Manipulating polymer composition to create low-cost, high-fidelity sensors for indoor CO2 monitoring

Zachary A Siefker 1,2, John N Hodul 3, Xikang Zhao 4, Nikhil Bajaj 1,2,5, Kelly M Brayton 4, Carsten Flores-Hansen 3, Wenchao Zhao 4, George T-C Chiu 1,2,5, James E Braun 1,2, Jeffrey F Rhoads 1,2,5,, Bryan W Boudouris 3,4,
PMCID: PMC8225849  PMID: 34168189

Abstract

Carbon dioxide (CO2) has been linked to many deleterious health effects, and it has also been used as a proxy for building occupancy measurements. These applications have created a need for low-cost and low-power CO2 sensors that can be seamlessly incorporated into existing buildings. We report a resonant mass sensor coated with a solution-processable polymer blend of poly(ethylene oxide) (PEO) and poly(ethyleneimine) (PEI) for the detection of CO2 across multiple use conditions. Controlling the polymer blend composition and nanostructure enabled better transport of the analyte gas into the sensing layer, which allowed for significantly enhanced CO2 sensing relative to the state of the art. Moreover, the hydrophilic nature of PEO resulted in water uptake, which provided for higher sensing sensitivity at elevated humidity conditions. Therefore, this key integration of materials and resonant sensor platform could be a potential solution in the future for CO2 monitoring in smart infrastructure.

Subject terms: Sensors and biosensors, Polymers

Introduction

It is estimated that the average American and European spends nearly 90%13 of their time indoors, and consequently, CO2 concentrations in buildings can range from those seen in outdoor environmental conditions (i.e., ~ 400 ppm) to 3000 ppm, depending on the occupancy of the confined space4,5. Moreover, CO2 is regarded as a toxic contaminant with an OSHA time-weighted average (TWA) exposure limit of 5000 ppm over an 8-h workday or a short-term exposure limit of 15,000–30,000 ppm over 15 min6. Importantly, CO2 exposure at as low of a concentration as 1000 ppm negatively affects cognitive performance, including decision making and problem resolution79. Thus, appropriate indoor air quality monitoring and building ventilation systems, equipped with low-cost, high-fidelity CO2 sensors, are required. However, many current sensing technologies suffer from limitations and drawbacks, such as arduous device fabrication techniques or high power consumption, which limits their practical and widespread implementation in residential, commercial, and industrial settings. Thus, there is a critical need for a low-cost, low-power CO2 sensor that is easy to manufacture and can be incorporated into existing buildings to upgrade these structures into “smart buildings” in a seamless manner.

State-of-the-art CO2 detection methods have relied primarily on gas chromatography and spectroscopy methods, which are typically high-cost and require large instrumentation footprints1013. In particular, there has been a large push to use infrared (IR) spectroscopy to detect CO2 gas. Typically, CO2 infrared sensors are nondispersive infrared (NDIR) sensors where a broadband lamp source and an optical filter are used to select a narrow band in the spectral region that overlaps with the absorption region of the gas of interest. However, NDIR detection of CO2 is limited by spectral interference, a high detection limit, and interference from water vapor14. In fact, even many new NDIR CO2 sensors have readings that deviate from actual CO2 concentrations by more than 75 ppm15,16 and potentially even greater error if not regularly calibrated17. Additionally, the infrared light inherent to NDIR sensors, often results in bulky instrument size due to the length of the light path (> 1 cm) and high power consumption (> 200 mW), which limits their use in embedded applications, such as internet-of-thing-based (IoT-based) smart buildings. Recently there has been work in creating a handheld, low-power (i.e., < 1 W), and sensitive (i.e., 50 ppm) CO2 NDIR sensor capable of performing breath analysis18. Though intriguing, this device is not being manufactured for indoor air quality monitoring, and therefore lags in areas of testing and performance typical of indoor environments18. Thus, current NDIR CO2 sensors do not meet the power, size, and selectivity metrics necessary for a practically scalable sensor that can meet the demands of smart building technologies suitable for the indoor monitoring of CO2.

Conversely, microelectromechanical systems-based (MEMS-based) resonant mass sensors are a promising sensor paradigm for this application space as they exhibit high performance metrics in gas detection due to their compact size, low cost, low power, fast response times, and high sensitivity1923. Importantly, when microresonators are functionalized with specific surface chemistries, target analytes non-covalently bind, or otherwise chemo-mechanically interact, with the sensor. This change in mass on the surface induces a shift in the resonant frequency of the device, which can be readily and precisely quantified. In fact, cantilevered-type resonant mass sensors are sensitive enough to detect bacteria and a single virus in the air24,25. Therefore, MEMS-based devices are an ideal platform for smart building integration if they can be functionalized with the appropriate and selective chemistry in a low-cost, high-throughput manner26. Given this potential, we fabricated a resonant mass sensor with a solution-processable polymer blend of poly(ethylene oxide) (PEO) and poly(ethyleneimine) (PEI) coated atop the resonant platform. The selection of these two materials was rather straightforward. First, PEI contains multiple amine groups that have been shown to effectively perform reversible acid–base reactions with CO22730. However, due to the viscous nature of PEI, diffusion of the CO2 into the material to perform such reactions is limited. Thus, we employed a hydrophilic, semicrystalline polymer, PEO31, in the blend with PEI to enhance the sensitivity and response rate of CO2 uptake. The PEO has two roles when being incorporated into the PEI. First, it disrupts intrachain and interchain PEI entanglement at the molecular level and the surface morphology at the nanoscale level. Both of these positive disruptions facilitate increased interactions between accessible amines and CO2. Second, the hydrophilic nature of PEO attracts water into the blended thin film; in turn, this water converts the reversible acid–base formed carbamates (i.e., the product of CO2 reacting with primary and secondary amines) into bicarbonates freeing amines to enhance the adsorption and uptake of CO2. This critical addition of the PEO moiety allows for the macromolecular blend to have selective and significantly enhanced detection of CO2 relative to previous efforts. This synergetic chemical blending and subsequent polymer processing, in combination with the resonant mass sensor platform, allows for the fabrication of a low-cost and effective CO2 sensor. In comparison to other CO2 sensing counterparts, this sensor is compact, with a footprint of < 25 mm2, and offers high sensitivity (i.e., at a detection limit of CO2 as low as 5 ppm). Moreover, these sensors detect CO2 selectively over other polar compounds (e.g., methanol and acetone), as well as non-polar compounds (e.g. xylene and propane). Thus, this sensing platform offers an easily functionalized, low-cost, low-power, multi-channel sensing array capable of quick and reliable detection.

Results

Sensor response and dynamic range

Resonant mass sensors functionalized with a PEI-PEO polymer blend were able to detect CO2 across an extended range of concentrations relevant to indoor air quality monitoring (Fig. 1). Critically, these sensors demonstrated a highly linear response at CO2 concentrations relevant to the targeted application of buildings. This range is roughly defined by a lower bound of 400 ppm (i.e., the concentration that is typical for air outdoors, located in unoccupied spaces) and an upper bound of 2000 ppm. A building with well-controlled ventilation will have CO2 concentrations around 1100 ppm, which is the central region of interest32. Fig. 1a–c highlight sensor responses at CO2 concentrations that are relevant to indoor environments. These data demonstrate sensor performance in a background of nitrogen and a background of air (i.e., ~ 78% nitrogen, ~ 21% oxygen, and 0.12% carbon dioxide). In both the nitrogen and air backgrounds, the sensor response was linear and proportional to the increase in CO2 concentrations above the background concentrations with an interpolated sensitivity of approximately 0.12 Hz ppm−1 CO2 (Fig. 1c). However, these responses were determined for 1 h pulses of CO2 which was often not long enough for the functional material to fully saturate with carbon dioxide. This delayed response and recovery time may prove problematic in some applications. In such cases, a thinner film of the functional material may be used such that it saturates with CO2 in less time. However, this will be done at the expense of increasing the limit of detection which may be interpolated based on a 1 Hz frequency resolution. Thus, optimization of this point will be specific to the end-use application. Further, the desorption of CO2 occurs at a slower rate than adsorption, resulting in the drifting baseline in the time series data (Fig. 1a,b). The time series data (Fig. 1a,b) show the resonators decreasing in frequency as CO2 is adsorbed on top of the resonator. The added CO2 mass on the resonator decreases its resonant frequency, as described, for example, by the Sauerbrey equation33,34. The magnitude of the frequency shift is greater at higher concentrations due to an increased amount of CO2 adsorbing onto the resonator. Thus, the change in CO2 concentration induces a clear shift in resonant frequency of the sensor.

Figure 1.

Figure 1

Sensor response to CO2 shown as a frequency shift of the resonant element. (a) Sensor response to CO2 over time with a background of nitrogen. The resonant frequency shift response is indicated by the blue line (left vertical axis), and the red bars indicate when CO2 is present (right vertical axis). (b) Sensor response to CO2 over time with a background of air. The resonant frequency shift response is indicated by the blue line (left vertical axis), and the red bars indicate when CO2 is present (right vertical axis). The use of air brought the baseline CO2 concentration to 1200 ppm. (c) Total frequency shift of the device after 1 h of CO2 at specified concentrations. The average of 8 responses is shown with error bars representing one standard deviation. Regardless of the baseline conditions, a similar linear response is obtained by the sensor, as demonstrated by the linear regression fit. (d) The dynamic range of the sensor is shown by plotting the resonant frequency shift in response to 1 h of CO2 in a background of nitrogen. For comparison, outdoor air CO2 concentrations35 are indicated by the solid blue line, healthy indoor air CO2 levels32 are indicated by the dashed green line, poor indoor air CO2 levels32,36 are indicated by the dashed orange line, and toxic CO2 levels37 are indicated by the dashed red line. Additionally, the sensitivity (indicated by the change in frequency per change in CO2 concentration, fc) is shown at both low and high concentrations.

Moreover, this sensor has a large dynamic range and can detect CO2 at concentrations well beyond what is relevant to indoor air monitoring (Fig. 1d). Unlike the relatively linear response demonstrated below 2000 ppm CO2, when the sensor is exposed to larger concentrations, a nonlinear response is apparent as the frequency shift per ppm of CO2 decreases asymptotically. This is consistent with a Langmuir sorption model where the rate of adsorption decreases as the available surface binding sites are filled38. Nevertheless, this sensor can discriminate CO2 concentrations well beyond toxic levels for human occupancy37.

Performance in indoor environments

Even in a relatively well-controlled, indoor environment, air conditions can drastically vary in both temperature and humidity level. Thus, it is important to account for these variables and demonstrate sensor performance across a span of potential environmental conditions. A ‘comfort zone’, which describes indoor air conditions that most people find comfortable, has been defined by the engineering society ASHRAE39. This region is outlined on the psychrometric chart (Fig. 2a) based on indoor air temperatures and humidity levels. Using the comfort zone as a guide, a test region was developed spanning approximately 22–26 °C and 0–80% relative humidity (at a given temperature), and testing was performed near the extremes of this region, as well as near the center.

Figure 2.

Figure 2

(a) Psychrometric chart defining the ‘Comfort Zone’ air temperature and humidity range, as defined by the engineering association, ASHRAE. Testing was performed across this region to simulate environmental conditions expected in high performance buildings. (b) Frequency response of devices functionalized with PEI only, and a 3:1 PEO:PEI blend ranging from 0 to 80% relative humidity (RH). Tests were performed holding temperature at 24 °C. The average of 8 responses is shown with error bars representing one standard deviation. (c) Sensor response to CO2 while varying temperature from 22 to 26 °C and relative humidity from 10 to 80% to cover the indoor air comfort zones39. The average of 8 responses is shown with error bars representing one standard deviation. A baseline condition of 400 ppm CO2 in nitrogen was used to simulate outdoor air conditions and a linear response is obtained at each condition, as demonstrated by the linear regression fits. (d) The rate of change in frequency shift after each increase in CO2 concentration from a background of 400 ppm. The average of 8 responses is shown with error bars representing one standard deviation. A similar linear response is obtained at each condition, as demonstrated by the linear regression fits.

Previously, PEI has been used to detect and capture CO227,28,4042. This is because CO2 reacts with the primary and secondary amines of PEI readily to form carbamates that can be stabilized by other primary amines or with water and create bicarbonate ions29. When PEI is mixed with PEO and supported onto mesoporous oxides, PEI is a powerful adsorbent of CO243,44. However, few studies have evaluated the adsorption of CO2 onto blended films of PEO and PEI without a mesoporous substrate for the purpose of measurement under indoor air conditions45,46. It must be noted that in these examples of PEO and PEI polymer blend films, that these films were fabricated with graphene-based materials. In our case, without any graphene additives, the PEO-PEI blend enhanced the frequency response and sensitivity of the sensor to CO2 (Fig. 2b, Table S1). Under dry air conditions (i.e., 0% RH) the frequency response of the polymer blend is more than twice that of PEI alone. Additionally, when increasing the background relative humidity level to 10% and then to 80% at a constant temperature, the frequency shift response to CO2 is nearly tripled and then quadrupled, respectively, relative to the resonator functionalized with PEI only. Furthermore, the PEO and PEI blends have shown promising performances in both elevated temperature and elevated humidity conditions, simultaneously (Fig. 2c,d). However, the addition of the hydrophilic PEO chemistry induces an inherent cross-sensitivity to water. Therefore, commercial implementation of this sensing device would require humidity compensation. However, this is a commonly-monitored metric in commercial HVAC systems. Thus, only simple, complementary circuitry would be required to account for the presence of humidity, and this could easily be manufactured within the same device as our sensors.

Sensor selectivity

These sensors showed relative selectivity to CO2 when interfering gases (i.e., distractant gases) were introduced into the chamber (Fig. 3a). Previously, PEI-based materials have shown responses to other analytes47. Therefore, selectivity testing was performed with analytes that could be present in an interior location. Specifically, these tests were performed with a variety of confounding species including propane, carbon monoxide, acetone, ethanol, toluene, and xylene. Though not an exhaustive list, each of these species were carefully selected to cover a broad range of functional chemical groups (i.e., alkyl hydrocarbons, ketones, alcohols, and aromatic hydrocarbon) typically found in interior locations. Each test alternated between 30 min pulses of analyte gases and a nitrogen purge of the test chamber. CO2 and the selected interfering gases were each introduced at concentrations of 1000 ppm for comparison. It should be noted that 1000 ppm is a common CO2 level for indoor environments; however, for the distractants considered, this concentration is well above what is considered safe36. Thus, these distractant gases tested are on the extreme side of what could potentially confound the sensors under practical operating conditions. Tests were performed to show a CO2 pulsed alone, the distractant vapor pulsed alone, CO2 and the distractant pulsed together, and CO2 pulsed with a background distractant level. Testing in this manner allowed for a direct comparison of sensor response to CO2 and the distractant, as well as any interacting effects on the sensor when CO2 and the distractant are presented together. Cross-sensitivity is apparent; however, for all of the distractants tested, the sensor had a distinguishable response to CO2 and a lesser response (if any) to the distractant vapor. Acetone, for example, induced an average shift of 128 Hz during a 30 min pulse, whereas, CO2 induced an average shift of 734 Hz for the same time period (Fig. 3b). Thus, the influence of acetone, at a relatively high concentration for indoor environments, was nearly 6 times less than the sensor’s response to CO2 at the same concentration.

Figure 3.

Figure 3

Sensor response to 1000 ppm pulses of CO2 and various distractants. (a) Frequency shift responses of a sensor in the presence of various interfering gas analytes. (b) Zoomed frequency shift response of a sensor in response to CO2 in the presence of acetone. The time series data shows 30 min pulses of CO2 with a background of nitrogen, followed by pulses of acetone, pulses of CO2 and acetone together, and finally pulses of CO2 with a constant background of acetone.

Polymer film properties impact CO2 detection

The optimal and reliable detection of CO2 using a 3:1 PEO:PEI blend film is due to the ability of the semi-crystalline nature of PEO to disrupt the intermolecular interactions of the hyperbranched PEI. PEI, a polymer with many amine branches, ranging from primary to tertiary amines, is an amorphous material that has a relatively low glass transition temperature (i.e., in our hands, it was – 50 °C for a PEI molecular weight of 25 kg mol−1). Thus, branched PEI at room temperature exists as a viscous liquid due to the strong non-covalent interchain amine interactions and polymer entanglements48. PEI, when drop cast onto a substrate and dried under vacuum, remains a uniform polymer film with minor surface defects or disruptions (Figure S1a,b) on the PEI surface until another material or polymer is introduced into the PEI casting solution. Therefore, a pristine PEI thin film has difficulty detecting CO2 due to the high viscosity and nanostructural uniformity caused by the hyperbranched amine interchain interactions of a PEI film (Fig. 2b), which can hydrogen bond and become highly entangled with each other. These entangled amines, many of which are primary amines, prevent the ready diffusion of CO2 into the material to interact, which ultimately limits the CO2 uptake and subsequent sensor response.

When PEO is blended in a 3:1 ratio with PEI, surface features and nanoscale disruptions in the blended polymer film were observed (Fig. 4a,b). This surface segregation also occurred to a lesser degree in the 1:1 PEO:PEI blend film (Figure S1c,d). These defects and disruptions in the PEI film are indicative of altering macromolecular interactions when PEO is incorporated into a PEI matrix. This macromolecular rearrangement promotes CO2 adsorption because CO2 can now diffuse into the PEI material and interact readily with accessible primary and secondary amines which were not accessible prior to the addition of PEO. Moreover, when incorporating the PEO into the PEI matrix there was an observed crystal structure as seen in X-ray diffraction (XRD) (Fig. 4c) with characteristics reflections at q = 1.3 Å−1 and q = 1.65 Å−1, which is consistent with the monoclinic crystal structure of PEO49,50.

Figure 4.

Figure 4

(a) SEM images of a 3:1 PEO:PEI blend film. Both images shown are of the same film but in different sections and locations. (b) AFM images of a 3:1 PEO:PEI blend films. (c) XRD patterns of PEO, 3:1 PEO:PEI blend, 2.5:1.5 PEO:PEI blend, 1:1 PEO:PEI blend, 1:3 PEO:PEI blend, and PEI only films. (d) DMA of a 2.5:1.5 PEO:PEI blend, 3:1 PEO:PEI blend, and PEO-only films.

When PEO is added to the amorphous PEI, PEO tries to maintain order, and this ordering of PEO disrupts the PEI entanglements. In turn, this reduces the side chain amines from interacting with other interchain amines. As a result, there is polymer phase separation and surface morphology alterations in the film. When these alterations occur, CO2 was transported into the PEI matrix in a more robust manner such that larger uptake occurred. Thus, as seen in a 0% relative humidity environment, the PEO:PEI blended film can interact better with CO2 than PEI alone (Fig. 2b). This surface morphology alteration agrees with previous work with similar blends when the PEO molecules physically shielded the PEI chains from one another to reduce individual PEI-PEI chain interactions43. This PEO-induced physical disruption of interchain PEI amines from one another is in direct agreement that intrachain CO2 adsorption events (i.e., rather than interchain) are a result of the PEO causing less PEI branched amine interchain interactions resulting in less diffusional limitations and more reactivity between CO2 and primary and secondary amines.

Furthermore, dynamic mechanical analysis (DMA) showed that a pure PEO film has a decreased tan δ maximum value of 0.28 in comparison to films containing amorphous PEI. This increased storage modulus in PEO reinforces our observations in the XRD data showing that PEO maintains an ordered structure (Fig. 4d). Unlike PEI, which behaves as a highly viscous liquid with many entangled amines, PEO has a low tan δ due to a larger storage modulus due to the crystalline order in the material. When PEO is added into the PEI material, at 2.5:1.5 and 3:1 PEO:PEI blend films the tan δ maximum was 0.32. As the ratio of PEO to PEI increases, the tan δ signal decreased due to the physical disruptions of PEO solvating and shielding branched PEI amines as PEO tries to maintain its crystal structure. As a result, this orders the polymer matrix, creates less amine entanglements, and increased the storage modulus in the blended material. This ordering of the PEI by PEO at the 3:1 PEO:PEI ratio produces a tan δ maximum in the material capable of interacting with CO2. More specifically, this tan δ maximum caused by the PEO allows for less amine entanglements which causes more surface area for CO2 to adsorb into the material to interact with PEI. Thus, more CO2 can interact with PEI intrachain amines and yield a better response on the sensor device.

The hydrophilic properties of PEO further enhance CO2 detection

In addition to providing structural changes in the PEI matrix, PEO facilitates water uptake into the polymer matrix, and this allows for more reversible acid–base reactions to occur between the PEI amines and CO2. When the 3:1 and 1:1 PEO:PEI blend films were exposed to a humid environment and had their Fourier Transform Infrared Spectroscopy (FTIR) spectra acquired, there was observed water uptake into the blend films (Figure S2). This water uptake in the 3:1 PEO:PEI films is important when detecting CO2 because these films showed a frequency shift response to CO2 that was significantly enhanced relative to the resonator functionalized with PEI only (Fig. 2b–d). PEI is a highly branched polymer with primary, secondary and tertiary amino groups, and these different chemical environments interact with CO2 in distinct manners51,52. That is, primary and secondary amino groups can directly react with CO2 to form carbamate groups by a reversible acid–base reaction. More specifically, direct nucleophilic attack on a free CO2 by a primary or secondary amine forms a zwitterion, which rapidly rearranges to carbamic acid via intramolecular proton transfer. In the presence of another free amine, which now acts as a Brønsted base, the carbamic acid may be converted into a carbamate via intermolecular proton transfer. Thus, these carbamates are stabilized by another amine that becomes protonated to form an ammonium ion. Under dry conditions the reaction stops here; however, the availability of water can further convert the carbamate into stable bicarbonate (Fig. 5). As a result, this frees an amine that then can react with more available CO2 gas. Tertiary amines do not directly react with CO2 without water. However, there is the possibility that water and CO2 can form carbonic acid which can be deprotonated by all of the types of substituted amines to form bicarbonate as well. In this alternative route, carbonic acid groups are typically deprotonated at neutral pH by a single amine (i.e., any substitution) instead of multiple amines. Due to a single amine being involved in the deprotonation on the carbonic acid this allows for another amine to be available to attack other carbonic acids that may be present. Regardless of which route is occurring (i.e., direct CO2 attack or deprotonation of carbonic acid), water does have a major impact on how the polymer matrix can interact with CO2. Therefore, PEO in addition to providing order to the PEI and increasing the accessibility of the amines to reversibly react with CO2 also increases the abundance of water in the polymer matrix when under humid conditions, and this increases the adsorption capacity of CO2 in the blended film.

Figure 5.

Figure 5

Proposed mechanisms of CO2 capture by PEI with and without the prescence of water. The intermediate step indicated in red is the key step in this reaction process. Without the presence of water the reaction does not proceed and the amine does not become accessible. With the presence of water the reaction can proceed forward due to a free amine which can capture more CO2.

Discussion

We have presented a resonant mass sensor treated with a polymer blend of PEO and PEI for the sensitive and selective detection of CO2. The synergetic blending of PEO and PEI provided an enhanced materials platform for reversible sorption of CO2. This, combined with a MEMS-based resonant mass sensing platform, created an exceptional sensor for indoor CO2 monitoring. The small size and low power requirement of these sensors provides the necessary qualifications for wireless and distributed sensing in buildings5355. Further, the readily accessible materials used to manufacture this sensor renders a device that is easy to procure at a low cost. Thus, this unique combination of well-known materials allows for a novel CO2 sensor that can be seamlessly integrated into smart building environments.

Experimental methods

Materials

All of the chemicals were purchased from Sigma-Aldrich, and they were used as received unless otherwise noted. The PEI utilized had a reported a weight average molecular weight of 25 kg mol−1. The PEO utilized was purchased from Alfa Aesar, and it had a reported weight average molecular weight of 100 kg mol−1. The methanol utilized to prepare the polymer samples was anhydrous grade and stored under nitrogen. Polished silicon dioxide substrates utilized for imaging were purchased from Silicon Valley Microelectronics.

General methods

A Veeco Dimension 3100 Atomic Force Microscope (AFM) in tapping mode was utilized for AFM imaging. For these images, the polymer samples were fabricated by depositing 1.0 μL of a 1 mg mL−1 polymer blend in methanol on a polished silicon dioxide substrate. Then, the sample wafers were dried under vacuum (P ≤ 0.4 Torr) overnight to remove solvent. The images for the 3:1 PEO:PEI, 1:1 PEO:PEI, PEO-only, and PEI-only films were acquired using this protocol. A Hitachi S-4800 Field Emission scanning electron microscope (SEM) was utilized to image the PEO:PEI. For these images, 1.0 μL of a 1 mg mL−1 polymer blend in methanol solution were drop cast on polished silicon dioxide substrates and dried overnight under vacuum. All of the polymer films were then coated with 20 nm of conducting carbon using a SPI carbon sputter coater prior to imaging. The images for the 3:1 PEO:PEI, 1:1 PEO:PEI, PEO-only, and PEI-only films were acquired using this protocol. X-Ray diffraction (XRD) measurements were measured with a Rigaku Cu-Kα source (λ = 1.54056 Å) in parallel beam mode. These samples were acquired while under ambient conditions. The polymer film samples were fabricated using a 240 mg mL−1 solution of the polymer blend (by weight ratio) in methanol pipetted into a metal mold and then annealed at 80 °C while being pressed for at least 10 min. After pressing, these films were dried overnight under vacuum (P ≤ 0.4 Torr) prior to XRD analysis being performed. A Thermo-Nicolet Nexus Fourier Transform Infrared Spectroscopy (FTIR) with a KBr beam splitter with a 800 cm−1–4500 cm−1 spectra range was utilized for FTIR analysis of the PEO:PEI polymer films. The polymer films were fabricated utilizing the same protocol as discussed for XRD analysis. For DMA testing of the polymer films, a TA Instruments DMA Q800 with a film tension clamp was utilized. These experiments were conducted at a temperature ramp of 0.5 °C min−1 and at a constant frequency of 1 Hz. The polymer films were fabricated utilizing the same general protocol as discussed for XRD analysis.

Device testing

The testing protocols utilized in this work are similar to those previously reported23,46,56. Testing of the devices was performed using the experimental setup shown in Fig. 6a. Gas tanks of nitrogen, air, and carbon dioxide were connected to a series of mass flow controllers (MFC; MKS, 1179C) in parallel. A subset of nitrogen-supplied MFCs was connected to bubblers (ChemGlass, AF-0085) for introducing humidity or select vapor distractants (i.e., acetone, ethanol, toluene, and xylene). The gas lines converged to a mixing manifold, the output of which was connected directly to the test chamber inlet. A 95 mm diameter and 23 mm in height cylindrical aluminum testing chamber was used for evaluating the sensors. A 6.4 mm gas inlet port was centrally-located on the top of the test chamber and two 6.4 mm exhaust ports were located on opposite sides of the test chamber. The small chamber volume allowed for complete gas exchange in less than 1 min, facilitating quick sensor responses upon changing MFC flow rates.

Figure 6.

Figure 6

(a) Schematic of the gas distribution system used for sensor testing. Mass flow controllers (MFCs) modulated supply gases to the test chamber containing functionalized oscillators. Bubblers connected to a MFC were used to moderate distractant analytes and humidity levels inside the testing chamber. A frequency counter, executed on a MyRIO FPGA monitored the frequency of each oscillator in parallel. (b) A schematic of the Pierce oscillator used. The resonant element, outlined by the red box, is shown on the left of the circuit diagram. The remainder of the oscillator circuit, which is contained on the instrumentation board, is outlined by the blue box. This portion of the diagram contains two load capacitors (C1 and C2), a feedback resistor (R1), and an isolation resistor (R2). A series of inverters between the supply voltage (Vcc) and the output voltage (Vout) are used to square-off the oscillator output signal to facilitate frequency counting. (c) A single packaged resonant element shown on a US quarter for scale. (d) An exposed quartz crystal resonant element. (e) A resonant mass sensing system with 16 Pierce oscillators. A resonator board (left) containing 16 resonant elements is shown offset from the instrumentation board (right) which completes the Pierce oscillator circuit.

Prior to sensor testing, the resonator board was attached to the instrumentation board. The test chamber was flushed with nitrogen or air to create an inert environment as the baseline for experimentation. Subsequently, the analyte gases were injected into the chamber to achieve the reported concentrations. A frequency counter was developed in LabVIEW to monitor the oscillation frequency of each oscillator with a 1 Hz resolution. To facilitate parallel monitoring, the frequency counter was synthesized and executed on an NI myRio Field Programmable Gate Array (FPGA). An FPGA consists of a collection of logic elements between which electrical paths can be created and allows for parallel computing. Thus, each of the 16 frequency counting loops could run simultaneously.

Device instrumentation

The device instrumentation utilized in this work was previously reported23,56. An array of 16 Pierce oscillators was used as the sensing platform. Figure 6b shows the Pierce oscillator circuit, which consisted of an inverter, two load capacitors (C1 = 22 pF and C2 = 22 pF), one feedback resistor (R1 = 2 MΩ), one isolation resistor (R2 = 510 Ω), and a 16 MHz quartz crystal resonator (Kyocera Corp., CX3225). The crystal oscillator driver (Texas Instruments, SN74LVC1GX04) provided the circuit with the Pierce oscillator inverter as well as three additional inverters, which effectively squared the oscillator output signal. The hardware implementation of the oscillator circuit resulted in two printed circuit boards: (i) a board containing only an array of resonators and (ii) an instrumentation board containing the 16 sets of oscillator electronics with spring pin connectors in place of the resonators (Fig. 6e). As such, the resonator boards could be functionalized independent of the rest of the oscillator circuit and easily interchanged without incurring high component costs.

A single crystal resonator has a small footprint (8 mm2) and low power requirement (< 200 μW) during operation. Figure 6c shows a single packaged crystal resonator on top of a United States quarter, for scale. The small size and low power requirement of a single resonant sensor is particularly promising when considering wireless and distributed sensing in buildings5355. The resonant element of the Kyocera CX3225 is shown in Fig. 6d, after the package cap has been removed. Functional materials were applied directly to this exposed element.

Device functionalization

PEI and PEO were dissolved in methanol to generate a solution of 0.1% (by volume) of PEI and 0.3% (by volume) of PEO. Then, 1 μL of this solution was deposited onto each resonator. The resonator board was then placed under vacuum at 70 °C for 12 h to remove any residual methanol leaving behind a 3:1 PEO:PEI blend film (by weight). Unless otherwise specified, the devices utilized in the tests were all functionalized with the 3:1 PEO:PEI (by weight). Prior to testing, the resonator board was allowed to equilibrate back to room temperature.

Supplementary Information

Acknowledgements

The information, data, or work presented herein was funded in part by the Advanced Research Projects Agency-Energy (ARPA-E), U.S. Department of Energy, under Award Number DE-AR0000943. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof.

Author contributions

Z.A.S. designed, conducted, and analyzed experiments and data for the sensing system. J.N.H. designed, conducted, and analyzed experiments associated with the materials preparation, performance, and characterization. X.Z. assisted in the materials preparation. N.B. designed the oscillator circuit and electronic platform. K.B.M. assisted in materials preparation and conducted DMA analysis experiments. C.F.H. acquired SEM images. W.Z. acquired AFM images. G.T.C., J.E.B., B.W.B., and J.F.R. conceived the project, designed experiments, and directed the research. All of the authors contributed to the writing and editing of the manuscript.

Competing interests

The authors declare no competing interests.

Footnotes

Publisher's note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Contributor Information

Jeffrey F. Rhoads, Email: jfrhoads@purdue.edu

Bryan W. Boudouris, Email: boudouris@purdue.edu

Supplementary Information

The online version contains supplementary material available at 10.1038/s41598-021-92181-4.

References

  • 1.EPA. Report to congress on indoor air quality (Vol. 2; Report No. EPA/400/1–89/001C) (1989).
  • 2.European Comission. Indoor air pollution: new EU research reveals higher risks than previously thought. Eur. Com. IP/03/1278 (2003).
  • 3.Sarigiannis, D. A. Combined or multiple exposure to health stressors in indoor built environments. World Heal. Organ. Rep. Eur. 82 (2014).
  • 4.Persily, A. & Gorfain, J. Analysis of Ventilation Data from the U.S. Environmental Protection Agency Building Assessment Survey and Evaluation (BASE) Study. NIST Interagency/Internal Report (NISTIR) 7145 (2004).
  • 5.Shriram S, Ramamurthy K, Ramakrishnan S. Effect of occupant-induced indoor CO2 concentration and bioeffluents on human physiology using a spirometric test. Build. Environ. 2019;149:58–67. doi: 10.1016/j.buildenv.2018.12.015. [DOI] [Google Scholar]
  • 6.Bhide A, Jagannath B, Tanak A, Willis R, Prasad S. CLIP: Carbon dioxide testing suitable for low power microelectronics and IOT interfaces using room temperature ionic liquid platform. Sci. Rep. 2020;10:2557. doi: 10.1038/s41598-020-59525-y. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 7.Azuma K, Kagi N, Yanagi U, Osawa H. Effects of low-level inhalation exposure to carbon dioxide in indoor environments: A short review on human health and psychomotor performance. Environ. Int. 2018;121:51–56. doi: 10.1016/j.envint.2018.08.059. [DOI] [PubMed] [Google Scholar]
  • 8.Satish U, et al. Is CO2 an indoor pollutant? Direct effects of low-to-moderate CO2 concentrations on human decision-making performance. Environ. Health Perspect. 2012;120:1671–1677. doi: 10.1289/ehp.1104789. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 9.Du, B., Tandoc, M. C., Mack, M. L. & Siegel, J. A. Indoor CO2 concentrations and cognitive function: A critical review. Indoor Air30(6), 1067–1082 (2020). [DOI] [PubMed]
  • 10.Gerlach G, Lambrecht A, Oelßner W. Carbon Dioxide Sensing: Fundamentals, Principles, and Applications, Ch. 3 Analytical Methods for the Detection of Gaseous CO2. Wiley-VCH Verlag GmBH & Co.; 2019. pp. 45–85. [Google Scholar]
  • 11.Murray JN, Doe JB. Gas chromatography method for traces of carbon dioxide in air. Anal. Chem. 1965;37:941–942. doi: 10.1021/ac60226a046. [DOI] [Google Scholar]
  • 12.Qiao S, et al. A sensitive carbon dioxide sensor based on photoacoustic spectroscopy with a fixed wavelength quantum cascade laser. Sensors. 2019;19:4187. doi: 10.3390/s19194187. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 13.Chen C, Ren Q, Wang Y-Z. Review on multi gas detector using infrared spectral absorption technology. Appl. Spectrosc. Rev. 2019;54:425–444. doi: 10.1080/05704928.2018.1474766. [DOI] [Google Scholar]
  • 14.Dinh T-V, Choi I-Y, Son Y-S, Kim J-C. A review on non-dispersive infrared gas sensors: Improvement of sensor detection limit and interference correction. Sens. Actuators B Chem. 2016;231:529–538. doi: 10.1016/j.snb.2016.03.040. [DOI] [Google Scholar]
  • 15.Fisk WJ, Sullivan DP, Faulkner D, Eliseeva E. CO2 Monitoring for Demand Controlled Ventilation in Commercial Buildings. Lawrence Berkeley National Lab LBNL-3279E; 2010. [Google Scholar]
  • 16.Shrestha SS. Performance Evaluation of Carbon-dioxide Sensors used in Building HVAC Applications. Iowa State University; 2009. [Google Scholar]
  • 17.Apte, M. G. A review of demand control ventilation. In Proc.Healthy Buildings, 371–376 (2006).
  • 18.Vincent TA, Gardner JW. A low cost MEMS based NDIR system for the monitoring of carbon dioxide in breath analysis at ppm levels. Sens. Actuators B Chem. 2016;236:954–964. doi: 10.1016/j.snb.2016.04.016. [DOI] [Google Scholar]
  • 19.DeMartini BE, et al. A single input-single output coupled microresonator array for the detection and identification of multiple analytes. Appl. Phys. Lett. 2008;93:2006–2009. doi: 10.1063/1.2964192. [DOI] [Google Scholar]
  • 20.Kumar V, et al. Bifurcation-based mass sensing using piezoelectrically-actuated microcantilevers. Appl. Phys. Lett. 2011;98:153510. doi: 10.1063/1.3574920. [DOI] [Google Scholar]
  • 21.Zribi A, Knobloch A, Tian WC, Goodwin S. Micromachined resonant multiple gas sensor. Sens. Actuators A Phys. 2005;122:31–38. doi: 10.1016/j.sna.2004.12.034. [DOI] [Google Scholar]
  • 22.Adams JD, et al. Nanowatt chemical vapor detection with a self-sensing, piezoelectric microcantilever array. Appl. Phys. Lett. 2003;83:3428–3430. doi: 10.1063/1.1621733. [DOI] [Google Scholar]
  • 23.Siefker, Z. A. et al. A resonant CO2 sensor functionalized with a polymerized ionic liquid. In Proc. IEEE Sensors (2019).
  • 24.Gupta A, Akin D, Bashir R. Detection of bacterial cells and antibodies using surface micromachined thin silicon cantilever resonators. J. Vac. Sci. Technol. B Microelectron. Nanom. Struct. 2004;22:2785–2791. doi: 10.1116/1.1824047. [DOI] [Google Scholar]
  • 25.Gupta A, Akin D, Bashir R. Single virus particle mass detection using microresonators with nanoscale thickness. Appl. Phys. Lett. 2004;84:1976–1978. doi: 10.1063/1.1667011. [DOI] [Google Scholar]
  • 26.Swager TM. Sensor technologies empowered by materials and molecular innovations. Angew. Chem. Int. Ed. 2018;57:4248–4257. doi: 10.1002/anie.201711611. [DOI] [PubMed] [Google Scholar]
  • 27.Xie GZ, et al. QCM sensors based on PEI films for CO2 detection. J. Electron. Sci. Technol. 2015;13:181–187. [Google Scholar]
  • 28.Sun B, Xie G, Jiang Y, Li X. Comparative CO2-sensing characteristic studies of PEI and PEI/starch thin film sensors. Energy Procedia. 2011;12:726–732. doi: 10.1016/j.egypro.2011.10.098. [DOI] [Google Scholar]
  • 29.Meth S, Goeppert A, Prakash GKS, Olah GA. Silica nanoparticles as supports for regenerable CO2 sorbents. Energy Fuels. 2012;26:3082–3090. doi: 10.1021/ef300289k. [DOI] [Google Scholar]
  • 30.Hampe EM, Rudkevich DM. Exploring reversible reactions between CO2 and amines. Tetrahedron. 2003;59:9619–9625. doi: 10.1016/j.tet.2003.09.096. [DOI] [Google Scholar]
  • 31.Ganji M, Docter M, Le Grice SFJ, Abbondanzieri EA. DNA binding proteins explore multiple local configurations during docking via rapid rebinding. Nucleic Acids Res. 2016;44:8376–8384. doi: 10.1093/nar/gkw666. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 32.ASHRAE. ANSI/ASHRAE Standard 62.1–2010 Ventilation for acceptable indoor air quality. (2010).
  • 33.Sauerbrey G. Verwendung von schwingquarzen zur wagung dünner schichten und zur mikrowagung. Zeitschrift fur Phys. 1959;155:206–222. doi: 10.1007/BF01337937. [DOI] [Google Scholar]
  • 34.Martin SJ, Granstaff VE, Frye GC. Characterization of a quartz crystal microbalance with simultaneous mass and liquid loading. Anal. Chem. 1991;63:2272–2281. doi: 10.1021/ac00020a015. [DOI] [Google Scholar]
  • 35.Cui Y, Schubert BA, Jahren AH. A 23 m.y. record of low atmospheric CO2. Geology. 2020;48:888–892. doi: 10.1130/G47681.1. [DOI] [Google Scholar]
  • 36.Occupational Safety and Health Administration, U.S. Dept. of Labor Occupational exposure limits (2019).
  • 37.Rice, S. A. Human health risk assessment of CO2: survivors of acute high-level exposure and population sensitive to prolonged low-level exposure. In Third Annu. Conf. Carbon Sequestration 1–9 (2004).
  • 38.Podoll RT, Irwin KC. Sorption of cationic oligomers on sediments. Environ. Toxicol. Chem. 1988;7:405–415. doi: 10.1002/etc.5620070602. [DOI] [Google Scholar]
  • 39.ASHRAE. ASHRAE/ANSI Standard 55–2010 Thermal environmental conditions for human occupancy. (2010).
  • 40.Wang D, Wang X, Ma X, Fillerup E, Song C. Three-dimensional molecular basket sorbents for CO2 capture: Effects of pore structure of supports and loading level of polyethylenimine. Catal. Today. 2014;233:100–107. doi: 10.1016/j.cattod.2014.01.038. [DOI] [Google Scholar]
  • 41.Li K, Jiang J, Yan F, Tian S, Chen X. The influence of polyethyleneimine type and molecular weight on the CO2 capture performance of PEI-nano silica adsorbents. Appl. Energy. 2014;136:750–755. doi: 10.1016/j.apenergy.2014.09.057. [DOI] [Google Scholar]
  • 42.Zhang W, Liu H, Sun C, Drage TC, Snape CE. Capturing CO2 from ambient air using a polyethyleneimine–silica adsorbent in fluidized beds. Chem. Eng. Sci. 2014;116:306–316. doi: 10.1016/j.ces.2014.05.018. [DOI] [Google Scholar]
  • 43.Sakwa-Novak MA, Tan S, Jones CW. Role of additives in composite PEI/oxide CO2 adsorbents: Enhancement in the amine efficiency of supported PEI by PEG in CO2 capture from simulated ambient air. ACS Appl. Mater. Interfaces. 2015;7:24748–24759. doi: 10.1021/acsami.5b07545. [DOI] [PubMed] [Google Scholar]
  • 44.Wang L, Al-Aufi M, Pacheco CN, Xie L, Rioux RM. Polyethylene glycol (PEG) addition to polyethylenimine (PEI)-impregnated silica increases amine accessibility during CO2 sorption. ACS Sustain. Chem. Eng. 2019;7:14785–14795. doi: 10.1021/acssuschemeng.9b02798. [DOI] [Google Scholar]
  • 45.Son M, et al. Charge transfer in graphene/polymer interfaces for CO2 detection. Nano Res. 2018;11:3529–3536. doi: 10.1007/s12274-017-1857-z. [DOI] [Google Scholar]
  • 46.Siefker, Z. A. et al. A chemiresistive CO2 sensor based on CNT-functional polymer composite films. In Proc. IEEE Sensors (2020).
  • 47.Barauskas D, Pelenis D, Vanagas G, Viržonis D, Baltrušaitis J. Methylated poly(ethylene)imine modified capacitive micromachined ultrasonic transducer for measurements of CO2 and SO2 in their mixtures. Sensors. 2019;19:3236. doi: 10.3390/s19143236. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 48.Kobayashi S, Shirasaka H, Suh K-D, Uyama H. Viscosity behaviors and gel properties of linear and branched polyethylenimines: Effects of micro-structures. Polym. J. 1990;22:442–446. doi: 10.1295/polymj.22.442. [DOI] [Google Scholar]
  • 49.Takahashi Y, Tadokoro H. Structural studies of polyethers, (-(CH2)m-O-)n. X. crystal structure of poly(ethylene oxide) Macromolecules. 1973;6:672–675. doi: 10.1021/ma60035a005. [DOI] [Google Scholar]
  • 50.Yang S, Liu Z, Liu Y, Jiao Y. Effect of molecular weight on conformational changes of PEO: An infrared spectroscopic analysis. J. Mater. Sci. 2015;50:1544–1552. doi: 10.1007/s10853-014-8714-1. [DOI] [Google Scholar]
  • 51.Couchaux G, Barth D, Jacquin M, Faraj A, Grandjean J. Kinetics of carbon dioxide with amines. I. Stopped-flow studies in aqueous solutions. A review. Oil Gas Sci. Technol. 2014;69:865–884. doi: 10.2516/ogst/2013150. [DOI] [Google Scholar]
  • 52.Kortunov PV, Siskin M, Paccagnini M, Thomann H. CO2 reaction mechanisms with hindered alkanolamines: Control and promotion of reaction pathways. Energy Fuels. 2016;30:1223–1236. [Google Scholar]
  • 53.Oikonomou P, et al. A wireless sensing system for monitoring the workplace environment of an industrial installation. Sens. Actuators B Chem. 2016;224:266–274. doi: 10.1016/j.snb.2015.10.043. [DOI] [Google Scholar]
  • 54.Sutton, F. et al. The design of a responsive and energy-efficient event-triggered wireless sensing system. In Proc. 14th Int. Conf. Embed. Wirel. Syst. Networks (EWSN 2017) 144–155 (2017).
  • 55.Gunay B, Shen W. Connected and distributed sensing in buildings: Improving operation and maintenance. IEEE Syst. Man Cybern. 2017;3:27–34. doi: 10.1109/MSMC.2017.2702386. [DOI] [Google Scholar]
  • 56.Hodul JN, et al. Modifying the surface chemistry and nanostructure of carbon nanotubes facilitates the detection of aromatic hydrocarbon gases. ACS Appl. Nano Mater. 2020;3:10389–10398. doi: 10.1021/acsanm.0c02295. [DOI] [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Supplementary Materials


Articles from Scientific Reports are provided here courtesy of Nature Publishing Group

RESOURCES