Dataset of the EnergyPlus model used in the assessment of natural ventilation potential through building simulation

NRM Sakiyama a,b,, L Mazzaferro c, JC Carlo d, T Bejat e, H Garrecht a
PMCID: PMC7843397  PMID: 33537372

Abstract

The data set compiled in this file refers to the Multizone EnergyPlus model, used in the investigations of the research article entitled "Natural ventilation potential from weather analyses and building simulation". The technical information regarding the model has been grouped into tables, which include: the general simulation settings, the properties of the building materials, the Airflow Network opening settings used in the annual investigation, in addition to the controls established in the Energy Management System (EMS) for hybrid ventilation system operation. The user behaviour, regarding the living and bedrooms occupancy schedule, is also presented in a graph. This data set is made available to the public to clarify details of the EnergyPlus model and how the hybrid operation was defined. In this way, other researchers can perform an extended analysis of the information.

Keywords: Building simulation, EnergyPlus, Airflow network, Hybrid system, Natural ventilation

Specifications Table

Subject Engineering, Architecture
Specific subject area Building simulation in hybrid mode: heating loads and thermal comfort assessment
Type of data Tables
Graph
Text
How data were acquired Building energy modelling – Computer simulation using EnergyPlus software
Data format Raw
Parameters for data collection Building energy model (input data file -.idf) created from a full-scale test passive house
Description of data collection The model geometry was developed using SketchUp Make 2017 with OpenStudio Plugin for EnergyPlus and the computer simulation run using EnergyPlus software, version 9.1
Data source location French National Institute for Solar Energy - INES
Chambery, French Alps
France
45° 38′38.5 "N, 5° 52′27.4 "E
Data accessibility With the article
EnergyPlus files (.idf): https://data.mendeley.com/datasets/rp6xy7rfhn/1
Related research article Sakiyama NRM, Mazzaferro L, Carlo JC, Bejat T, Garrecht H. Natural ventilation potential from weather analyses and building simulation. Energy and Buildings 2021;231:110596. https://doi.org/10.1016/j.enbuild.2020.110596

Value of the Data

  • The detailed data related to the EnergyPlus model guarantees a better and deeper understanding of the building addressed in the research paper [1], grounding the study developed and providing more information to aid in reading the paper.

  • Both building modelling and simulation are performed using EnergyPlus software. Different configurations/ simulation techniques could be employed based on this available data, so different studies might be compared.

  • The data presented in this article can assist designers and researchers who deal with the modelling of naturally ventilated buildings, especially with Airflow Network and multizone approach.

  • The use of Energy Management System (EMS) to model hybrid ventilation operation could be adopted as a reference for further research on naturally ventilated buildings.

1. Data Description

The data in this article present the input data regarding the EnergyPlus model used at the investigations addressed in the research paper. General simulation settings are summarised in Table 1, while the building materials properties are listed in Table 2. Table 3 shows the Airflow Network opening settings used in the annual investigation. Finally, the occupancy schedule, which specifies when the living and bedrooms were occupied, as well as its respective number of people, can be seen in Fig. 1.

Table 1.

General simulation settings.

Calibration Model (a) Annual Analyses (b)
Run period 19th till 25th August 1st January till 31th Dezember
Airflow simulation Airflow Network
HVACTemplate:Zone:PTHP
EMS: Airflow Network
HVACTemplate: Zone:IdealLoadAirSystem
Solar distribution FullExteriorWithReflections
Surface convection Algorithm: Inside TARP
Surface convection Algorithm: Outside DOE-2
Heat Balance Algorithm ConductionTransferFunction
Monthly ground temperature (˚C) 4.5, 6.21, 9.3, 12.99, 16.28, 18.27,18.43, 16.69, 13.55, 9.86, 6.58, 4.62
Time steps per hour 6

Table 2.

Building material properties.

Construction type Construction name Material layers
(outside to inside)
Thickness (m) Conductivity (W/m-K) Density (kg/m3) Specific Heat (J/kg-K) Thermal Absorptance Solar Absorptance Visible Absorptance
Façade MurExt_isole Porotherm R42
(Hollow brick)
0.425 0.115 700 986 0.9 0.6 0.6
Plaster 0.01 0.4 1200 1000 0.9 0.6 0.6
Internal walls Cloisons_Etage Placo_13mm 0.013 0.25 825 1008 0.9 0.6 0.6
Glass Wool 5cm 0.05 0.032 12 840 0.9 0.6 0.6
Placo_13mm 0.013 0.25 825 1008 0.9 0.6 0.6
Underground walls Mur_vs Structural Wall 0.425 2.5 2500 1000 0.9 0.6 0.6
Underground floor slab PB_VS Gravel 0.05 1.4 2100 650 0.9 0.6 0.6
Underground ceiling slab PH_VS_isole Structural slab 0.2 2.5 2500 1000 0.9 0.6 0.6
PolystyreneXtrude 0.16 0.027 35 1400 0.9 0.6 0.6
Ground floor slab PH_RCD Concrete screed 0.08 1.75 2400 880 0.9 0.6 0.6
Compression slab 0.04 1.75 2400 880 0.9 0.6 0.6
Hollow concrete slab 0.16 1.23 1300 648 0.9 0.6 0.6
Attic slab PB_COMBLES_isole Plaster 0.9 0.6 0.6
Glass Wool Filling 0.44 0.032 12 840 0.9 0.6 0.6
OSB Floor 0.022 0.13 640 1700 0.9 0.6 0.6
Roof Toit Tiles 0.015 2.2 1121 1460 0.9 0.7 0.7
Wood Structure 0.08 0.055 265 836 0.9 0.7 0.7
Metal Decking 0.0015 45 7680 418 0.9 0.6 0.6

Table 3.

AFN opening settings – annual investigation.

Opening name/ orientation U-factor (W/m²K) Solar Heat Gain Coefficient Opening Factor Ventilation Control Mode Discharge Coefficient Temp. set point Ventilation Availability schedule
External Windows Cellar_N 1.68 0.24 0.75 Temp. 0.50 20 EMS
Living_E 1.4 0.21 0.75 Temp. 0.50 20 EMS
Hall_E 1.4 0.21 0.75 Temp. 0.50 20 EMS
Living_S 1.28 0.47 0.75 Temp. 0.50 20 EMS
Bedroom3_S 1.34 0.39 0.75 Temp. 0.50 20 EMS
Stairs_N 1.32 0.21 0.75 Temp. 0.50 20 EMS
Internal Doors - - - NoVent 0.55 - -
Horizontal Opening
(Stair case)
- - 1 Constant 0.2 - -

Fig. 1.

Fig 1

Occupancy schedule – annual simulation a=Weekdays schedule; b= Weekend schedule.

The model set up is based on consolidated practices used in studies involving INES' experimental houses, and therefore does not use the EnergyPlus database. Since they are originally unoccupied, a classic family occupancy schedule was established, which would represent an extreme/worse possible scenario.

Besides, the EnergyPlus input data files (.idf) are available for download in the Mendeley repository [2], and the link can be found in the Specifications table/ Data accessibility. The files supplied include: the calibration (a) and the annual analysis (b) models, which are summarized in Table 1.

2. Experimental Design, Materials and Methods

The controls developed in the Energy Management System (EMS) object for the consolidation of the hybrid behaviour at the annual analyses are presented below. The operation mode was adopted in all occupied zones, exemplified here by the living room zone.

The set up enables the following changes: triggering the thermal load calculation at a temperature different from the thermostat; deactivation of the thermal load calculation only after occupancy in a room is null; hybrid control, where the local thermal prognosis is not allowed to occur together with the window opening for natural ventilation in the same time step.

All objects in class: energymanagementsystem:sensor

EnergyManagementSystem:Sensor,

OT_Living, !- Name

Living, !- Output:Variable or Output:Meter Index Key Name

Zone Operative Temperature; !- Output:Variable or Output:Meter Name

EnergyManagementSystem:Sensor,

Occ_Living, !- Name

Living_Occ, !- Output:Variable or Output:Meter Index Key Name

People Occupant Count; !- Output:Variable or Output:Meter Name

EnergyManagementSystem:Sensor,

Ext_Temp, !- Name

Environment, !- Output:Variable or Output:Meter Index Key Name

Site Outdoor Air Drybulb Temperature; !- Output:Variable or Output:Meter Name

EnergyManagementSystem:Sensor,

T_Living, !- Name

Living, !- Output:Variable or Output:Meter Index Key Name

Zone Mean Air Temperature; !- Output:Variable or Output:Meter Name

EnergyManagementSystem:Sensor,

Heat_Living, !- Name

Heat_Living, !- Output:Variable or Output:Meter Index Key Name

Schedule Value; !- Output:Variable or Output:Meter Name

All objects in class: energymanagementsystem:Actuator

EnergyManagementSystem:Actuator,

HeaterControl_Living, !- Name

Heat_Living, !- Actuated Component Unique Name

Schedule:Constant, !- Actuated Component Type

Schedule Value; !- Actuated Component Control Type

EnergyManagementSystem:Actuator,

NVControl_Living, !- Name

NV_Living, !- Actuated Component Unique Name

Schedule:Constant, !- Actuated Component Type

Schedule Value; !- Actuated Component Control Type

All objects in class: energymanagementsystem:programcallingmanager

EnergyManagementSystem:ProgramCallingManager,

HybridControl, !- Name

BeginTimestepBeforePredictor, !- EnergyPlus Model Calling Point

Hyb_Living, !- Program Name 1

All objects in class: energymanagementsystem:program

EnergyManagementSystem:Program,

Hyb_Living, !- Name

SET Temp_Heat = T_Living <= 19, !- Program Line 1

IF ((Occ_Living > 0) && (Temp_Heat ==1)), !- Program Line 2

SET HeaterControl_Living =1, !- A4

SET NVControl_Living = 0,!- A5

ELSEIF ((Occ_Living > 0) && (Heat_Living >0)), !- A6

SET HeaterControl_Living = 1, !- A7

SET NVControl_Living = 0,!- A8

ELSEIF (Occ_Living > 0), !- A9

IF ((Ext_Temp<T_Living) && (Ext_Temp>20)), !- A10

SET HeaterControl_Living = 0, !- A11

SET NVControl_Living = 1,!- A12

ELSEIF ((Ext_Temp>T_Living) && (Ext_Temp>20)), !- A13

SET HeaterControl_Living = 0, !- A14

SET NVControl_Living = 0,!- A15

ELSEIF (Ext_Temp<20), !- A16

SET HeaterControl_Living = 0, !- A17

SET NVControl_Living = 0,!- A18

ENDIF, !- A19

ELSEIF (Occ_Living == 0),!- A20

SET HeaterControl_Living = 0, !- A21

SET NVControl_Living = 0,!- A22

ENDIF; !- A23

CRediT Author Statement

Nayara R. M. Sakiyama: Conceptualization, Methodology, Software, Data-curation, Formal analysis, Investigation, Writing-Original draft preparation; Leonardo Mazzaferro: Software, Visualization, Validation, Writing-Reviewing and Editing; Joyce C. Carlo: Supervision; Timea Bejat: Resources; Harald Garrecht: Project administration.

Declaration of Competing Interest

The authors declare that they have no known competing financial interests or personal relationships which have, or could be perceived to have, influenced the work reported in this article.

Acknowledgements

This research was possible thanks to the contributions of the French National Institute for Solar Energy (INES, France), the Federal University of the Jequitinhonha and Mucuri Valleys (UFVJM, Brazil), and the Materials Testing Institute University of Stuttgart (MPA, Germany), which collectively supported this work.

Footnotes

Supplementary material associated with this article can be found in the online version at doi:10.1016/j.dib.2021.106753.

Appendix. Supplementary materials

mmc1.zip (19KB, zip)
mmc2.zip (21.2KB, zip)
mmc3.zip (207.9KB, zip)
mmc4.zip (202.4KB, zip)

References

  • 1.Sakiyama N.R.M., Mazzaferro L., Carlo J.C., Bejat T, Garrecht H. Natural ventilation potential from weather analyses and building simulation. Energy and Buildings. 2021;231:110596. doi: 10.1016/j.enbuild.2020.110596. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 2.Sakiyama N. EnergyPlus Models - Research paper: Natural ventilation potential from weather analyses and building simulation. Mendeley Data. 2021;V2 doi: 10.17632/rp6xy7rfhn.2. [DOI] [PMC free article] [PubMed] [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Supplementary Materials

mmc1.zip (19KB, zip)
mmc2.zip (21.2KB, zip)
mmc3.zip (207.9KB, zip)
mmc4.zip (202.4KB, zip)

Articles from Data in Brief are provided here courtesy of Elsevier