 343 12.7421 12.7421 0.0050
360 346.4253 275.5112 327.2502 301.38,078 343 −3.1347 0.0000 0.0054

Fig. 2.

Fig. 2

Results of GPC calibration for the obtained product.

Fig. 3.

Fig. 3

Display of temperature of the reactor and set point during the reaction.

Fig. 4.

Fig. 4

Heat duty and control action during the reaction.

Fig. 5.

Fig. 5

GPC analysis report for real time control.

2. Process and model description

In this work, styrene acrylonitrile copolymer is chosen where it is also modeled prior to experimentation [2,3]. The feed is a mixture of monomers (M1, M2), solvent and initiator (I). The mathematical model of the process is given as follows:

dM1/dt=u(M1fM1)/V[(kp11+kf11)P+(kp21+kf21)Q]M1 (1)
dM2/dt=u(M2fM2)/V[(kp22+kf22)Q+(kp12+kf12)P]M2 (2)
dI/dt=u(IfI)/VkdI (3)
dV/dt=u (4)

The moment equations for dead polymers are given by three moments:

dλ0d/dt=(ktc11/2+ktd11)P2+(ktc22/2+ktd22)Q2+(ktc12+2ktd12)PQ+(kf11M1+kf12M2)P+(kf22M2+kf21M1)Q(λ0d/V)u (5)
dλ1d/dt=(ktc11P+ktd11P+ktc12Q+ktd12Q+kf11M1+kf12M2)P1+(ktc22Q+ktd22Q+ktc12P+ktd12P+kf22M2+kf12M1)Q1(λ1du)/V (6)
dλ2d/dt=(ktc11P+ktd11P+ktc12Q+ktd12Q+kf11M1+kf12M2)P2+(ktc22Q+ktd22Q+ktc12P+kf22M2+kf21M1)Q2+ktc11P12+ktc22Q12+2ktc12P1Q1λ2du/V (7)

The rate constants, kd, kfij, kpij, ktcij and ktdij are Arrhenius functions of temperature, the pre-exponential factors and activation energies of which are reported [4].

3. Experimental design, materials, and methods

Experiments were conducted for styrene acrylonitrile polymerization process in a batch reactor with the conditions mentioned in Table 1. Styrene and acrylonitrile of technical grade were used as the reactants. The solvent used is xylene and initiator is AIBN. The experiment was carried out for a constant set point of 343 K (70 °C). The total experiment was carried out for six hours. The product is just cooled to de-activate the polymerization and then precipitated the product into methanol to isolate the polymer. The sample at the end of reaction is given to GPC analysis for molecular weight determination. The monomer used in this study was obtained with 99% purity from Sigma Aldrich. The feedstock was maintained under a temperature of 4 °C in a cold room. The solvent used was xylene purchased from Aldrich with a purity of 99%, and was used without any further purification. Initially, the mixture of styrene and acrylonitrile was heated up to the desired initial temperature of 70 °C.

4. Data aquisition software

The data was monitored using a data aquisition software “LabVIEW” which is a commercial software package installed in the personnel computer to acquire, monitor, handle, analyze and log the data. All the control logic and the program for data logging is written using functions in the block diagram. All the controls and indicators are displayed in the front panel where we can also have online monitoring of the process in the form of charts at runtime. In the block diagram the process parameters are read using the input DAQ Assistant function. These values are logged into text files using the write to measurement file function. The process variable is given to the PI control function and the obtained controller output is fed back to the O/P modules using the output DAQ Assistant function. The required process values are given to a chart to have an online trend while running the process which can be seen on the front panel.

5. Bench scale experiments

Free radical polymerization experiments were carried out in 250 ml glass reactor to establish and optimize the process conditions. The experiment is conducted with varying temperatures (323, 333 and 343K) is listed in Table 1. The molecular weight is analyzed through GPC analysis and a molecular weight of approximate value of 39,900–∼40,000 is observed. GPC analysis as tabulated in Table 2, indicate the conformity of results with the simulated results Anandet.al, 2013, 2014 [2,3].

Real time temperature monitoring using DAQ with desired set point is shown in Fig. 1. Results of GPC calibration at bench scale experiment for optimum molecular weight is shown in Fig. 2. Fig. 3 shows the comparison of temperatures of reactor and jacket. Fig. 4. Shows the heat duty and control action during the reaction. Fig. 5. GPCanalysis report for the polymer in pilot scale experimentation.

6. Gel permeation chromatography (GPC)

The polymer synthesized at the end of the reaction time is subjected to GPC analysis for determination of molecular weight. The sample is first dissolved in solvent (THF-tetra hydro furan) and is injected into a continually flowing stream of tetrahydrofuran (THF) without disturbing the continuous mobile phase flow at a flow rate of 0.05 ml/min. The mobile phase flows through millions of highly porous, rigid particles tightly packed together in a column. The column separates sample components from one another with rapid analyses. Detector used is refractive index to monitor molecular weight distribution which is directly proportional to concentration. In this procedure the molecular weight of the sample is determined based on the standards obtained by plotting the retention time against the log of molecular weight. The operating conditions for these methods are established as flow rate of 0.05 ml/min, detectors were refractive index, the temperature is 24 °C and the column porosities are10000 Å. The molecular weight of SAN copolymer obtained through this method is 30,000.

7. Pilot scale experiments

The operating conditions of reaction time for 6 hrs and temperature of 343 K yield a molecular weight of 39,900 g mol-1 which is nearer to the desired molecular weight of 40,000 g mol-1 is selected as the best operating conditions. The experiment with optimal operating conditions is repeated in a 2 L batch reactor having a PC for online monitoring with data acquisition software. The experimental setup consists of a stainless-steel reactor (Parr) of 2 L capacity with an external jacket with an electric coil for heating, and also with an internal cooling coil. A total volume of 1200 ml of mixture (70% of styrene and 30% of acrylonitrile) was used to carry out the experiments. The experiments were carried out by monitoring and controlling the reactor temperature using the manipulated heater with the aid PID controller algorithms accordingly. The optimum operating conditions that are used in pilot scale experiments were temperature: 343K, styrene: 160ml, acrylonitrile:160ml,xylene:800ml and azobisisobutyronitrile: 1.6 g.

Acknowledgments

Financial assistance from Department of Science and Technology, New Delhi through the grant SR/FTP/ETA-011/2009 is gratefully acknowledged. (CSIR-IICT Communication No: IICT/Pubs./2019/208.)

Conflict of Interest

The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.

References

  • 1.Balaton MiklósGábor, Nagy Lajos, FerencSzeifert Jacket temperature control of a batch reactor using three different temperature levels. Ind. Eng. Chem. Res. 1939;52(5):1946–2013. [Google Scholar]
  • 2.Anand P., Venkateswarlu Ch, BhagavanthaRao M. Multistage dynamic optimization of a copolymerization reactor using differential evolution, Asia-Pac. J. Chem. Eng. 2013;8:687–698. [Google Scholar]
  • 3.Teng Hai-peng, Song Yi-ming. Temperature Control of bench-scaled batch reactor equipped with a monofluid heating/cooling system. J. Therm. Sci. 2014;23(2):187–195. [Google Scholar]
  • 4.Choi K.Y., Butala D.N. Synthesis of open loop controls for semi batch copolymerization reactors by inverse feedback control method. Automatica. 1989;25:917–923. [Google Scholar]

Articles from Data in Brief are provided here courtesy of Elsevier

RESOURCES