. 2021 Jan 26;8:101253. doi: 10.1016/j.mex.2021.101253

Modeling of an air-to-air exchanger with dual-core in cascade connection

Haïfa Souifi a,, Yassine Bouslimani a, Mohsen Ghribi a, Serge Colin b
PMCID: PMC8374255  PMID: 34434776

Abstract

With the current leaning towards finding effective solutions to maintain a good indoor air quality (IAQ) inside houses and buildings and to simultaneously reduce the energy consumption, air-to-air exchangers with heat/energy recovery have emerged as one of the promising technologies to provide a healthy and comfortable indoor environment. To deeply evaluate these systems performances, the present investigation focuses on modeling a combined ERV-HRV exchanger using the effectiveness-NTU (εNTU) method. To this end, a detailed mathematical model introducing heat and mass exchange mechanisms was developed and applied to predict the system energy recovery efficiency. To assess its suitability, the developed model was validated and compared to real measurements which carried out under the Atlantic Canada weather. The comparison findings disclosed that the developed model can predict the system performance with a maximum relative discrepancy less than 10%.

• The detailed mathematical model including heat and mass exchange mechanisms was clearly developed using the εNTU approach in order to carefully predict the dual-core system performance in terms of sensible and latent recovery potential.

• The developed model was validated against real data to evaluate its suitability and accuracy. Obtained results show that it could be satisfactory for predicting the dual-core system performances.

• The εNTU approach adopted in this study could be a convenient method for modeling single or/and dual-core air-to-air heat/energy recovery systems.

Keywords: Hybrid-core, Heat/energy recovery, Mathematical model, Effectiveness, Sensible heat transfer, Latent heat transfer

Graphical abstract

Image, graphical abstract


Specifications table

Subject Area Engineering
More specific subject area Mechanical ventilation systems
Method name effectiveness-NTU (i.e.εNTU) method
Name and reference of original method G. Zhou et al., Modeling air-to-air plate-fin heat exchanger without dehumidification, Applied Thermal Engineering 143 (2018) 137-148, https://doi.org/10.1016/j.applthermaleng.2018.07.064
Resource availability There are no special resources.

Method details

Background

According to many research studies [18], ensuring ventilation, via air-to-air heat/energy recovery systems (HRV/ERV) could provide healthy and comfortable indoor environment. By recovering heat/humidity between fresh and exhaust airstreams, HRVs/ERVs are widely adopted to significantly reduce the cooling and heating costs [18]. Thus, these ventilation systems are becoming considerably used worldwide, particularly in cold or humid weather regions [1,2,7,8]. Although several kinds of heat/energy recovery systems are available, the plate-fin type is one of the most promising technologies due to its many benefits including simplicity, low cost, no cross contamination between airstreams, no moving parts, and high efficiency [8], [9]10]. Generally, air-to-air plate-fin heat/energy recovery systems consist of corrugated fins placed between flat plates. The structure is brazed together forming a monolithic block. Without mixing with each other, two airstreams flow along the space between adjacent plates. However, the heat or/and humidity is harvested and transferred between airflows [4,10]. As referred by [1,4,7,10[11], [12], the recovery potential of these air-to-air exchangers can reach up to 94% and 83% of sensible heat and latent heat, respectively. In order to recover more energy, new heat/energy exchangers designs (including core geometries, flow arrangements, materials, etc.) are brought to light and have ceaselessly evolved. In this context, important efforts have been, over the recent years, dedicated to evaluating and enhancing HRVs and ERVs performances [812]. Experimental investigations have been conducted [1,4,8,12] and many researchers have been interested in mathematical modeling using numerical calculation approaches (the effectiveness-NTU (known as εNTU) methods, computational fluid dynamics (CFD), and finite element methods (FEM)), and mainstream simulation platforms as well. In this respect, air-to-air heat/energy exchangers models are extensively developed in the literature to deeply evaluate the systems performances.

In [13], a pioneer modeling method was conducted by Wetter using the εNTU approach. In his research, the author developed an explicit simulation plate-type heat exchangers model to only evaluate the sensible heat transfer efficiency. The research findings indicated that this adopted method ensured a numerical stability coupled with a short computational time. Its main limitation is the use of an empirical correlation relying on a fixed air velocity exponent so as to evaluate the convective heat transfer coefficient [10,14].

Under unsteady flow conditions, Nakonieczny [15] suggested a numerical model of a plate-fin type heat exchanger in which detailed geometric parameters are heavily needed [10]. Furthermore, in order to discretize the unsteady-flow equations, a semi-discrete finite element method was adopted in this study. As consequence, the obtained results revealed that the proposed approach is computationally intensive and subsequently can cause convergence issues [10].

Thanks to Rose et al. [16] and Nielsen et al. [17], quasi-steady-state as well as dynamic models of counter-flow heat exchangers are put forward, respectively using discretization with finite element method (FEM). Apart from the resort to geometric data to evaluate the Reynolds number, the authors assessed, in their models, the dehumidification and frost formation impacts.

In [18], a model for a membrane-based energy recovery ventilator (MERV) with quasi-counter flow configurations was proposed using FLUENT CFD software. Based on humidity, temperature, and pressure non-dimensional values, Zhang considered the resistance of membrane moisture transfer as constant in this developed model. Furthermore, the author intentionally changed the Prandtl number and thermal diffusion values to be similar to Schmidt number and mass diffusion ones, respectively. Consequently, the conjugate problem of mass transfer was converted into a conjugate one of heat transfer.

Another detailed numerical analysis of HRV and MERV with counter/parallel flow arrangements has been carried out by Yaïci et al. [6], under typical winter and summer Canadian weathers. Relying on several assumptions, the authors developed a two-dimensional CFD model which was then validated with data gathered from the literature. Once validated, the proposed model was applied to assess the effect of numerous parameters on the system performances regarding sensible and latent efficiencies. As results, the authors stressed that the CFD approach has been proved to be a practical yet an effective design tool of air-to-air heat/energy recovery systems [6].

Similar investigations about three-dimensional CFD model of MERV were performed by Al-Waked et al. [19,20]. To validate the developed model, the authors resorted to published experimental works. Obtained results from validation pointed out that the proposed CFD model has been reasonably accurate in predicting the MERV performance.

To overcome the limitations of some existing models of air-to-air plate-fin heat exchangers, Zhou et al. [10] shed light on a new mathematical model based on the εNTU approach. Using a set of explicit equations, the recommended model was dedicated to calculating the heat transfer and flow resistance as well. Moreover, the authors highlighted that their model could be applied for various types of air-to-air heat exchangers without taking into account the dehumidification and if only some correlations must respect specific forms [10]. Despite its conspicuously short computational time compared to other models and the no requirement to detailed geometric information of exchanger, the proposed model was intended to be used for dry climatic operating conditions in which it can be only predict sensible heat effectiveness.

More recently, to predict the MERV performances regarding the energy exchange effectiveness, Qiu et al. [14] proposed a new approach which is based on two models: the cross-flow MERV efficiency numerical calculation model relying on the εNTU method and the multivariate polynomial regression model. A comparative analysis with existing numerical calculation methods revealed that the suggested approach did not need detailed core geometric data, was computationally more efficient and could be a promise tool in several engineering applications.

As for the use of mainstream simulation platforms, a wide range of research study has been a spate of interest in modeling air-to-air heat/energy recovery systems using TESS Library [21], TRNSYS 17 Library [22], Modelica Library [23], and so on. Nevertheless, using a fixed heat transfer coefficient, using a constant heat efficiency without taking into consideration the effects of changing conditions on heat transfer, etc. still represent their main limitations [10].

Modeling a single core HRVs and ERVs was extensively tackled in previous works as well as the adopted methods to evaluate their performances. In the current study, a modeling approach for a dual-core exchanger was proposed and an experimental validation was presented. In this regard, an appropriate and an accurate mathematical model for a hybrid dual-core exchanger (ERV-HRV in cascade connection), known as Hybrid 120, was developed in order to evaluate its energy recovery potential. Relying on the εNTU approach, a heat and mass transfer models are clearly presented for a thorough evaluation. Finally, the developed model validation was performed through a comparison between simulation results and real data gathered from laboratory environment experiments.

Mathematical model development

Manufactured by the ClairiTech Innovations company, the air-to-air total heat exchanger used in this study consists of a hybrid dual-core (ERV-HRV), three filters and three fans. Installed in cascade connection (Fig. 1), both the ERV and HRV cores have cross-flow plate-fin structures. Apart from the indoor air quality (IAQ) improvement and the moisture control, this ventilation system, which was dedicated to residential sector applications, recovers latent and sensible heat.

Fig. 1.

Fig 1

Hybrid dual-core system (ERV-HRV).

As depicted in Fig. 1, the indoor air along with toxins are continually exhausted to outdoor via the ERV core. While, the HRV core, which was reserved only to crawlspaces or/and basements, serves to raise the downstairs temperature by recirculating the warm air from the upstairs. Further, the fresh air was simultaneously treated twice through the ERV and HRV cores before its injection to the habitation.

As aforementioned, the intended investigation aims to develop an adequate model of the combined ventilation system illustrated in Fig. 1. To this end, two mathematical heat and mass transfer models are clearly presented relying on the εNTU method.

Sensible and latent efficiencies determination

Commonly, three indicators are used to specify the total energy recovery potentials of the dual-core exchanger: Sensible efficiency εs, latent efficiency εl, and enthalpy efficiency εh known as total exchange efficiency [5,10,14]. Mathematically speaking, these indicators are respectively given as:

εs=Q˙sQ˙s_max (1)
εL=Q˙LQ˙L_max (2)
εT=Q˙TQ˙T_max (3)

Where: Q˙s,Q˙L and Q˙T are respectively the actual rates of sensible, latent and enthalpy heat transfer which are represented by [5,6,14]:

Q˙s=m˙1cp1|T1,outT1,in|=m˙2cp2|T2,inT2,out| (4)
Q˙L=m˙1lfg1|w1,outw1,in|=m˙2lfg2|w2,inw2,out| (5)
Q˙T=Q˙s+Q˙L=m˙1|h1,outh1,in|=m˙2|h2,inh2,out| (6)

Where: T1,in,T1,out represent the inlet and outlet temperatures of incoming fresh air, respectively;w1,in,w1,out are the inlet and outlet humidity ratios of incoming fresh air, respectively; h1,in,h1,out represent the inlet and outlet specific enthalpies of incoming fresh air respectively; T2,in T2,out represent the temperatures of stale air and exhaust air respectively; w2,in w2,out represent the humidity ratios of the stale air and exhaust air respectively; h2,in,h2,out are respectively the specific enthalpies of the stale air and exhaust air; m˙1,m˙2 represent the mass flow rates of incoming fresh air and exhaust air respectively; cp1,cp2 are the specific heat capacities of inlet and outlet fresh air respectively; and lfg is the water vaporization's specific latent heat.

Further, the maximum possible rates of sensible, latent and enthalpy heat transfer can be respectively expressed by Eqs. (7)(9) [6,10]:

Q˙s_max=C˙min|T2,inT1,in| (7)
Q˙L_max=G˙min|w2,inw1,in| (8)
Q˙T_max=m˙min|h2,inh1,in| (9)

Where: m˙min, G˙min and C˙min represent the minimum value of mass flow, latent flow, and thermal capacity flow rates between exhaust and fresh airstreams which are respectively given as:

m˙min=min{m˙1,m˙2} (10)
G˙min=min{m˙1lfg1,m˙2lfg2} (11)
C˙min=min{m˙1cp1,m˙2cp2} (12)

Moreover, to calculate the humid air's specific enthalpy, Eq. (7) was used [5]:

hi,in/out=cpiTi,in/out+(2501+cpmTi,in/out)wi,in/out (13)

Where: Cpm represents the specific heat capacity at a constant pressure.

By substituting Eqs. (4) and (7) into Eq (1), the sensible heat recovery efficiency εs can be written as:

εs=m˙1cp1|T1,inT1,out|C˙min|T1,inT2,in| (14)

Similarly, the latent heat recovery efficiency εl can be expressed by rearranging Eqs. (5), (8) and (2):

εL=m˙1lfg1|w1,inw1,out|G˙min|w1,inw2,in| (15)

As for the total heat recovery efficiency εT, it can be given by substituting Eqs. (6) and (9) into Eq (3):

εT=m˙1|h1,inh1,out|m˙min|h1,inh2,in| (16)

For balanced airflows, the sensible, latent and enthalpy efficiencies can be written respectively as follows [5,14]:

εs=|T1,inT1,out||T1,inT2,in| (17)
εL=|w1,inw1,out||w1,inw2,in| (18)
εT=|h1,inh1,out||h1,inh2,in| (19)

As reported by [5,14], the enthalpy efficiency can be further given by combining Eqs. (13) and (19):

εT=CS×εS+CL×εL (20)

Where: CS and CL referred to as weighted coefficients which expressed respectively by Eqs. (21)(22):

CS=AA+B (21)
CL=BA+B (22)

Where: A=1.005max(w1,in,w2,in)min(w1,in,w2,in) and B=2501max(T1,in,T2,in)min(T1,in,T2,in)

Heat and mass transfer evaluation

To theoretically evaluate and predict the dual-core exchanger performances, simulations of both sensible and latent heat exchange in the combined system are crucial. To this end, two mathematical models of heat and mass transfer are then presented based on εNTU approach.

In the present study, some assumptions are considered as following: (1) No heat loss and no airflows leakage are considered, (2) The fouling and the material's thermal resistance are neglected; (3) The air properties are approximately evaluated; (4) The membrane resistance for heat conduction is neglected.

Heat transfer model

By referring to the εNTU approach adopted by Zhou et al. [10], the general form of sensible heat exchange efficiency of the unmixed cross-flow dual-core ventilation system can be represented by Eq. (23) [7,10]:

εs=1exp{NTUs0.22Rc,s[exp(Rc,sNTUs0.78)1]} (23)

Where: NTU and Rc represent the number of heat transfer units and capacity rate ratio, respectively. These dimensionless parameters are given as [7,10]:

NTUs=AUsC˙min (24)
Rc,s=C˙minC˙max (25)

Where: Us and A are the overall heat transfer coefficient and total surface of heat exchange, respectively; and C˙max represents the maximum value of thermal capacity flow rate between exhaust and fresh airstreams which is expressed as follows:

C˙max=max{m˙1cp1,m˙2cp2} (26)

As for the overall heat transfer coefficient Us, its general form is represented by [14,25]:

Us1=1hs+δλm+1fs+1fe+1he (27)

Where: he and hs represent the convective heat transfer coefficients of exhaust and supply airstreams, respectively; fe and fs are the fouling coefficients of exhaust and supply airflows, respectively; and δ and λm are the core membrane thickness and thermal conductivity, respectively.

By neglecting the membrane resistance for heat conduction, the overall heat transfer coefficient can be further expressed by Eq (28):

Us1=1hs+1he (28)

Commonly, the evaluation of convective heat transfer coefficients of exhaust and supply airstreams depends on the calculation of several parameters. In this respect, a set of mathematical correlations including, Reynolds, Prandtl and Nusselt numbers are extensively highlighted based on simulations and experiments [3,10,25].

Regarding the Reynolds number, it is expressed by Eq. (29). While Eq (30) represents the Prandtl number:

Rei=ViDhρair,iμair,i (29)
Pri=Cp,iμair,iλair,i (30)

Where: i is an index which denotes the exhaust and supply airflows (e: exhaust and s: supply); μair,ρair, and λair represent the, dynamic viscosity, density and thermal conductivity of the air, respectively; V represents the velocity of air flow, and Dh is the hydraulic diameter which is expressed as follows [3,10]:

Dh=4SP=2×a×La+L2×a (31)

Where: S and P are the cross-sectional surface and wetted perimeter, respectively; L and a are respectively the core width and space between adjacent plates.

Moreover, in order to calculate the Nusselt number, the correlation referred by Zhou et al. [10] was adopted in this investigation. To this end, the heat transfer Colburn factor correlation is given as:

j=c1c2Rem (32)

Where: c1 is a constant real number, c2 represents a constant which absolutely depends on the geometry of the heat/energy cores, and m is the Reynolds number's exponent.

The above relation may be further expressed as [10]:

j=NuRePr1/3 (33)

Therefore, the Nusselt number was calculated by Eq. (34) which lead subsequently to calculate the convective heat transfer coefficients using Eq. (35) [10]:

Nu=c1c2Rem+1Pr1/3 (34)
hi=Nuiλair,iDh (35)

Once the above parameters are calculated, the overall heat transfer coefficient Us as well as the sensible heat efficiency εs are respectively calculated using Eqs. (28) and (23).

Hence, the temperatures of supply and exhaust airstreams can be predicted based on Eq. (36) and Eq. (37), respectively [10]:

T1,out=T1,in+εsC˙minm˙1cp1(T2,inT1,in) (36)
T2,out=T2,inQ˙sm˙2cp2 (37)

Mass transfer model

On the other hand, a mass transfer model is equally important to be developed to properly assess the total heat recovery potentials of the system. In this respect, the present study referred to the heat and mass transfer analogy.

According to the adopted εNTU approach, the latent heat efficiency can be written as:

εl=1exp{NTUl0.22Rc,l[exp(Rc,lNTUl0.78)1]} (38)
NTUl=AUlm˙min (39)
Rc,l=m˙minm˙max (40)

Where: m˙max represents the maximum value of mass flow rates between exhaust and supply airstreams.

m˙max=max{m˙1,m˙2} (41)

Analogously to heat exchange, the overall moisture transfer coefficient Ul can be represented as follows [3], [7], [12], [24], [25]:

Ul1=1kmass,s+rmm+1kmass,e (42)

Where: kmass,e and kmass,s represent the convective mass transfer coefficients of exhaust and supply airstreams, respectively; and rmm is the plate's moisture resistance.

As pointed out by research studies [3,7,25], the calculation of this resistance is rather complicated, and it strongly depends on the membrane properties and operating conditions as well. In this investigation, the plate's moisture resistance calculation was performed based on a mathematical relation adopted by [3] which is given as:

rmm=δDwp (43)

Where: Dwp represents the mass diffusivity.

Regarding the convective mass transfer coefficients calculation, it is generally carried out using Sherwood correlations. Relying on the Chilton-Colburn analogy, the Sherwood number is given as [7,12,25]:

Shi=Nui.Le1/3 (44)

Where: Le denotes the Lewis number which varies from 1.19 to 1.22 under atmospheric conditions [7,25].

The above formula may be further written as [5,12,25]:

Shi=kmass,iDhDva (45)

Where: Dva represents the vapor diffusivity in the air.

Furthermore, the convective mass transfer coefficients can be expressed by rearranging Eqs. (35), (45) and (44):

kmass,i=hiCpiLe1/3 (46)

It is obvious that the convective mass transfer coefficients calculation leads to the calculation of the overall moisture transfer coefficient Ul (Eq. (42)), and latent heat efficiency εl as well (Eq. (38)).

Finally, the humidity ratios of supply air and exhaust air can be predicted based on Eqs. (47) and (48), respectively:

w1,out=w1,in+εlG˙minm˙1lfg1(w2,inw1,in) (47)
w2,out=w2,inQ˙lm˙2lfg2 (48)

Method validation

The suitability of the developed model in predicting the combined system recovery performances was furthered, in this present study, by its validation against real data gathered from laboratory environment experiments. In this respect, the simulation results of sensible and latent heat efficiencies are compared with experimental measurements.

It is worthy to note that the dual-core exchanger was set up and its operating modes are monitored over three weeks in March 2019 in a laboratory environment at the University of Moncton. As for the model validation, collected measured data for March 7, 2019 are used. The real outside temperature was varied between −10°C and −18.6°C and the relative humidity range was between 40% and 77%, during this day. The combined ERV-HRV system was operated on low-speed mode where the air flow rates remained at 43.64 - 46.64 L/s and are closely balanced.

The hybrid dual-core system geometry characteristics used to perform simulations are presented in Fig. 2 and Table 1.

Fig. 2.

Fig 2

Cross-flow ERV and HRV structures.

Table 1.

Combine ERV-HRV system geometrical specifications.

Parameters ERV core HRV core
Channels number for each flow: N 46 46
Duct height: 2a 3.8 mm 3.8 mm
Duct width: 2b 5 mm 5 mm
Core width: W 240 mm 94 mm
Core length: L 240 mm 240 mm
Core height: H 315 mm 340 mm

So as to clearly validate the developed model, the temperatures and air humidity ratios of supply and exhaust airstreams are predicted for a set of given variable inputs. Figs. 35 show the comparison between results obtained from simulation and experiment in which the consistency between them is, generally, hard to be ensured. Commonly, owing to systematic as well as random errors of equipment used in experiments to measure and collect data which are subsequently used as inputs to validate the developed mathematical model.

Fig. 3.

Fig 3

Comparison between simulation and experimental results of supply air and exhaust air temperatures.

Fig. 5.

Fig 5

Comparison between simulation and experimental results of sensible, latent and total heat efficiencies.

As a rough rule of thumb, a discrepancy between simulation and experimental results was always obtained.

In this investigation, results agreement between measurements and simulation results was evaluated based on a relative discrepancy given as [10]:

error=|ValueexpValuesim|Valueexp×100 (49)

Where: Valuesim and Valueexp represent results obtained from simulation and experiment, respectively.

Figs. 3 and 4 depict the comparison between theoretical and experimental results of supply air and exhaust air temperatures and humidity ratios, respectively.

Fig. 4.

Fig 4

Comparison between simulation and experimental results of supply air and exhaust air humidity ratios.

As shown in Fig. 3, it is obvious that results obtained from simulations have a good agreement with experimental ones within maximum relative discrepancies of 9.9 % and 9.2 % for the supply air and exhaust air temperatures, respectively. Regarding the humidity ratios of supply and exhaust airstreams, reasonable agreements are noticed within maximum relative discrepancies of 5.67 % and 10.07 % between simulation and experimental results (Fig. 4).

As for the theoretical developed model predictions and experimental results of sensible, latent and total heat efficiencies, they are illustrated in Fig. 5. The mathematical model predicted that the maximum values of sensible, latent and total heat recovery efficiencies are around 70 %, 44 %, and 62 %, respectively. Under the same circumstance, the experimental results pointed out that the corresponding effectiveness are around 75.56%, 48.38 %, and 68.66 %. Therefore, reasonable agreements, within maximum relative discrepancies of 7.95%, 9.94 % and 8.53 %, are obviously observed.

Conclusion

In this paper, an air-to-air dual-core exchanger was analyzed for a thorough prediction and assessment of its performance. To this end, a detailed mathematical model including heat and mass exchange mechanisms was clearly developed using the εNTU approach in order to carefully predict the ventilation system sensible and latent recovery efficiencies. Furthermore, the developed model was validated against real data to evaluate its suitability and accuracy. To sum up, the results disclosed that the developed mathematical model can be satisfactory for predicting the dual-core system performances in a conspicuously short time. A maximum relative discrepancy less than 10% was obtained between theoretical and experimental results which have a very good agreement. Therefore, the εNTU approach adopted in this study could be a convenient method for modeling air-to-air heat/energy recovery systems.

Declaration of Competing Interest

The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.

Acknowledgments

The authors would like to deeply thank the New Brunswick Innovation Foundation (FINB) for their support for this work.

References

  • 1.Beattie C. Experimental study of air-to-air heat exchangers for use in arctic housing. Appl. Thermal Eng. 2018;129:1281–1291. doi: 10.1016/j.applthermaleng.2017.10.112. [DOI] [Google Scholar]
  • 2.Li B. Performance of a heat recovery ventilator coupled with an air to air heat pump for residential suites in Canadian cities. J. Build. Eng. 2019;21:343–354. doi: 10.1016/j.jobe.2018.10.025. [DOI] [Google Scholar]
  • 3.Liu P. A theoretical model to predict frosting limits in cross-flow air-to-air flat plate heat/energy exchangers. Energy Build. 2016;110:404–414. doi: 10.1016/j.enbuild.2015.11.007. [DOI] [Google Scholar]
  • 4.Al-Zubaydi A.T., Hong G. Experimental investigation of counter flow heat exchangers for energy recovery ventilation in cooling mode. Int. J. Refrig. 2018;93:132–143. doi: 10.1016/j.ijrefrig.2018.07.008. [DOI] [Google Scholar]
  • 5.Liu J. Efficiency of energy recovery ventilator with various weathers and its energy saving performance in a residential apartment. Energy Build. 2010;42:43–49. doi: 10.1016/j.enbuild.2009.07.009. [DOI] [Google Scholar]
  • 6.Yaïci W. Numerical analysis of heat and energy recovery ventilators performance based on CDF for detailed design. Appl. Therm. Eng. 2013;51:770–780. doi: 10.1016/j.applthermaleng.2012.10.003. [DOI] [Google Scholar]
  • 7.Liu P. Performance of a quasi-counter-flow air-to-air membrane energy exchanger in cold climates. Energy Build. 2016;119:129–142. doi: 10.1016/j.enbuild.2016.03.010. [DOI] [Google Scholar]
  • 8.Souifi H. Experimental investigation and modeling of a dual-core air-to-air exchanger. Energy Build. 2020 doi: 10.1016/j.enbuild.2020.110600. [DOI] [Google Scholar]
  • 9.Al-Waked R. Enhancing the performance of energy recovery ventilators. Energy Convers. Manag. 2018;171:196–210. doi: 10.1016/j.enconman.2018.05.105. [DOI] [Google Scholar]
  • 10.Zhou G. Modeling air-to-air plate-fin heat exchanger without dehumidification. Appl. Therm. Eng. 2018;143:137–148. doi: 10.1016/j.applthermaleng.2018.07.064. [DOI] [Google Scholar]
  • 11.Nassif M.S. University of New South Wales; Sydney, Australia: 2008. Analysis and Modelling of Membrane Heat Exchanger in HVAC Energy Recovery Systems. Thesis. [Google Scholar]
  • 12.Zhang J., Fung A.S. Experimental study and analysis of an energy recovery ventilator and the impacts of defrost cycle. Energy Build. 2015;87:265–271. doi: 10.1016/j.enbuild.2014.11.050. [DOI] [Google Scholar]
  • 13.M. Wetter, Simulation model air-to-air plate heat exchanger, Office of Scientific & Technical Information Technical Reports 13 (32) (1999).
  • 14.Qiu Sh. An energy exchange efficiency prediction approach based on multivariate polynomial regression for membrane-based air-to-air energy recovery ventilator core. Build. Environ. 2019;149:490–500. doi: 10.1016/j.buildenv.2018.12.052. [DOI] [Google Scholar]
  • 15.Nakonieczny K. Numerical modeling of cross-flow plate-fin air-to-air heat exchanger under unsteady flow conditions. Numer. Heat Trans. 2006;49:1–24. doi: 10.1080/10407780500302265. [DOI] [Google Scholar]
  • 16.Rose J. Quasi-steady-state model of a counter flow air-to-air heat-exchanger with phase change. Appl. Energy. 2008;85:312–325. doi: 10.1016/j.apenergy.2007.07.009. [DOI] [Google Scholar]
  • 17.Nielsen T. Dynamic model of counter flow air to air heat exchanger for comfort ventilation with condensation and frost formation. Appl. Therm. Eng. 2009;29:462–468. doi: 10.1016/j.applthermaleng.2008.03.006. [DOI] [Google Scholar]
  • 18.Zhang L.Z. Heat and mass transfer in a quasi-counter flow membrane-based total heat exchanger. Int. J. Heat Mass Trans. 2010;53:5478–5486. doi: 10.1016/j.ijheatmasstransfer.2010.07.009. [DOI] [Google Scholar]
  • 19.Al-Waked R. CFD simulation of air to air enthalpy heat exchanger. Energy Convers. Manage. 2013;74:377–385. doi: 10.1016/j.enconman.2013.05.038. [DOI] [Google Scholar]
  • 20.Al-Waked R. CFD simulation of air to air enthalpy heat exchanger: variable membrane moisture resistance. Appl. Therm. Eng. 2015;84:301–309. doi: 10.1016/j.applthermaleng.2015.03.067. [DOI] [Google Scholar]
  • 21.J. Thornton et al., TESSLibs 17 HVAC Library Mathematical Reference, Thermal Energy System Specialists (2014), Madison, Wisconsin.
  • 22.Klein S. Solar Energy Laboratory, University of Wisconsin-Madison; Madison, WI, USA: 2014. TRNSYS 17. A TRaNsient SYstem Simulation Program. Mathematical Reference 4. [Google Scholar]
  • 23.Wetter M. Modelica buildings library. J. Building Perform. Simul. 2014;7:253–270. doi: 10.1080/19401493.2013.765506. [DOI] [Google Scholar]
  • 24.Liu P. Energy transfer and energy saving potentials of air-to-air membrane energy exchanger for ventilation in cold climates. Energy Build. 2017;135:95–105. doi: 10.1016/j.enbuild.2016.11.047. [DOI] [Google Scholar]
  • 25.Zhang L.Z. Nova Science Publishers, Inc.; New York: 2008. Total Heat Recovery: Heat and Moisture Recovery from Ventilation Air. [Google Scholar]

Articles from MethodsX are provided here courtesy of Elsevier