Skip to main content
ACS Omega logoLink to ACS Omega
. 2021 Oct 27;6(44):29921–29931. doi: 10.1021/acsomega.1c04404

Energy Saving Benefit Analysis of the Compressor Short-Stop Adjustment Method Based on TGNET

Kong Fulin , Liu Yuxin , Lige Tong †,‡,*, Li Wang †,, Qiu Yinan §
PMCID: PMC8582042  PMID: 34778664

Abstract

graphic file with name ao1c04404_0014.jpg

Aiming at the problem of gas emissions caused by the high-pressure operation of a large industrial gas (O2, N2, and Ar) pipeline network, this study establishes a mathematical model of the oxygen transmission and distribution system (OTDS) based on TGNET software. In addition, the study conducts transient simulation, comprehensively considering theoretical constraints and actual operation requirements, and adopts a large air separation company for the OTDS as a case study. After comparing two traditional adjustment methods, a compressor short stop adjustment strategy is proposed to reduce the peak pressure of the pipe network system. This study determines the energy-saving benefits and the difference in the scope of application of compressor short-stop adjustment. Compared with the medium-pressure release and inlet guide vane opening adjustment (IGVOA) strategies, the compressor short-stop adjustment strategy reduced oxygen emission by 3850.9 Nm3 and increased by 927.1 Nm3. Furthermore, the compressor operating energy consumption was reduced by 3349 and 2919 kW h. Compared with the IGVOA strategy, the compressor short-stop adjustment strategy has increased the application range of compressor inlet pressure and medium-pressure pipeline pressure by more than 70%. This strategy is effective for reducing the emission of pipeline gases caused by fluctuations in user demand.

1. Introduction

In 2020, China produced 996 million tons of crude steel,1 consumed 106.5–127.8 billion cubic meters of oxygen, and consumed 122.4–168.4 billion kW h of electricity. The power consumption of air separation units (ASUs) accounted for 15–20% of the electricity consumption of iron and steel enterprises.2 Taking oxygen as an example, processes such as ironmaking, steelmaking, and continuous casting require a considerable amount of oxygen, which is usually produced by a low-temperature air separation device3 and delivered to users at all levels through an oxygen transmission and distribution system (OTDS). Affected by factors, such as converter intermittent blowing and blast furnace shutdown, the OTDS often leads to loss of oxygen due to unbalanced supply and demand. An annual reduction of 1% of oxygen emission will contribute approximately 0.87% to China’s 2030 CO2 emission reduction target.4 The nitrogen transmission and distribution system (NTDS) and argon transmission and distribution system (ATDS) are similar to OTDS. Therefore, reducing the gas (O2, N2, and Ar) emission caused by the imbalance of supply and demand is very important for industrial consumption reduction, energy saving, and emission reduction.5

OTDS, NTDS, and ATDS belong to the gas transmission and distribution system (GTDS), whose functions include compression, transmission, secondary pressure regulation, and distribution and are an important part of steel enterprises. In the GTDS, when the user’s gas consumption is reduced, the gas generated by the ASU device exceeds the gas consumption or the gas equipment fails, and the excess quantity exceeds the storage limit. To protect the safety of the GTDS, the safety valve is usually activated, and the gas is released. In recent years, as China’s ASU becomes larger and more efficient, the imbalance between gas supply and demand has gradually increased and has become more prominent in the OTDS. Therefore, reducing reactive power consumption, reducing gas emissions, and maintaining the balance of supply and demand have attracted great attention from air separation companies. Taking oxygen as an example, the oxygen supply pressure in the steelmaking process only needs 0.8 MPa to meet the technological requirements. However, to increase the storage capacity of the OTDS, most companies increase the transmission pressure of the pipe network. On the one hand, this method increases the compression energy consumption of gas transmission. On the other hand, once the gas consumption is reduced, oxygen can be easily dispersed due to overpressure. In addition, the smelting cycle of a steel furnace in the steelmaking process is approximately 30–45 min, and the oxygen blowing time generally lasts for approximately 18 min. The time taken in oxygen consumption and blowing for different steel types varies. Therefore, oxygen overpressure release is likely to occur when the oxygen demand of the converter users decreases, which also leads to many studies on the user’s variable load regulation. To reduce gas emission, the ASU’s variable load adjustment is used to achieve the changing rhythm consistent with the converter consumption. For example, the demand response operation of the air separation plant is optimized based on, first, a mixed-integer linear program (MILP).6 MILP is an optimal scheduling method for multiple sets of air separation equipment with frequent load changes based on the shunt mode strategy.7 Then, such demand response operation is also optimized based on a two-layer framework automatic variable load system of ASU high- and low-pressure towers proposed in combination with a nonlinear model predictive control.8,9

These studies provided adjustment directions and strategies for the ASU’s rapid load change. Moreover, other studies focused on user scheduling. Examples include the following: an oxygen decision support system based on linear programming to balance the production, storage, use of oxygen, and to realize the rational use of oxygen;10,11 the decision support system established based on the MILP model that realizes the multiperiod optimization of the oxygen system and the minimization of oxygen discharge; the production scheduling model established by using mixed-integer linear12,13 and mixed nonlinear programming methods14 to minimize oxygen emission; the mathematical model of oxygen optimization scheduling15 established based on the improved simplex method; the oxygen system transient mathematical model based on the principle of supply and demand balance;16 and the oxygen scheduling of converter production based on particle swarm optimization.17 These studies provide solutions for reducing the peak pressure of the oxygen pipe network and reducing oxygen emission. However, research on the OTDS connecting the ASU and the user is insufficient, and reports on reducing the gas emission by adjusting the OTDS are limited.

However, the structure of the OTDS of Chinese iron and steel enterprises is complex, and establishing a transient model is difficult.18 At present, when solving the unsteady state engineering problems of gas pipelines, relatively mature commercial simulation software (SPS software, TGNET software, etc.) is usually used for comparative analysis.1922 Research on reducing oxygen emission focuses on the ASU variable load adjustment and the transient scheduling of the user’s production plan. Moreover, research on the adjustment method of the compressor connecting the ASU and the pipe network is limited. When the OTDS is over pressured in the actual operation, the medium-pressure release strategy (MPRS) is usually adopted by enterprises to open the relief valve when the pipeline pressure exceeds the set value to reduce the pressure of the pipeline network. The MPRS and these two research strategies have the following problems: adopting the MPRS has the characteristics of a medium-pressure release, high pressure, large instantaneous flow, and large oxygen loss and the life of the equipment is affected when adopting the ASU automatic load change strategy to adapt to fluctuations in user usage because of the adjustment hysteresis of the ASU. That is, matching the variable load regulation speed of the ASU with the fluctuating speed of gas consumption and frequent switching of valves is difficult, which is not suitable for long-term frequent adjustment. The user’s transient scheduling method is adopted to adjust the user’s oxygen consumption and production plan, which limits user production and reduces the efficiency of enterprise products to a certain extent. In summary, solving the imbalance between supply and demand without restricting production and user consumption is difficult using the current strategies or methods. Therefore, this study proposes a compressor parallel optimization adjustment [compressor short-term shutdown adjustment (CSSA)] method based on low-pressure release for the fluid mechanical load pipe network (OTDS, NTDS, and ATDS) of iron and steel enterprises when the pressure is too high. In this study, the OTDS mathematical model is established through the Pipeline Studio software TGNET module. Moreover, the historical data of a steel company in China are used as a sample to conduct transient simulations and analyze the changes in the pressure of the medium-pressure pipe network (Pmpn) and the pressure of the centrifugal oxygen compressor outlet (OCO) (Poco) during the operation process. These data are also used to compare CSSA with the inlet guide vane opening adjustment strategy (IGVOA) and MPRS in detail, analyze the adjustment effects and energy-saving performance, and provide guidance for GTDS adjustment and design.

2. Model and Methods

The novelty of this strategy lies in the adjustment of compressors to compressor stations, some of which can be shut down for a short time. The advantage of this method is that when the gas consumption is reduced, other normal gas consumption demands can be met, and the processing gas adjustment range is larger. This strategy will not affect the use of the ASU, will not limit the user’s production needs, and there is no need to worry about the possibility of compressor surge or blockage.

2.1. Mathematical Model

The OTDS is a complex looped pipe network with multiple branches, as are the NTDS and ATDS. Therefore, it is necessary to consider the influence of all pipelines and their accessories when establishing the mathematical model, especially the influence on flow and resistance.

2.1.1. Pipeline Hydraulic Calculation

For the OTDS, NTDS, or ATDS, the purity of the conveyed medium is very high. For example, the concentration of the nitrogen product exceeds 99.99 mol %, and the concentration of the oxygen product exceeds 99.6 mol %. However, they are all binary mixed media, while the Benedict-Webb-Rubin-Starling (BWRS) equation is for binary mixtures, and the precision of the actuarial calculation is high. Therefore, in the simulation, the gas state equation uses the BWRS equation, as shown in eq 1.

2.1.1. 1

where R is the cross-sectional area of the gas and A0, B0, C0, D0, a, b, c, d, α, and γ are the parameters related to the composition of the gas in the pipeline.

The calculation during transient simulation adopts the Colebrook White formula23 shown in eq 2.

2.1.1. 2

where Ke is the Reynolds number and Re is the rugosity of the pipe.

2.1.2. Pressure Loss Correction

To ensure the accuracy of the model, some types of pressure drop during pipeline transportation are analyzed in the study.

1 The valve in the model is 100% open and closed by default. The flow coefficient Cv value of the valve is calculated using the GPSA (generalized pattern search algorithm) correlation method.24 Besides, the case studied in this paper does not include temperature changes; therefore, the transportation process is simplified to an isothermal process, and temperature changes are not considered in the simulation.

Valve pressure loss is converted into a straight pipe length equivalent to the pressure drop in the model, that is, the valve equivalent length Le. The valve equivalent correction is used to calculate the flow coefficient Cv of the valve in the model. Table 3 shows the calculation method of the equivalent length of several main valves in the model.

Table 3. Size of the Pipes Used in the Network.
size quantity of pipes (piece) length of pipes (m) length of pipes/overall length (%)
DN530 44 10,060 46.88
DN350 23 1030 4.80
DN300 13 5420 25.26
DN150 5 3550 16.54
DN80 7 1340 6.24
DN50 6 60 0.28
overall 98 21,460 100

2 The remaining local pressure loss. In addition to the abovementioned two points, pressure loss caused by variable pipe diameters, elbows, flanges, tees, and others is calculated using the remaining local pressure drop. Moreover, the resistance element is used in the model to replace the remaining local pressure drop, and the damping coefficient K is calculated as shown in eq 3 where K is the damping coefficient.

2.1.2. 3

2.2. Model Constraints

Before the transient simulation starts, it is necessary to set constraint conditions for the main equipment. The model constraints of the main equipment in this paper are shown in Table 1.

Table 1. Calculation of Equivalent Length of the Main Valve.

valve type equivalent length Le
stop valve Le = 340 D
check valve Le = 600 D
block valve Le = 400 D

In addition, for steady-state control and transient-state control, the maximum iterations are 200, and the maximum convergence tolerance and the minimum convergence tolerance are set to 0.01 and 0.0001, respectively.

2.3. Simulation Methods

The continuous and stable production of gases (O2, N2, and Ar) in the air separation plant and the fluctuating gas consumption of some gas users are the main reasons for the fluctuation of the GTDS operating pressure. When the supply exceeds the demand, the gas can be easily released due to overpressure. In China, when the GTDS operating pressure is too high, that is, when Pmpn and Pco exceed Pmpn,max and Pco,max, companies usually use the MPRS to quickly release the medium-pressure and high-pressure gas in the pipeline. In addition, the compression equipment in the GTDS is usually centrifugal compressors (CCs),25 which can reduce the amount of air processed by the compressor by adjusting the inlet guide vanes of the CC.26 This adjustment scheme is called the compressor IGVOA, which is currently only used in CCs.27 Therefore, this study proposes a low-pressure oxygen release CSSA scheme.

In the GTDS, a CC with inlet guide vanes is mainly used to prevent surge during CC operation. The CC surges when the suction volume flow is lower than the limit lineref (20). To avoid surge, a certain safety margin is set, and the compressor runs at a higher mass flow. Multiple CCs can be connected in parallel, and the compressor units operating in parallel are called centrifugal compressor stations (CCS).23

2.3.1. IGVOA Strategy

The IGVOA needs to obtain a set of optimal operating parameters, which refers to ref (27), and the detailed implementation steps are shown in Figure 1. Under the premise that the user’s production scheduling plan is known, the orthogonal experiment of the optimal parameters is designed, and the pipeline studio software TGNET module is used to establish the GTDS transient mathematical model. The user’s production demand data are inputted into the model for transient simulation, and Pmpn, Pco, and other related curves are outputted from the simulation results. According to the compressor inlet flow data and outlet pressure data, the operating data Eco is calculated using Matlab software. In addition, according to the judgment requirements of Pmpn < Pmpn, max and Pco < Pco, max, the minimum gas emission Qge corresponding to the minimum is selected from the results. The optimal parameters include the adjustment size of the compressor inlet guide vane opening Δk, the adjustment start time t1, and the adjustment duration Δt1.

Figure 1.

Figure 1

IGVOA optimal parameter acquisition flowchart. a is the beginning of the overpressure interval; b is the end of the overpressure interval; and m is the auxiliary parameter, which is used to adjust the parking time.

2.3.2. CSSA Strategy

This paper puts forward CSSA by referring to IGVOA, and the core of the CSSA operation is to change a single CC to CCS. To ensure GTDS supply capacity without reducing, the design capacity of CC in CCS should not be less than its original design capacity, as shown in eq 4. The specific steps of CSSA are as follows. During the operation, when the GTDS pressure is too high, some CCs in the CCS will be shut down for a short time. According to the determined user scheduling data, the compressor outlet pressure and the pressure change of the medium-pressure pipeline located in the converter gas pipeline are simulated during the operation. The medium-pressure pipeline pressure changes in the pipeline through partial CC shut down, and the amount of gas processed by the CC and compressed to GTDS is reduced. The original CC processing gas volume that was stopped is released to the environment, and Pmpn and Pco during operation are reduced. Moreover, the CC operation energy consumption is reduced because of the CC shutdown. CSSA needs to obtain a set of operating parameters, including three operating parameters, namely, the number of CC parking n, the parking start time and the parking end time t2,e, and the parking duration Δt2. Figure 2 shows the specific acquisition process.

2.3.2. 4
Figure 2.

Figure 2

CSSA optimal parameter acquisition flowchart. n is the number of compressors stopped at the compressor station.

CSSA uses CCs to perform a short-term stop during the OTDS overpressure period, which significantly reduces the amount of gas entering the CC and GTDS, which can quickly alleviate the problem of excessive GTDS pressure. CSSA is based on the following assumptions:

1 The user’s scheduling plan has been determined. In the actual production process, the user’s gas consumption arrangement is determined in advance, that is, the scheduling plan has been determined.

2 Ignore the runtime required for the decision-making process. The strategy needs to adjust the operating parameters several times to obtain the operating parameters. To ensure the best energy-saving effect, the operating parameters need to be n = 1, and Δt is the minimum adjustment unit.

3 Ignore the impact of the CC start-stop process on CSSA. The study ignores the time required for driving and stopping in the research process strategy.

3. Specific Case Study

3.1. Brief Introduction of the OTDS

To test the effects and differences of the low-pressure release strategy (LPRS) in the GTDS, this article takes the OTDS as a case study. The OTDS is a kind of GTDS, in which the front end is an air separation plant for stable oxygen production, and the back end is a user side composed of different users. The main users in the OTDS are blast furnaces and converters. The total amount of oxygen used accounts for the total amount of oxygen in the steel plant, which is approximately 90%. The OTDS usually contains more than two CCs, pipelines with lengths ranging from several kilometers to hundreds of kilometers, multiple oxygen spherical tanks, various valves, and secondary pressure regulating stations located in the front of the user. This study selects the oxygen pipeline network transmission and the distribution system of a large steel enterprise in China and establishes an OTDS transient mathematical model based on the system diagram, as shown in Figure 3. Table 2 shows the size of the pipes.

Figure 3.

Figure 3

Large-scale OTDS in China. (a) Flow chart of the OTDS and (b) OTDS mathematical model diagram established in the pipeline.

Table 2. Main Equipment Functions and Constraints in the Model (Gas Include O2/N2/Ar).

type module name module function functional constraints
gas supply area gas source provide gas maximum flow
  centrifugal compressor compress gas minimum inlet pressure
buffer area spherical tank store gas when the pipe network pressure is higher than the set value, and release gas when lower pressure setting range
regulatory zone drain valve rapid release of gas when switched on open and close state
  pressure regulating station reduce the post-station pressure regulation to the set value post-station pressure
user area blast furnace smelt molten iron minimum pressure
  converter process molten iron for steelmaking  
  hot rolling process molten steel for continuous casting steel  
  other users small users in the venue use gas  

Figure 3 shows the OTDS diagram and the established mathematical model of a large-scale air separation company in China. The working capacity of two OCOs is 72,000 Nm3·h–1, and the design capacity is 75,000 Nm3·h–1. A piece of data recorded with a total duration of 100 min and Δt = 2 min intervals are selected from historical data, and Poco > Poco,max and Pmpn > Pmpn,max are found in this period. The oxygen production and use of the main equipment during this period are as follows. As shown in Figure 4, the maximum values of Poco and Pmpn in this case are Poco,max = 2.53 MPa and Pmpn,max = 2.70 MPa, respectively. Besides, in IGVOA, Δkmin = 3°, Δkmin = 11°, and Δ(Δk) = 2°.

Figure 4.

Figure 4

ASU and main equipment oxygen flow.

The results and errors of the model established in this paper when transient simulating pressure are shown in Figure 5. During transient simulation, the maximum pressure error is only 0.115 MPa and the average pressure error is 0.035 MPa, which indicates that the model established in this paper has high accuracy, and the transient simulation results are credible.

Figure 5.

Figure 5

Model accuracy and error.

3.2. Results and Discussion

3.2.1. Pressure Regulation Result

Figure 6 shows that the three adjustment strategies of MPRS, IGVOA, and CSSA can all adjust the pressure of the OTDS, but the difference among the three can also be seen. Among them, the MPRS is about to reach Pmpn,max and Poco,max before the Pmpn and Poco curves. In the beginning, in this case, the operating time period is 68–74 min, and Pmpn and Poco fall the fastest in this interval; the method of IGVOA starts some time before the Pmpn and Poco curves reach Pmpn,max and Poco,max operation, and in this case, the operation time period is 30–40 min. Through the adjustment of 40 min, the Pmpn and Poco curves are controlled under the Pmpn,max and Poco,max curves. Figure 4 shows that the MPRS adjustment position is same as the IGVOA adjustment position, and Figure 7 shows that the operating time period of MPRS is similar to that of MPRS, ranging from 64 to 70 min, and the adjusted Pmpn and Poco curves are similar to those of IGVOA.

Figure 6.

Figure 6

Pressure changes at key locations during OTDS operation. (a) pressure of the centrifugal OCO and (b) pressure of the CC outlet.

Figure 7.

Figure 7

Oxygen compressor adjustment plan results in CSSA. (a) single compressor structure; (b) compressor station composed of two compressors of different sizes; and (c) compressor station composed of three equal volume compressors.

3.2.2. Energy Consumption Calculation of the Centrifugal Oxygen Compressor

In this study, the energy consumption of the centrifugal oxygen compressor (COC) is calculated by the performance curve.2830 The regress function in Matlab R2014a software is used for fitting to obtain the relationship among the flow-pressure, flow-shaft power, and opening of the oxygen compressor. Table 4 shows the calculation steps of COC Eco.

Table 4. Calculation Steps of Oxygen Compressor Energy Consumption.
procedure specific operation
STEP1 use Matlab R2014a software to calculate the inlet guide vane opening k according to the intake flow Qi and exhaust pressure Po
STEP2 calculate the shaft power Nz from the inlet guide vane opening k and the intake airflow Qi
STEP3 calculate the isothermal efficiency ηT combined with the isothermal efficiency calculation formula of the CC
STEP4 use the trapz function in Matlab R2014a software to calculate the integral of the shaft power Nz during the study period to obtain the value of the total energy consumption Eco

CSSA adjusts the original single large COC to a COCS that does not reduce the total design capacity. Figure 3 shows that the two COCs in the OTDS are completely symmetrical. The following is a single COC to analyze the adjustment results of CSSA. The COC adjustment scheme with a design capacity of 75,000 Nm3·h–1 in this strategy consists of the following two cases. Figure 7 shows the result. Table 5 shows the design capacity of each parallel COC, the inner diameter, and the wall thickness of the pipe connecting the CC. The design capacity of the COC based on eq 4 is adjusted, and the inner diameter and wall thickness parameters of the connecting pipe are designed according to “Oxygen Station Design Specification GB50030.” The improved COCS can realize a short stop that increased the adjustment method and adjustment ability. This study mainly examines the short stop adjustment ability of the COCS.

Table 5. Calculation Steps of Oxygen Compressor Energy Consumption and Efficiency.
  parameter
object serial number designed capacity/Nm3·h–1 connecting pipe’s inner diameter/wall thickness/mm
(a) compressor 1# 75,000 510/10
(b) compressor 1# 25,000 309/8
  compressor 2# 50,000 460/10
(c) compressor 1# 25,000 309/8
  compressor 2# 25,000 309/8
  compressor 3# 25,000 309/8

Figure 8 shows the energy consumption comparison of the three regulation strategies in this case. Within 100 min of operation, in this case, the operating energy consumption of the oxygen compressor of the MPRS was 38,454 kW h, and the operating energy of oxygen compressors of IGVOA and CSSA was 38,024 and 35,105 kW h, respectively. In terms of total oxygen emission loss, IGVOA and CSSA are far less than the MPRS, saving 66.58 and 53.66% respectively; but in terms of oxygen compressor operating energy consumption, CSSA saves the most, which is 3349 kW h less than the MPRS. IGVOA reduced 2919 kW h.

Figure 8.

Figure 8

Comparison of operating energy consumption of the oxygen compressor.

3.2.3. Calculation of Oxygen Emission

During the operation of the OTDS, the relief valve opens to release oxygen when the pressure of the gas pipeline is too high. The pipeline pressure drops below the setting pressure after Δt2 time. During this period, the theoretical calculation of the total amount of oxygen emission Qge is as follows

3.2.3. 5

CSSA shows excellent performance in the control of oxygen emission loss and the convenience of oxygen compressor operation energy consumption control. Figure 9 shows the total oxygen emission comparison of the three regulation strategies in this case, in which the total oxygen emission loss of the MPRS in the 6 min emission interval is 7176.2 Nm3, and the total oxygen emission loss of IGVOA and CSSA is 2398.2 and 3325.3 Nm3, respectively. Compared with the MPRS, the oxygen emission losses of IGVOA and CSSA are reduced by 4778 and 3850.9 Nm3, respectively.

Figure 9.

Figure 9

Comparison of total oxygen emission.

3.2.4. Comprehensive Energy Consumption Comparison

To better compare the energy-saving performance of IGVOA and CSSA based on the MPRS, the unit consumption of oxygen ηO2 is introduced, and the saved amount of oxygen emission is converted into electricity consumption and then combined with the comprehensive analysis of the energy consumption of the compressor. The specific calculation method is as follows

3.2.4. 6

In this paper, the average annual comprehensive unit consumption of oxygen production by the research company in 2019 is about 0.96 kW h. Figure 8Figure 10 shows that CSSA saves about 2029 kW h more power than IGVOA, which has higher energy-saving performance.

Figure 10.

Figure 10

Comprehensive energy consumption comparison.

3.2.5. Comparison of Adjustment Methods

Comparison of CSSA with MPRS and IGVOA shows that the adjustment position is different from the object, and Figure 11 shows the difference between them.

Figure 11.

Figure 11

MPRS, IGVOA, and CSSA regulation principle in the OTDS (ASU photograph is from the literature;31 low-pressure and medium-pressure relief valves are from the literature;32 the OTDS is from the literature;33 buffer unit is from the literature;34 the CC is from the literature;35 user photographs are from the literature36,37).

1 The MPRS is currently the most popular adjustment method, and the safety valve will automatically open after setting the pressure;

2 IGVOA is a theoretically feasible adjustment method. IGVOA reduces the CC processing gas volume by reducing the CC inlet guide vane opening in a small range and releases oxygen in a low-pressure manner in advance, but estimating Qge is not easy; and

3 CSSA adjusts the CC to the CCS to stop for a short time when the pipe network is overpressured, and oxygen is released hypoxically in advance.

Although IGVOA is excellent in reducing the amount of oxygen released, CSSA is more significant in terms of compressor energy-saving and has a wider adjustment capacity and adjustment range. IGVOA and CSSA belong to the LPRS, but their adjustment capabilities are different. IGVOA and CSSA can be used to alleviate the problem of excessive pressure in the pipe network and oxygen emission caused by oversupply. The action positions are in front of the gas supply main pipe, and the targets are compressors, but IGVOA adjusts the compressor inlet guide vanes. IGVOA is only applicable to CCs with inlet guide vanes, whereas CSSA adjusts the start and stop status of the compressor, which is applicable to all compressors.

The instantaneous flow regulation characteristics of IGVOA and CSSA are classified into continuous and intermittent types. Figure 12 shows the different characteristics of IGVOA and CSSA in flow regulation. The three closed ranges formed by curves in the figure represent the safe working ranges of 25,000, 50,000, and 75,000 Nm3 h–1 CC; IGVOA is continuous. The line L0 represents the initial state of adjustment in the case, and L1 is the lower limit of the adjustment of IGVOA. The shaded parts of L0 and L1 indicate the adjustment range of IGVOA, which also shows that the adjustment range of IGVOA is continuous, that is, the initial state of compressor work L0 can reach any working state in the shaded area by adjusting k theoretically. CSSA is intermittent. The initial state L0 can go through the A1 line to the L2 line state (n = 1 corresponding state), and if necessary, L0 can go through the A2 line to the L3 line state (n = 2 corresponding state). The initial state L0 can also directly reach the L2 line via the A3 line (n = 2 corresponding state). In addition, from the L0 state to the L1 state and from the L0 state to the L2 state or the L3 state, CSSA greatly exceeds IGVOA in terms of flow regulation capability.

Figure 12.

Figure 12

IGVOA–CSSA instantaneous flow adjustment comparison in case.

4. Conclusions

This paper proposes a new adjustment strategy to reduce oxygen emission in the OTDS. This method adjusts the compressor to the compressor station structure, stops some compressors in a short time when the pipe network is overpressured, and quickly reduces the pressure of the pipe network. Aiming at the gas emission problems often caused by the high-pressure operation of large-scale industrial gas pipeline networks, taking OTDS as an example, transient simulation is carried out through the established mathematical model, and the three adjustment methods of MPRS, IGVOA, and CSSA are analyzed by analyzing the pressure and flow of key parts and equipment. The conclusion is as follows:

1 Transient simulation through TGNET modeling can accurately reflect the change of the flow process, and the simulation accuracy is high (maximum pressure error is 0.115 MPa).

2 CSSA is a new type of strategy with a significant energy-saving effect. CSSA fully utilizes the compressor’s adjustment function and adds optional new adjustment methods to the GTDS.

3 CSSA reduces the compressor processing gas volume and the gas volume entering the gas pipe network system, reduces the compressor outlet pressure and the medium-pressure pipeline pressure, reduces the compressor operating energy consumption, and significantly reduces the amount of gas emission.

4 Both IGVOA and CSSA can reduce oxygen emission and reduce compressor energy consumption, but CSSA has greater instantaneous adjustment ability and requires a shorter adjustment time compared to IGVOA.

5 Compared with MPRS and IGVOA, CSSA reduced oxygen emission by 3850.9 Nm3 and increased by 927.1 Nm3; compressor operating energy has been reduced by 3349 and 2919 kW h. In addition, the operation time periods of CSSA and MPRS are similar, 64–70 and 68–74 min, respectively, whereas the start time of IGVOA operation is earlier, and the operation time is longer, which is 30–70 min.

5. Discussion

A compressor short stop adjustment strategy is proposed to reduce the peak pressure of the pipe network system after comparing two traditional adjustment methods. The strategy is based on three assumptions (see Section 2.2.3). Assumptions 1 and 2 have less impact on the strategy, and assumption 3 has a greater impact because the compressor start and stop time increases with the increase in compressor processing capacity. If the time required for the compressor to start and stop exceeds the time required for the short-term stop of the strategy, oxygen emission will be increased, which will increase the energy consumption of the system and greatly reduce the energy-saving effect. In future research, the time required for the compressor to start and stop can be used as a constraint for further research.

Acknowledgments

This work was supported by the National Key Research and Development Program of China (no. 2018YFB0606104).

Glossary

Nomenclature

D

pipe inner diameter [mm]

Re

dimensionless number of Reynolds [-]

Q

the gas flow rate [m3/h]

k

inlet guide vane opening [°]

t1

IGVOA adjustment time [min]

t2

CSSA adjustment time [min]

Q

flow of centrifugal compressor [m3/h]

P

pressure [MPa]

T

temperature [K]

E

operating energy consumption [kW h]

t

time[min]

Glossary

Subscripts

min

minimum

max

maximum

s

start

e

end

co

centrifugal compressor

oco

oxygen compressor outlet

oe

oxygen emission

ge

gas emission

mpn

medium-pressure pipe network

i

in

o

out

Glossary

Greek symbols

λ

coefficient of friction

ρ0

the gas molar density [kg/mol]

Δ

difference (−)

Glossary

Acronyms

ASU

air separation unit

OTDS

oxygen transmission and distribution system

GTDS

gas transmission and distribution system

MPRS

medium-pressure release strategy

LPRS

low-pressure release strategy

IGVOA

inlet guide vane opening adjustment strategy

CSSA

compressor short-term shutdown adjustment strategy

CC

centrifugal compressor

CCS

centrifugal compressor stations

COC

centrifugal oxygen compressor

The authors declare no competing financial interest.

References

  1. National Bureau of Statistics of the People’s Republic of China. http://www.stats.gov.cn/ (accessed 2021-03-07).
  2. Zhang Y.; Chen L.; Zhou J.; Zhai G. Energy consumption and optimize circulate of air separation unit of steel corporation. Energy Metall. Ind. 2014, 33, 6. [Google Scholar]
  3. Fu Q.; Kansha Y.; Song C.; Liu Y.; Ishizuka M.; Tsutsumi A. A cryogenic air separation process based on self-heat recuperation for oxy-combustion plants. Appl. Energy 2016, 162, 1114–1121. 10.1016/j.apenergy.2015.03.039. [DOI] [Google Scholar]
  4. Tong L.; Zhang A.; Li Y.; Yao L.; Wang L.; Li H.; Li L.; Ding Y. Exergy and energy analysis of a load regulation method of CVO of air separation unit. Appl. Therm. Eng. 2015, 80, 413–423. 10.1016/j.applthermaleng.2015.01.074. [DOI] [Google Scholar]
  5. Han Z.; Zhao J.; Wang W.; Liu Y. A two-stage method for predicting and scheduling energy in an oxygen/nitrogen system of the steel industry. Control Eng. Pract. 2016, 52, 35–45. 10.1016/j.conengprac.2016.03.018. [DOI] [Google Scholar]
  6. Kelley M. T.; Pattison R. C.; Baldick R.; Baldea M. An MILP framework for optimizing demand response operation of air separation units. Appl. Energy 2018, 222, 951–966. 10.1016/j.apenergy.2017.12.127. [DOI] [Google Scholar]
  7. Zhou D.; Zhou K.; Zhu L.; Zhao J.; Xu Z.; Shao Z.; Chen X. Optimal scheduling of multiple sets of air separation units with frequent load-change operation. Sep. Purif. Technol. 2017, 172, 178–191. 10.1016/j.seppur.2016.08.009. [DOI] [Google Scholar]
  8. Xu Z.; Zhao J.; Chen X.; Shao Z.; Qian J.; Zhu L.; Zhou Z.; Qin H. Automatic load change system of cryogenic air separation process. Sep. Purif. Technol. 2011, 81, 451–465. 10.1016/j.seppur.2011.08.024. [DOI] [Google Scholar]
  9. Kopanos G. M.; Xenos D. P.; Cicciotti M.; Pistikopoulos E. N.; Thornhill N. F. Optimization of a network of compressors in parallel: Operational and maintenance planning - The air separation plant case. Appl. Energy 2015, 146, 453–470. 10.1016/j.apenergy.2015.01.080. [DOI] [Google Scholar]
  10. Liu Z.; Tang X. Z.; Zhao L. H. R$D on oxygen rational utilization system in iron and steel enterprises. Energy Metall. Ind. 1998, 17, 6–11. [Google Scholar]; (in Chinese)
  11. Tong L. G.; Tong L. G.; Wang L.; Tang X. Z.; et al. Model of blast furnace blow down for oxygen releasing rate. Energy Metall. Ind. 1999, 18, 16–19. [Google Scholar]; (in Chinese)
  12. Zhang P.; Wang L.; Tong L. MILP-based optimization of oxygen distribution system in integrated steel mills. Comput. Chem. Eng. 2016, 93, 175–184. 10.1016/j.compchemeng.2016.06.015. [DOI] [Google Scholar]
  13. Zhang P. K.; Wang L. Effects of oxygen pipe-network pressure on the oxygen scheduling during blast furnace blow-down. Chin. J. Eng. 2017, 39, 283–293. 10.13374/j.issn2095-9389.2017.02.017. [DOI] [Google Scholar]
  14. Chen C.; Zhao J.; Shao Z. J. Balance of the oxygen pipe network and scheduling in iron and steel enterprises. Comput. Appl. Chem. 2012, 29, 1089–1094. [Google Scholar]; (in Chinese)
  15. Zhang Z. Y.; Sun Y. G.; Ma Y. Based on the improved simplex method of iron and steel enterprise oxygen system optimization scheduling research. Math. Pract. Theory 2018, 48, 189–194. [Google Scholar]; (in Chinese)
  16. Chen G.; Lu Z. W.; Cai J. J.; Bu Q. Dynamic simulation of oxygen supply system in iron and steel company. J. Northeast. Univ. 2002, 23, 940–943. [Google Scholar]; (in Chinese)
  17. Fulin K.; Lige T.; Pengcheng W.; Peikun Z.; Li W.; Bing W.; Enjun C. Optimal scheduling of converter oxygen based on particle swarm optimization. Chin. J. Eng. 2021, 43, 279–288. 10.13374/j.issn2095-9389.2020.04.02.002. [DOI] [Google Scholar]
  18. Taler D.; Kaczmarski K. Mathematical modelling of the transient response of pipeline. J. Therm. Sci. 2016, 25, 549–557. 10.1007/s11630-016-0897-0. [DOI] [Google Scholar]
  19. Chen Q.; Xing X.; Jin C.; Zuo L.; Wu J.; Wang W. A novel method for transient leakage flow rate calculation of gas transmission pipelines. J. Nat. Gas Sci. Eng. 2020, 77, 103261. 10.1016/j.jngse.2020.103261. [DOI] [Google Scholar]
  20. Du M.; Mhaskar P.; Zhu Y.; Flores-Cerrillo J. Safe-Parking of a Hydrogen Production Unit. Ind. Eng. Chem. Res. 2014, 53, 8147–8154. 10.1021/ie4043938. [DOI] [Google Scholar]
  21. Yuan Z.; Deng Z.; Jiang M.; Xie Y.; Wu Y. A modeling and analytical solution for transient flow in natural gas pipelines with extended partial blockage. J. Nat. Gas Sci. Eng. 2015, 22, 141–149. 10.1016/j.jngse.2014.11.029. [DOI] [Google Scholar]
  22. Su H.; Zhang J.; Zio E.; Yang N.; Li X.; Zhang Z. An integrated systemic method for supply reliability assessment of natural gas pipeline networks. Appl. Energy 2018, 209, 489–501. 10.1016/j.apenergy.2017.10.108. [DOI] [Google Scholar]
  23. Coelho P. M.; Pinho C. Considerations about equations for steady state flow in natural gas pipelines. J. Braz. Soc. Mech. Sci. Eng. 2007, 29, 262–273. 10.1590/S1678-58782007000300005. [DOI] [Google Scholar]
  24. Sahamifar S.; Kowsary F.; Mazlaghani M. H. Generalized optimization of cross-flow staggered tube banks using a subscale model. Int. Commun. Heat Mass Tran. 2019, 105, 46–57. 10.1016/j.icheatmasstransfer.2019.03.004. [DOI] [Google Scholar]
  25. Seleznev V. E.; Aleshin V. V. Numerical analysis of fire risk at pipeline systems of industrial power facilities. Int. J. Pres. Ves. Pip. 2006, 83, 299–303. 10.1016/j.ijpvp.2006.02.005. [DOI] [Google Scholar]
  26. Zhang L.; He R.; Wang S.; Zhang Q. A Review of Rotating Stall in Vaneless Diffuser of Centrifugal Compressor. J. Therm. Sci. 2020, 29, 323–342. 10.1007/s11630-020-1261-y. [DOI] [Google Scholar]
  27. Tong L.; Kong F.; Wang Li.; Yin S.; Liu C.. Energy-saving method and system for reducing energy consumption of oxygen pipe network transmission and distribution system 2020, CN110985887B, pp 2020–1222.
  28. He X.; Liu Y.; Rehman A.; Wang L. A novel air separation unit with energy storage and generation and its energy efficiency and economy analysis. Appl. Energy 2021, 281, 115976. 10.1016/j.apenergy.2020.115976. [DOI] [Google Scholar]
  29. Adamson R.; Hobbs M.; Silcock A.; Willis M. J. Steady-state optimisation of a multiple cryogenic air separation unit and compressor plant. Appl. Energy 2017, 189, 221–232. 10.1016/j.apenergy.2016.12.061. [DOI] [Google Scholar]
  30. Meroni A.; Zühlsdorf B.; Elmegaard B.; Haglind F. Design of centrifugal compressors for heat pump systems. Appl. Energy 2018, 232, 139–156. 10.1016/j.apenergy.2018.09.210. [DOI] [Google Scholar]
  31. Liu Y.; Tong L.; Kong F.; He X.; Yang H.; Wang L.; Ding Y. An improved ASU distillation process and DIM-LPB method for variable product ratio demand. Sep. Purif. Technol. 2021, 277, 119499. 10.1016/j.seppur.2021.119499. [DOI] [Google Scholar]
  32. Stewart M.Piping system components. In Surface Production Operations; Stewart M., Ed.; Gulf Professional Publishing: Boston, 2016, pp 193–300. [Google Scholar]
  33. Kumar G. A.; Patil A. K.; Kang T. W.; Chai Y. H. Sensor Fusion Based Pipeline Inspection for the Augmented Reality System. Symmetry 2019, 11, 1325. 10.3390/sym11101325. [DOI] [Google Scholar]
  34. Curadelli O. Seismic reliability of spherical containers retrofitted by means of energy dissipation devices. Eng. Struct. 2011, 33, 2662–2667. 10.1016/j.engstruct.2011.05.015. [DOI] [Google Scholar]
  35. Hundy G. F.; Trott A. R.; Welch T. C.; Hundy G. F.. Compressors. In Refrigeration, Air Conditioning and Heat Pumps, 4th ed.; Trott A. R., Welch T. C., Eds.; Butterworth-Heinemann, 2016; pp 59–87. [Google Scholar]
  36. Sun W.; Wang Q.; Zhou Y.; Wu J. Material and energy flows of the iron and steel industry: Status quo, challenges and perspectives. Appl. Energy 2020, 268, 114946. 10.1016/j.apenergy.2020.114946. [DOI] [Google Scholar]
  37. Zhou P.; Xu Z.; Zhao J.; Song C.; Shao Z. Long-term hybrid prediction method based on multiscale decomposition and granular computing for oxygen supply network. Comput. Chem. Eng. 2021, 153, 107442. 10.1016/j.compchemeng.2021.107442. [DOI] [Google Scholar]

Articles from ACS Omega are provided here courtesy of American Chemical Society

RESOURCES