The collected datasets are relevant and related to Optimization of Design and Operation of Solar Assisted District Cooling Systems [1] paper. Part of the data is collected on the main and common components of the system. That includes solar collectors unit price ($/m2), type, and efficiency; absorption chiller capacity (kW), type, initial cost ($), and COP; the hot/chilled water thermal energy storage tank type, initial cost ($) and capacity (kWh); and auxiliary boiler initial cost ($), capacity (kW), type and efficiency. The other part of the data is collected on hourly cooling demand over the year for the state of Qatar (kW), hourly global solar irradiance over the year for the state of Qatar (W/m2) and variable cost of producing and storing chilled and hot water ($/kWh, $/kW). The data are collected from different resources such as government websites, commercial websites, government sectors, journals and real-life case studies. The value of this data comes from that most of the data required to conduct such research in this area are available in one resource. Also, some of the data such as the annual hourly cooling demand and global solar radiation are not available online. Moreover, the collected data are already filtered and the units are consistent and ready to be used. Finally, the data considered to be crucial and the core of such research are available in this paper.

Keywords: Solar assisted cooling system, Solar collectors, Absorption chillers, Annual cooling demand


Specifications table

Subject Energy Engineering and Power Technology
Specific subject area District Cooling Systems Coupled with Solar Energy
Type of data Tables
Graph
Figure
How data were acquired Derived Data, Commercial Websites, Governmental Website, Journal Papers, and Real-Life Case Studies.
Data format Raw
Analysed
Filtered
Derived
Parameters for data collection The data of the annual hourly cooling demand and global solar radiations are collected on the year 2016 for state of Qatar. However, the rest of data are collected over the last ten years. The keywords used during the data collected are related to the system components such solar collectors, absorption chillers, auxiliary boilers, and hot and chilled water thermal energy storage (TES) tank
Description of data collection Most of the data are collected from different sources such as commercial and governmental websites, real-life case studies and journal papers. However, the data of the global solar radiation is obtained from a government official. And the data of the annual cooling demand is derived from available data online using a certain approach.
Data source location Department of Mechanical and Industrial Engineering, Faculty of Engineering, Qatar University, Qatar - Doha
Data accessibility The complete datasets described in this study are available in the Mendeley Data repository. The reserved DOI is 10.17632/754wphy77k.1
Related research article Dana Alghool, Tarek Elmekkawy, Mohamed Haouari, Adel Elomari, Optimization of design and operation of solar assisted district cooling systems, Energy Conversion and Management: X, 10.1016/j.ecmx.2019.100028

1. Value of the data

  • Most of the collected data on the parameters of the model such as the annual hourly cooling demand and the annual hourly global solar radiation for the state of Qatar is not available on any sources. These types of data are considered to be essential and the core of any research conducted in this area. Hence, having easy access to this data would save a lot of time on the researcher.

  • The collected data will open doors to other researchers by encouraging them to conduct researches in this area. Most of the data that could be used in this area of research is already available in this paper.

  • Gaining access to such data would make it convenient for the researcher to conduct researches in this area, for instance, the cooling demand data represents the core of any research carried in this area. The researcher can scale down or up the generated cooling demand as per his requirement and experiment since the pattern of the demand would remain the same.

  • The collected data combines all types of data such as capacity, fixed costs, variable costs, etc. required for each component of the system. The complete data of each component are collected from various sources. Hence, having all this data in one source would provide easy access to other researchers in the future.

  • The collected data are filtered and ready for use. Most of the data collected on different parameters were collected and obtained from various sources, so most of the parameters had different measurements units such as capacity and currency units.

1. Data description

The data collected and presented in this paper are based on the parameters of the mathematical model developed in paper [1] which are related to the design and operation of solar assisted district cooling system. The data in this paper are presented in two forms as tables and figures. The figures are generated to represent the tabulated data conveniently and to make a better conclusion. The dataset included in the Mendeley Data repository is an excel sheet that has the data collected on the mathematical model parameters. The sheets of the excel file represent the data collected or derived on a certain parameter. The entire sets of the data collected on the parameters are presented in tables and two out of these parameters are also presented in figures for better data visibility. The type of collected data is related to, the annual hourly cooling demand for the state of Qatar (kW), where Fig. 3 shows the cooling demand of August as a sample and the complete data and figures are included in the repository; the annual hourly global solar radiation for the state of Qatar (W/m2), where Fig. 1 shows the global solar radiation of August as a sample and the complete data and figures are included in the repository; and the annual hourly variable cost of producing and storing chilled and hot water for the state of Qatar ($/kW and $/kWh) is obtained from [32]. Moreover, data specific to the components of the solar assisted district cooling system is collected. One of the components is the absorption chiller where data related to fixed cost ($), capacity (kW), and COP are collected. The collected data are shown in Table 1. The other component is solar collectors, where data related to the type, efficiency and fixed cost ($/m2) are collected. The collected data are shown in Table 2. other components are the hot and chilled water thermal energy storage (TES) tanks, where data related to the type of TES, capacity (kWh) and fixed cost of TES ($) are collected. The collected data are shown in Table 3. Finally, data on the auxiliary boiler component related to fixed cost ($), efficiency, and capacity (kW) are collected. The collected data are shown in Table 4. Hence, data on the five main components of the system were collected. The data collected on each parameter are explained below.

Fig. 2.

Fig. 2

Monthly cooling demand per day for State of Qatar.

Fig. 3.

Fig. 3

Monthly cooling demand of August.

Fig. 1.

Fig. 1

August global solar irradiance.

Table 1.

Data collected on absorption chiller component.

Fixed cost ($) Capacity (kW) Coefficient of performance
8120 35 0.6
16,704,000 12,000 0.8
2,784,000 6000 0.75
5,568,000 12,000 0.75
5,846,400 12,600 0.75
8,352,000 18,000 0.75
153,336 150 0.7
116,999 50 0.7
128,599 100 0.7
145,999 200 0.7
151,799 250 0.7
163,398 300 0.7
174,998 350 0.7
184,990 400 0.7
198,198 450 0.7
600,000 176 0.7
2,024,000 1547 0.74
4,752,000 4642 0.79
1,980,000 1161 1.42
5,808,000 4642 1.42
2,178,000 1161 1.35
4,000,000 3517 1.38
124,120 233 1.36
229,680 582 1.36
283,040 872 1.36
338,720 1163 1.36
399,040 1454 1.36
443,120 1745 1.36
559,120 2326 1.36
650,760 2908 1.36
737,760 3489 1.36
892,040 4652 1.36
1,053,280 5830 1.36
1,195,960 7000 1.36
1,512,640 9304 1.36
3,493,920 24,000 1.36
5,240,880 36,000 1.36
6,987,840 48,000 1.36
8,734,800 60,000 1.36
1,746,960 12,000 1.36
80,000 100 0.5
2,150,000 5000 1.3
1,228,000 2000 1.2
737,000 1000 1.1
460,500 500 0.8
2,568,031.2 17,640 1.36

Table 2.

Data collected on solar collectors component.

Solar collector type Fixed cost ($/m2) Efficiency
Flat plate and evacuated tube 162$/m2 0.70
Flat collector 300 $/m2 0.75
500 $/m2 0.75
700 $/m2 0.75
900 $/m2 0.75
1100 $/m2 0.75
34.19 - 56.98 $/m2
102.56 - 170.93 $/m2
650 $/m2 0.40
429.61 $/m2 0.40
859.23 $/ m2 0.40
1287.70 $/m2 0.40
533 $/m2 0.21
505 $/m2
159 $/m2
339 $/m2 0.38
360 $/m2 0.43
333.33 $/m2 0.45
346 $/m2 0.36
310 $/m2 0.35
827.32 $/m2 0.327
747.55 $/m2 0.268
708.80 $/m2 0.212
1220.46 $/m2 0.316
731.59 $/m2 0.371
711.08 $/m2 0.356
920.76 $/m2 0.345
589.15 $/m2 0.346
1125 $/m2 0.70
Vacuum tube 847 $/m2 0.49
621 $/m2 0.36
Evacuated tube 1154$/m2 0.44
858 $/m2 0.63
827$/m2 0.54
576 $/m2 0.39
815 $/m2 0.52
1148 $/m2 0.57
740 $/m2 0.42
2000$/m2
1095 $/m2

Table 3.

Data collected on chilled & hot TES component.

Thermal energy storage type Capacity (kWh) Fixed cost ($)
TTES 1,230,898 360,294
8,616,289 2,522,059
1,195,730 350,000
8,370,110 2,450,000
2,285,954 455,000
2,180,449 434,000
3,165,168 630,000
6,330,335 1,260,000
18,991,005 3,780,000
703,371 500,000
50 580
14 488
4 1069
375,000 495,000
938 237,600
1278 308,880
1,440,000 1,900,800
8,640,000 11,404,800
855,000 1,128,600
156,900 740,305
261,621 1,105,887
600,966 1,398,353
PTES 12,000,000 4,752,000
4,500,000 1,782,000
3,600,000 1,425,600
7,200,000 2,851,200
84,000 33,264
270,000 106,920
63,000 24,948
75,663 29,963
126,000 49,896
90,000 35,640
58,106 462,691
40,758 196,500
307,246 726,595
579,710 913,956
4,330,985 3,513,021
BTES 285,000 150,480
562,000 297,000
504,855 266,563
900,000 475,200
949,500 501,336
140,250 73,920
290,322 514,100
261,627 257,050
619,008 855,692
Hot water tank 576,000 5,220,000
2556 617,760
1876 475,200
2814 712,800
500 58,000
750 87,000
1000 116,000
1250 145,000
1500 174,000
1750 203,000
2000 232,000
2250 261,000
2500 290,000
17,482 163,369
34,865 311,888
Chilled water tank 998,786 626,600
2,707,977 913,000

Table 4.

Data collected on auxiliary boiler component.

Auxiliary boiler type Fixed cost ($) New capacity (kW) Efficiency
Gas boiler 4,640,000 50,000 0.55
32,450 234 0.85
Oil boiler 4,640,000 50,000 0.8
1,392,000 10,000 0.8
4,176,000 30,000 0.8
5,568,000 40,000 0.8
6,960,000 50,000 0.8
2,784,000 20,000 0.8
31,500 234 0.82
82,064 4104 0.85
123,096 6156 0.85
164,128 8208 0.85
205,160 10,260 0.85
246,192 12,312 0.85
125,000 7000 0.85
254,398,4 12,722 0.85
318,750 17,850 0.85
Liquid fuel boiler 2,250,000 60 0.6
4,230,000 120 0.6
9,900,000 300 0.6
18,900,000 600 0.65
36,900,000 1200 0.65
74,250,000 3000 0.7
148,500,000 6000 0.7
222,750,000 9000 0.7
297,000,000 12,000 0.7
Coal boiler 2,250,000 60 0.5
4,230,000 120 0.5
9,900,000 300 0.5
18,900,000 600 0.55
36,900,000 1200 0.55
74,250,000 3000 0.6
41,032 2052 0.85
182,438 733 0.8
1,459,504 5861 0.8
103,010 733 0.8
486,156 440 0.8
101,278 733 0.8
180,674 440 0.8
95,125 733 0.8
88,475 586 0.8
Electric boilers 7047 25 0.96
24,000 100 0.96
57,000 250 1
1,328,100 5875 1
11,750 165 0.98

2. Experimental design, materials, and methods

The method used to acquire the collected data in this paper varies between using commercial websites, governmental websites, journal papers, real-life case studies and governmental officials. A vast number of commercial websites, journal papers, and real-life case studies of different countries (i.e., Europe, the United States of America and Qatar) are visited to collect the required information and data on the parameters. Different keywords related to the area of research are used in the research engine during data collection. The raw data collected on a certain parameter had usually different units as they gathered from websites of different countries, so they are filtered to enhance their quality. The filtration process included unifying all measurement units such as currency and power conversions to make all the collected data consistent and then they are included in the below tables. This applies to the data collected on parameters related to the system components which are absorption chiller, solar collectors, auxiliary boiler, chilled and hot water TES tank. However, data of other parameters which are variable costs of producing and storing hot and chilled water, annual hourly global solar radiation and annual hourly cooling demand, the data are collected from other sources. The data of the variable costs of producing and storing hot and chilled water parameters are obtained directly from a governmental website which is Kahramaa's - the water and electricity service provider at Qatar- website. While data of the annual hourly global solar radiation parameter are obtained from Kahramaa's database through a governmental official. The obtained raw data had solar global radiation values from December 2014 to December 2016 for the state of Qatar. However, the data was filtered and only the data related to the year 2016 was extracted and used in the research to match the annual hourly cooling demand data. The data of annual hourly cooling demand is derived using a specific approach explained thoroughly below. The approach uses temperature as an input, so the temperature of the year 2016 for Qatar is used, along with other inputs. The process of collecting data for each parameter of the solar assisted district cooling system is explained below.

2.1. Absorption chiller component

The data collected on the Absorption Chiller component includes the following parameters, fixed investment cost of installing a chiller ($), its capacity (kW) and coefficient of performance (COP). The data are collected from commercial websites [2]. Different keywords related to the area of research are used in the research engine during data collection. The collected data are filtered and refined, it means that all the data have consistent units. The number of collected inputs is 46. Table 1 shows the data collected on the absorption chiller component.

2.2. Solar collectors component

The data collected on the Solar Collector component includes the following parameters, fixed cost of installing a unit area ($/m2), and efficiency of a solar collector. The data are collected from different sources such as real-life case studies and commercial websites [3], [4], [5], [6]. There are 40 inputs. Data are collected on different types of solar collectors which are flat plate, evacuated tube, vacuum tube, and evacuated tube. Different keywords related to the area of research are used in the research engine during data collection. The collected data are filtered and refined, it means that all the inputs have consistent units. Table 2 shows the data collected on the solar collector component.

2.3. The chilled and hot water thermal energy storage tank component

The collected data on Thermal Energy Storage (TES) component includes the following parameters, fixed cost of installing chilled water and a hot TES tank ($), and their capacity (kWh). The data are collected from different sources [7], [8], [9]. Most of the collected data are obtained from real-life case studies from all around the world. There are different types of TES that can be used for commercial aspects such as Water Tank Thermal Energy Storage (TTES), Pit Thermal Energy Storage (PTES), and Borehole Thermal Energy Storage (BTES). These types differ in the way they function, installation and duration of storing the heat of the water in the tank (Inter day, seasonal, etc.). The data are collected on different types of TES and different keywords related to the area of research are used in the research engine during data collection. The collected data are filtered and refined, it means that all the inputs have consistent units. The number of collected inputs for hot and chilled water thermal energy storage tank is 63 inputs. Table 3 shows the data collected on the chilled and hot water TES component.

2.4. Auxiliary boiler component

The collected data on the auxiliary boiler component includes the following parameters, fixed cost of installing boiler ($), it is capacity (kW) and efficiency. The data are collected from different sources such as real-life case studies and commercial websites [10], [11], [12], [13], [14]. The data are collected on different types of boiler such as oil, gas, and electric boiler. Different keywords related to the area of research are used in the research engine during data collection. The collected data are filtered and refined, it means that all the inputs have consistent units. The number of collected inputs is 46. Table 4 shows the data collected on the auxiliary boiler component.

2.5. Variable cost of producing and storing chilled and hot water

The variable cost of producing or storing chilled or hot water at TES is related to the cost of electricity consumption. In Qatar, the cost of electricity is constant throughout the year, so it doesn't vary. Hence, the cost of electricity consumption is obtained directly from the electricity and water service provider in Qatar, which is Kahramaa's website [15]. The variable costs of producing a unit of chilled water from a chiller or a unit of hot water from an auxiliary boiler ($/kW) will be the same as the cost of electricity consumption. Moreover, the variable cost of storing a unit of chilled water at chilled TES or storing a unit of hot water at hot TES ($/kWh) will be the same as the cost of electricity consumption. According to Kahramaa's website [15], the cost of electricity consumption for the commercial industry is 0.055 $/kWh.

2.6. Annual hourly global solar radiation

The data required for global solar radiation (W/m2) is the annual hourly global solar radiation for the state of Qatar. It is collected from the government sector Kahramaa's database -the water and electricity service provider - at Qatar. Hence, the collected data represents the state of Qatar- Doha. The raw data obtained from the database, through a governmental official, had solar radiation values from December 2014 to December 2016. However, the data was filtered and only the data related to the 2016 year was extracted and used in the research. As an example, the global solar radiation of August is shown in Fig. 1, the complete data and figures are included in the repository. The figures and data indicate that the global solar radiation is obtained during the daytime periods.

2.7. Annual hourly cooling demand

The annual hourly cooling demands for Qatar state are collected over 8784 h/ year. However, the only cooling demand data available for Qatar is the hourly cooling demand for only a day in the month for the year 2016. They are obtained from a graph included in Quantifying the Cost of Cooling in Qatar [16] as shown in Fig. 3. However, the required data for the cooling demand is the annual hourly cooling demand (i.e., 8784 h/ year). In order to find the cooling demands for the other days in the month, the average temperature for each day in the month is calculated and the day with the highest average temperature in the month is assigned to the cooling demand which is already given in the graph. This day is considered to be a reference day where the cooling demand for the other days is calculated based on this day. So, for the rest of the days in the month, a ratio of the hourly temperature of the day -the day to find the cooling demand for- to the hourly temperature of the reference day multiplied by the cooling demand of that hour of the reference day. By doing so, the required data (i.e., annual hourly cooling demand) are derived from the online available raw data.

CoolingDemandforadayiatanhourj=TemperatureofdayiatanhourjTemperatureofreferencedayatanhourj×Coolingdemandofreferencedayatanhourj

The hourly temperature of Qatar is obtained from [17] and these temperatures correspond to the year 2016 to ensure that it is consistent with the data of global solar radiation and cooling demand as they represent the year 2016. The complete figures and data of hourly cooling demands for each day in the month for the 2016 year are included in the repository. Fig. 3 shows the annual hourly cooling demand of August as an example. The pattern is the same as the cooling demand obtained from Quantifying the Cost of Cooling in Qatar [16].

Acknowledgments

The publication of this article was funded by the Qatar National Library.

This publication was made possible by the NPRP award [NPRP 10-0129-170280] from the Qatar National Research Fund (a member of The Qatar Foundation). The statements made herein are solely the responsibility of the author[s].

Conflict of Interest

The authors have no known competing financial interests or personal relationships which influenced the work reported in this article.

References


Articles from Data in Brief are provided here courtesy of Elsevier

RESOURCES