Abstract
Hard water and elevated ammonia are problems for many United States groundwater drinking water utilities, and some utilities, particularly those in the Midwest, face both challenges. Ion (cation) exchange (IX) is a common treatment technique for hardness reduction (i.e., softening) and may be used to remove ammonia as well, but these constituents may compete in IX and impact overall treatment performance. Few data have been reported on the impact on ammonia concentrations when using IX for softening in full-scale systems. This study investigated four full-scale groundwater treatment plants in Illinois that practice IX for softening (raw water hardness > 220 mg/L as CaCO3) and have elevated groundwater ammonia concentrations (> 2 mg N/L). Sampling throughout the year revealed consistent finished water hardness levels but variable ammonia concentrations. Ammonia removal varied and depended on how much water had been treated since the last regeneration. High ammonia removal (sometimes > 90%) occurred in the first half of the IX service cycle, while effluent ammonia concentrations increased compared to the influent (sometimes > 200%) towards the end of the IX cycle (total length 50,000–92,000 gallons [190–350 m3]). Ammonia removal efficiency varied among the plants, but the overall trends were similar. Because variable ammonia concentrations may make it difficult to produce a consistent total chlorine residual, they can negatively impact disinfection and water quality in the distribution system. Ammonia concentrations should be considered when designing softening systems to determine regeneration frequency, develop blending strategies, or include an alternative ammonia treatment process before IX softening to produce a more stable and consistent finished water.
Keywords: Ammonia, Hardness, Ion exchange, Softening, Chloramination, Breakpoint
1. Introduction
Many groundwater drinking water sources in the United States (U.S.) are very hard (> 180 mg/L as CaCO3) and contain elevated free ammonia (the sum of ammonia (NH3) and ammonium ion (NH4+), hereinafter referred to as free NH3), neither of which is regulated in drinking water by the U.S. Environmental Protection Agency (EPA). Hardness is the sum of dissolved multivalent cations in a water, with calcium (Ca2+) and magnesium (Mg2+) ions being the primary constituents. Hardness in groundwater is associated with naturally occurring mineralogical processes and depends on the local geology where limestone and sedimentary rock aquifers tend to have greater hardness. Elevated hardness can cause scaling and staining of plumbing materials (e.g., valves, faucets, and fixtures), which are nuisance aesthetic issues, and decrease the efficiency of drinking water delivery processes (e.g., water heaters). Softening treatment techniques include ion (cation) exchange (IX), nanofiltration, and lime softening.
There are no federal regulatory requirements to monitor NH3 in source water so there is no way to precisely identify how many IX softening plants treat NH3-containing waters. To get an indication as to the potential prevalence and geographic distribution of this treatment scenario, Fig. 1 shows community water systems (CWSs) in the conterminous U.S. that treat groundwater using IX softening along with groundwater free NH3 concentrations from monitoring wells (i.e., the NH3 data are not from the CWSs’ source water). In total, 1,167 CWSs were identified, and 353 of these systems had at least one monitoring well within a 10-mile radius. Of these 353, 155 CWSs were located near a well with free NH3 > 0.5 mg N/L. Most of these CWSs (> 90%) were small systems serving fewer than 10,000 people. The states that were found to have the highest number of IX softening water treatment plants that might be treating groundwater with elevated NH3 were Illinois, Minnesota, Iowa, Ohio, Florida, and Louisiana. This analysis illustrates that the treatment scenario investigated in the current study may exist in several areas throughout the conterminous U.S.
Fig. 1.
Community water systems that treat groundwater using ion exchange for softening (“X”) and groundwater free ammonia concentrations in the conterminous U.S.
Sources of free NH3 in groundwater include agricultural and urban runoff, degradation of naturally occurring organic matter, septic systems, and discharges from municipal wastewater treatment plants and concentrated animal feeding operations. The EPA has set a health advisory for the lifetime intake of free NH3 through drinking water of 30 mg N/L (USEPA 2018). At concentrations much less than the health advisory level (e.g., 1 mg N/L), free NH3 may negatively impact some drinking water treatment processes and cause problems in the distribution system. Treatment processes that involve free chlorine (free Cl2) addition (chlorination) can be negatively impacted because free NH3 reacts with free Cl2 to produce chloramines, which are weaker oxidants than free Cl2. Chlorination often is used in arsenic and manganese removal processes, and the presence of free NH3 may inhibit treatment efficacy (Chen et al. 2018, Lytle et al. 2007). In the distribution system, the biological oxidation of free NH3 (nitrification) can lead to disinfectant residual loss, corrosion of distribution system materials, taste and odor complaints, elevated nitrite (NO2−) and nitrate (NO3−) concentrations, and excessive oxygen demand (Bremer et al. 2001, Edwards and Dudi 2004, Odell et al. 1996, Rittmann and Snoeyink 1984, Speitel et al. 2011, Suffet et al. 1996). Of particular concern is NO2− generation, which is regulated with a maximum contaminant level (MCL) of 1 mg as N/L entering the distribution system as an acute health risk (USEPA 2018). Incomplete nitrification resulting in NO2− accumulation can occur when insufficient dissolved oxygen is present (Park et al. 2010), and NO2− accumulation can approach 1 mg N/L in distribution systems experiencing nitrification (Odell et al. 1996). Although federally regulated at the entry point into the distribution system, some states (e.g., Iowa) choose to also enforce the MCL in the distribution system if nitrification is suspected.
Treatment techniques for elevated groundwater free NH3 include free Cl2 addition to form chloramines or remove free NH3 by breakpoint chlorination, biofiltration, and IX. Chloramine formation can be difficult to control, and chloramines can lead to nitrification in the distribution system (Wilczak et al. 1996). Breakpoint chlorination may require an excessive amount of chlorine, which can be costly and generate undesired disinfection byproducts. In biofiltration, nitrification occurs as a controlled process at the treatment plant, producing an effluent with free NH3 concentrations below 0.1 mg N/L that is more biologically stable (i.e., less likely to promote changes in the microbial community and thus water quality within the distribution system) (de Vet et al. 2011, Lytle et al. 2013, Lytle et al. 2015).
IX processes can remove free NH3 because free NH3 is predominantly NH4+ at typical pH values of most drinking waters (pKa of NH4+/NH3 is 9.24 at 25°C; Smith et al. 1996). Some zeolite resins, particularly clinoptilolite, are selective towards NH4+. A typical selectivity profile for clinoptilolite is: K+ > NH4+ > Na+ > Ca2+ > Mg2+ (Colella 1996). Nevertheless, other cations, including Ca2+ and Mg2+, can compete with NH4+ and lower its removal efficiency (Beler-Baykal and Cinar-Engin 2007, Wang et al. 2007).
IX is also commonly used to remove hardness ions (i.e., softening). IX tends to be more attractive to small groundwater systems because it is simpler and has lower capital and operation and maintenance costs than other softening processes, such as lime softening (Logsdon et al. 1990). IX softeners typically use a sulfonated polystyrene resin loaded with sodium (Na+). These resins are selective towards cations with a higher valence and smaller hydrated ionic radius with a typical selectivity profile of: Ca2+ > Fe2+ > Mg2+ > K+ > NH4+ > Na+ (Clifford et al. 1986). In contrast to zeolite resins, sulfonated polystyrene resins generally are only slightly more selective towards NH4+ than Na+.
IX resin selectivity determines removal profiles over time when multiple competing cations are present. In general, the most preferred cations are removed consistently and are the last to breakthrough with a sharp breakthrough curve, reaching their influent concentration. Less preferred ions are removed early in the service cycle, concentrated within the bed, and then are released as the more preferred cations out-compete and replace them on IX sites (Clifford 1982). The displacement of less preferred ions results in “peaking” for these ions where their effluent concentration is greater than their influent concentration. Peaking has been observed in drinking water anion exchange systems treating arsenate and NO3− (Ghurye et al. 1999, Wang et al. 2002). In IX softeners where Ca2+ and Mg2+ are the preferred species, however, the impact of competition between hardness cations and NH4+ has not been reported.
Variable effluent free NH3 concentrations and peaking could negatively impact finished water quality by affecting the form and concentration of the desired disinfectant (i.e., chlorination or chloramination) at the treatment plant that may subsequently impact the distribution system (e.g., promoting nitrification). IX softener water plant operators have indicated that they often observed unexplained changing disinfectant levels despite maintaining a consistent free Cl2 feed rate (personal communication). Despite the broad use of IX softening, its impact on free NH3 has not been extensively reported, particularly in full-scale drinking water treatment applications. The objective of this study was to investigate IX used to soften hard water and its concurrent impacts on free NH3 removal, finished free NH3 levels through an operation cycle, and subsequent chlorination. Four full-scale groundwater treatment plants serving small systems in Illinois were investigated.
2. Materials and methods
2.1. Systems
Four small drinking water systems in Illinois treating groundwater with hardness greater than 300 mg/L as CaCO3 and free NH3 greater than 2 mg N/L were identified. The treatment plants were designed to remove iron, manganese and/or arsenic and hardness ions, and the treatment trains all included aeration, filtration, IX softening (with some bypass), and free Cl2 addition (Table 1). Three of the plants added free Cl2 or permanganate before the filters to oxidize and remove iron, manganese, and arsenic ahead of the softeners. The plants operated a portion of the day.
Table 1.
Treatment plant descriptions.
System A | System B | System C | System D | |
---|---|---|---|---|
| ||||
Connections | 620 | 200 | 1,300 | 456 |
Population | 1,300 | 500 | 3,600 | 1,280 |
Number of Wells | 3 | 2 | 3 | 3 |
Plant Capacity | 233 gpm 1,270 m3/d |
100 gpm 550 m3/d |
192 gpm 1,050 m3/d |
190 gpm 1,050 m3/d |
Treatment Process | Aeration Detention time Filters IX Softeners (n=3)1 Fluoride addition Chlorine addition Polyphosphate addition |
Aeration Chlorine addition Detention time Filters IX Softener (n=1) Caustic soda addition Fluoride addition Chlorine addition |
Aeration Detention time Chlorine or permanganate addition Microfiltration IX Softeners (n=4) Chlorine addition |
Aeration Chlorine addition Filters IX Softeners (n=2) Fluoride addition Polyphosphate addition Chlorine addition |
IX Softener Bypass (approx.) | 15% | 10% | 33% | 25% |
IX Softener Service Cycle | 50,000 gal 190 m3 |
45,000–55,000 gal 170–210 m3 |
92,000 gal 350 m3 |
62,000–65,000 gal 235–245 m3 |
IX Resin Volume per Vessel | 42 ft3 1,190 L |
65 ft3 1,840 L |
113 ft3 3,200 L |
84 ft3 2,380 L |
Daily Operating Time (hours/day) | 10–12 | 7–10 | 8–10 | 8–9 |
“n” refers to the number of IX softening units in the treatment process.
2.2. Sampling
Routine monthly water samples were collected over a 6-month period. Generally, samples were collected from four locations within the treatment each train: (i) raw water (RW), (ii) after filtration/before IX softening (BS), (iii) after IX softening (AS), and (iv) finished water (FW). The AS sample captured the effluent from a single IX softener. The FW sample included the combined IX softener effluent as well as filtered water (i.e., BS sample) that bypassed softening and was collected after chlorination. An AS sample was not collected at System B because a sample tap was not available at this location within the treatment train. Two AS samples were collected at System C. At System D, two BS and two AS samples were collected, one from each IX softener. The volume of water treated by each sampled IX softener since its last regeneration was recorded on the chain of custody form.
In addition to routine samplings, at least one set of AS samples was collected at regular time intervals within an IX softener service cycle (i. e., between brine regenerations) at each system to understand cation breakthrough patterns. The intention was to collect samples every 5,000–10,000 gallons (20–38 m3) of water treated over the course of one cycle; however, complete profiles were not captured at all facilities because samples could only be collected during normal operating hours.
Sampling taps were flushed for at least one minute at a moderate rate prior to collecting water samples. Samples were collected in 250-mL high-density polyethylene (HDPE) bottles and were filled to the top and tightly sealed. Two sample bottles were filled at each location. One sample bottle was preserved with 0.15% nitric acid (HNO3) for metals analysis, and the other did not contain a preservative. Collected water samples were shipped overnight on ice to the EPA laboratories in Cincinnati, Ohio for analysis. Operators recorded the volume of water that had been treated by the IX softener(s) since the last regeneration when the samples were collected on the chain of custody form that accompanied the samples.
2.3. Water quality analyses
No water quality analyses were performed on-site, which is a limitation because some parameters (e.g., pH and total Cl2) change over time, and it is preferred to measure them immediately. Upon receipt, water samples were immediately tested for pH, free Cl2, and total Cl2. The pH was measured using a benchtop pH/ISE meter (EC40, Hach, Loveland, CO) and combination pH electrode (Model 48600, Hach, Loveland, CO) with temperature corrections. The probe and meter were calibrated daily using pH 7 and 10 standard solutions (Whatman, Hillsboro, OR). Free Cl2 and total Cl2 were measured using the DPD method (4500-Cl, APHA 2005), and absorbance was measured using a spectrophotometer (DR/2000, Hach, Loveland, CO).
Total inorganic NH3 (350.1, USEPA 1983) and NO2− and NO3− (353.2, USEPA 1983) were measured via automated colorimetric methods. Total NH3 includes free NH3 and NH3 that is combined in chloramines. All NH3 in the RW was assumed to be present as free NH3. Free NH3 in the FW samples was calculated using total Cl2, free Cl2, and total NH3 data. The combined Cl2 concentration was calculated by subtracting the free Cl2 concentration from the total Cl2 concentration. The amount of NH3 combined in chloramines was calculated, assuming that all combined Cl2 was present as monochloramine. Finally, the free NH3 concentration was calculated by subtracting the calculated combined NH3 concentration from the measured total NH3 concentration. Organic nitrogen species were not considered. Alkalinity was measured via potentiometric titration (2320, APHA 2005). Metals and other elements (iron, manganese, calcium, magnesium, and potassium) were measured by inductively coupled plasma atomic emission spectroscopy (200.7, USEPA 1994; Thermo Jarrel Ash, Franklin, MA). Arsenic was measured by inductively coupled plasma mass spectrometry (200.8, USEPA 1994; Agilent, Santa Clara, CA). Hardness was calculated as the sum of the magnesium and calcium concentrations.
2.4. Mapping
Records of CWSs that treat groundwater using IX for softening were obtained from the 3rd quarter 2020 of EPA’s Safe Drinking Water Information System (SDWIS) Federal Data Warehouse (USEPA 2020). The system addresses were geocoded using the U.S. Census Bureau’s Public AR Current reference database (U.S. Census Bureau 2020). Groundwater data from January 1, 2015 to November 1, 2020 were obtained from the Water Quality Portal (Read et al. 2017). Reported free NH3 concentrations were averaged if a well was sampled multiple times during that period. If more than one well was located within 10 miles of a PWS, the highest free NH3 concentration was used to determine whether the CWS might have elevated free NH3 in its source water. Geospatial calculations and mapping were performed in R using the sf and tidyverse packages (Pebesma 2018, R Core Team 2020, Wickham et al. 2019).
3. Results
3.1. Treatment performance
Table 2 summarizes the RW and FW quality observed at each system during this study. The four systems treated very hard groundwater, with hardness levels usually exceeding 300 mg/L as CaCO3. They also had high iron levels, with average RW iron concentrations ranging from 2.11–3.84 mg/L, which are much greater than the secondary MCL (SMCL) of 0.3 mg/L. Manganese was less prevalent, and average RW manganese concentrations were below the SMCL of 0.05 mg/L. These groundwaters contained elevated levels of free NH3, ranging from 1.99–7.37 mg N/L.
Table 2.
Summary of raw and finished water quality [average (minimum − maximum)].
System | n | pH | Alkalinity (mg/L CaCO3) | Hardness (mg/L CaCO3) | Ca (mg/L) | Mg (mg/L) | Fe (mg/L) | Mn (mg/L) | As (μg/L) | K (mg/L) | Total NH3 (mg N/L)1 | Free NH3 (mg N/L)2 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| |||||||||||||
A | RW3 | 7 | 7.97 (7.88–8.28) | 465 (444–472) | 322 (305–339) | 78.5 (73.9–83.5) | 30.6 (29.3–32.0) | 2.11 (1.58–2.60) | 0.044 (0.030–0.051) | 0.4 (<0.4–0.7) | 17.3 (1.8–110.3) | 2.09 (1.99–2.14) | 2.09 (1.99–2.14) |
FW4 | 7 | 7.82 (7.62–8.06) | 467 (460–471) | 72 (33–119) | 12.9 (7.9–24.1) | 9.6 (3.1–16.9) | 0.02 (0.01–0.03) | 0.011 (0.004–0.019) | <0.35 | 7.9 (0.6–47.4) | 0.46 (0.02–1.10) | 0.08 (0.01–0.29) | |
B | RW | 6 | 7.52 (7.16–8.16) | 430 (406–451) | 220 (36–341) | 49.8 (8.2–78.3) | 23.4 (3.7–36.0) | 3.15 (0.09–7.61) | 0.028 (0.005–0.043) | 18.3 (2.0–37.9) | 2.2 (0.4–5.9) | 5.20 (0.93–7.37) | 5.20 (0.93–7.37) |
FW | 5 | 8.13 (7.71–9.27) | 436 (407–470) | 71 (16–309) | 15.9 (3.9–68.5) | 7.5 (1.5–33.5) | 0.10 (0.01–0.57) | 0.010 (0.004–0.040) | 3.5 (1.4–9.3) | 1.0 (0.4–2.2) | 4.45 (0.90–8.76) | 4.45 (0.38–8.75) | |
C | RW | 7 | 7.56 (7.25–7.85) | 470 (462–481) | 367 (361–380) | 87.2 (85.3–91.3) | 36.4 (35.6–37.9) | 3.84 (3.14–4.86) | 0.094 (0.080–0.105) | 26.2 (24.1–31.0) | 2.1 (1.9–2.5) | 6.27 (5.95–6.52) | 6.27 (5.95–6.52) |
FW | 6 | 7.45 (7.25–7.60) | 447 (439–456) | 162 (127–196) | 33.3 (27.1–38.8) | 19.1 (14.1–24.2) | 0.05 (0.02–0.19) | 0.044 (0.033–0.055) | 8.0 (6.8–9.4) | 2.9 (2.1–3.6) | 5.22 (3.05–7.45) | 5.20 (2.87–7.03) | |
D | RW | 7 | 7.35 (7.11–7.98) | 458 (448–467) | 314 (301–325) | 73.1 (70.4–76.0) | 32.0 (30.5–33.0) | 2.80 (2.28–3.42) | 0.029 (0.024–0.042) | 14.1 (12.4–15.1) | 2.5 (2.3–2.8) | 2.93 (2.73–3.50) | 2.93 (2.73–3.50) |
FW | 6 | 7.59 (7.45–7.76) | 446 (438–453) | 124 (93–168) | 28.0 (21.4–36.3) | 13.2 (9.6–18.9) | 0.27 (0.08–0.40) | 0.012 (0.006–0.019) | 4.2 (2.9–5.7) | 1.8 (1.1–3.3) | 2.13 (0.65–4.02) | 1.73 (0.24–4.02) |
Total NH3 includes both free NH3 and NH3 combined in chloramines.
All RW NH3 is assumed to be free NH3. FW free NH3 is calculated using free Cl2 and total Cl2 data, assuming all combined Cl2 is present as monochloramine.
RW: raw water
FW: finished water
All systems achieved good hardness reduction (55–80% on average), with average FW hardness ranging from 71–162 mg/L as CaCO3 after blending the IX softener effluent with unsoftened bypass stream. Average iron removal was >88% at all systems, although the FW iron concentration sometimes was greater than the non-enforceable SMCL at Systems B and D.
In contrast, total NH3 removal was inconsistent and varied among and within the four systems. At System C, for example, the FW total NH3 concentration ranged from 3.05–7.45 mg N/L despite a consistent RW free NH3 concentration of 6.3 ± 0.21 mg N/L (average ± standard deviation). The range in FW total NH3 concentrations was even wider at System B where it spanned from <1 mg N/L to 8.76 mg N/L. The observed wide range in FW total NH3 levels could substantially impact the ability to maintain a consistent disinfectant residual and the water quality in the distribution system.
3.2. Nitrogen speciation through treatment
To better understand the fate of nitrogen through the treatment plants, individual inorganic nitrogen species were measured through the treatment processes (Fig. 2), allowing calculation of total inorganic nitrogen concentrations (sum of total NH3, NO2−, and NO3−, hereinafter TOTIN). Free NH3 was the dominant constituent of TOTIN in the RW samples at all four plants, and the greatest change in TOTIN concentration occurred across the IX softeners. System A was the only plant that was observed to consistently achieve total NH3 removal within the plant during the routine sampling events. At the other three facilities, the FW total NH3 concentration sometimes exceeded the RW total NH3 concentration. It is important to note that the IX softeners were at different stages in their service cycle (i.e., they had treated different volumes of water since regeneration) between the sampling dates and sometimes between multiple IX softeners at one system on the same sampling date. This difference likely contributed to the range in observed FW NH3 concentrations.
Fig. 2.
Nitrogen balances through Systems (A) A, (B) B, (C) C, and (D) D. RW: raw water, BS: before IX softener, AS: after IX softener, FW: finished water. Multiple BS and AS sample locations at one plant are indexed as 1 and 2. * indicates no data are available. Note that the ordinate scale is different for each system.
NH3 removal occurred through multiple processes at System A. Nitrification appeared to occur before the IX softeners. Between the RW and BS samples, approximately 0.5–1 mg N/L total NH3 was converted to NO3−. System A was the only plant where evidence of nitrification (i.e., NO2− and/or NO3− formation) was observed, and importantly, it also was the only system that did not practice prechlorination, thereby providing a conducive environment for biological activity. The IX softeners were very effective at removing total NH3. The IX softeners reduced total NH3 levels during all six routine sampling events by 1–1.5 mg N/L so that the total NH3 concentration in the AS sample was <0.05 mg N/L. Notably, the resulting total NH3 concentration after nitrification was 1.34 ± 0.17 mg N/L, which was the lowest BS total NH3 concentration of all systems, and the lower IX softener influent concentration likely allowed for better total NH3 removal through the IX softeners. The total NH3 concentration in the FW was greater than that in the IX softener effluent and had greater variability, which was attributed to blending with unsoftened water. NO3−, a monovalent anion, levels were not impacted by IX softening, as expected.
The total NH3 trends at Systems B, C, and D were similar to each other and differed substantially from the trend observed at System A. At these three facilities, total NH3 was the dominant TOTIN species, and the TOTIN speciation did not change within the plant. The total NH3 concentration generally was consistent between the RW and BS samples but varied widely across the IX softeners and in the FW samples over the routine sampling events.
At System B, the total NH3 concentration of RW and BS samples were typically similar (Figure 2B). It is unclear why the total NH3 concentration was greater in the BS sample than the RW sample in June 2012. The total NH3 concentration in the FW sample fluctuated to be both greater than and less than that in the RW sample, with the difference ranging from −2.87 mg N/L to +1.86 mg N/L. An AS sample, separate from the FW sample, was not collected at System B. Approximately 10% of the plant flow bypassed the IX softener, so blending may have contributed to increased total NH3 in the FW sample. Nevertheless, the IX softener demonstrated the ability to both remove (up to 77%) and increase (up to 33%) total NH3.
The variability in IX softened total NH3 levels was largest at System C. Compared to BS total NH3, sometimes total NH3 removal was greater than 95% while other times up to a 200% increase in total NH3 occurred (Fig. 2C). This variability resulted in AS total NH3 concentrations that ranged from 0.05–19.3 mg N/L. The total NH3 concentration often was very different between the two collected AS samples. Sometimes the FW sample appeared to be a blend of the two IX softener effluents, with a total NH3 concentration somewhere between them. However, the total NH3 concentration in the FW sample sometimes was greater or less than both AS samples.
At System D, the IX softeners achieved greater than 90% total NH3 removal at times, but at other times, the total NH3 concentrations increased more than 100% from the BS total NH3 (Fig. 2D). The FW sample total NH3 concentration sometimes was between the concentrations in the two IX softener effluents, helping to dampen IX softener effluent concentrations, but the FW sample total NH3 concentrations were also, at times, greater or less than either of the AS samples.
During the routine sampling events at three of the four facilities (Systems B, C, and D), the IX softeners both removed and increased total NH3 such that the total NH3 concentration in the FW sample was sometimes greater than that in the RW sample. The IX softener at System A appeared to consistently remove total NH3 during the routine samplings, and importantly it was sampled early in the service cycle and had the lowest average BS sample total NH3 concentration (1.34 mg N/L vs. 4.90 mg N/L, 6.27 mg N/L, and 2.82 mg N/L at Systems B-D, respectively). Overall, the total NH3 plant profiles demonstrate that IX softeners can have a strong but inconsistent impact on the total NH3 concentration.
3.3. Ammonia removal throughout IX softener service cycles
The FW sample total NH3 concentrations observed during the routine sampling varied widely despite consistent total NH3 concentrations in the RW samples (Table 2), likely because the FW samples were collected at different stages within the IX softener service cycle (i.e., between regenerations). Fig. 3 shows the total NH3 concentration ratio between the AS and BS samples as a function of the stage in the service cycle based on (A) the volume of water treated and (B) the equivalents of hardness loaded per unit volume of IX resin. Occasionally, an IX softener was operated beyond its stated treated water volume regeneration setpoint. At all systems, total NH3 tended to be removed (i.e., C/C0 < 1) when the normalized hardness loading was less than approximately 0.5 eq/L, which typically occurred during the first half of the service cycle. The initial removal efficiency varied from 40% up to approximately 100%. The total NH3 removal efficiency tended to decrease as the service cycle continued, with total NH3 release (i.e., C/C0 > 1) occurring when the normalized hardness loading exceeded 0.5 eq/L resin. In one instance, the total NH3 concentration in the AS sample was more than twice as large as the concentration in the BS sample. Competition for exchange sites on the resin likely increased as the service cycle continued, causing the more preferred cations (i.e., Ca2+ and Mg2+) to displace the previously adsorbed NH4+. Thus, the IX softeners sometimes functioned as a source of NH4+ within the treatment plant. IX softeners are operated and regenerated based on hardness removal goals, whereas if NH4+ removal was the goal, the units would need to be regenerated at approximately 50% of the current service cycle length to prevent NH4+ breakthrough and release. Consequently, brine waste production would approximately double at an increased financial cost.
Fig. 3.
Total ammonia IX softener effluent and influent concentration ratios observed during routine sampling events as a function of the stage in the service cycle based on (A) the relative volume of water treated and (B) the amount of hardness loaded per unit volume of resin.
To better understand the fate of multiple cations as a function of the volume of water treated by IX softening, a series of water samples were collected from the AS sample location throughout a service cycle at each system (Fig. 4). Two profiles were collected at System C on different dates. The profile at System D was split between the two AS sampling locations such that samples were collected from AS_1 during the first half of the profile and from AS_2 during the second half. It was not always possible to collect samples over the entire service cycle due to personnel and operational constraints, so the end of the service cycle was prioritized when possible.
Fig. 4.
IX softener effluent ammonia concentrations at each system over one service cycle based on (A) the relative volume of water treated and (B) the amount of hardness loaded per unit volume of resin.
Fig. 4 shows the AS sample total NH3 concentration at each system over the course of one service cycle. The RW sample total NH3 concentration is shown before the service cycle for reference. At each system, the total NH3 concentration increased at some point in the second half of the service cycle, and it exceeded the RW concentration at Systems A, C, and D. Peaking above the RW total NH3 concentration was followed by a decrease at Systems A and D. The behavior at System C could not be determined because sampling did not continue to the end of the cycle. The normalized loaded hardness at which peaking was observed differed among the systems, ranging from 0.45–0.7 eq/L resin.
The changes observed over one service cycle help explain the variability shown in Fig. 2, and these profiles indicate that large changes happened over a short period. For instance, the AS sample total NH3 concentration changed from 6.5 mg N/L to 13.8 mg N/L to 3.9 mg N/L over a period of 3 hours (treated water volume of 10,000 gal [38 m3]) in one of the IX softeners at System D.
Fig. 5 shows the concentration ratio of common cations in the IX softener effluent as compared to the RW samples at each system. At most of the systems, the IX softeners continued to perform well by removing Ca2+ and Mg2+, the most dominant hardness cations, throughout the service cycle, as expected. However, breakthrough of Mg2+ was observed at Systems A and D in the last 80–90% of the service cycle, at which point the normalized loaded hardness were 0.8 eq/L resin and 0.6 eq/L resin, respectively.
Fig. 5.
Concentration ratios of common cations in the IX softener effluent as compared to the raw water through one service cycle at Systems (A) A, (B) B, (C) C in November 2012, (D) C in March 2013, and (E) D. Note that the volume of water treated in one service cycle is system-specific based on plant conditions and hardness removal goals.
Total NH3 removal ranged from 28–98% in all systems early in the service cycle; then, removal tended to decrease as the cycle progressed. The concentration ratio values and trends were similar to those observed during the routine sampling events (Fig. 3). Release of NH4+ (i.e., C/C0 > 1) was observed at three of the systems at some point during the last 30% of the service cycle (Fig. 5A, 5D, and 5E). Towards the end of the cycle, Ca2+ and Mg2+ appeared to out-compete NH4+ and K+ for exchange sites on the IX resin such that Ca2+ and Mg2+ continued to be removed while NH4+ and K+ were released. Effluent peaking of less preferred ions is a known phenomenon in IX (Clifford et al. 1986), and these data demonstrate that effluent peaking of NH4+ can occur in IX softeners.
3.4. Disinfection chemistry implications
Fluctuating total NH3 concentrations associated with IX softening operations as illustrated in this work can have important, possibly dramatic, implications on Cl2 disinfection by complicating the ability to produce a consistent disinfectant residual (type and concentration). As noted previously, operators at the four systems included in this study have observed changing disinfectant levels in the FW despite maintaining a consistent Cl2 feed rate. Fig. 6 shows free and total Cl2 concentrations in FW samples collected during the routine sampling events. Although there was the limitation that concentrations were measured when the samples were received at the laboratory (i.e., within 24 hours after collection), they may still reflect early points in the distribution system. Both free Cl2 and total Cl2 were detected in samples from System A, indicating that the disinfectant residual could be present as free Cl2 and/or chloramines, whereas no free Cl2 was detected in Systems B-D and their disinfectant residual was present exclusively as chloramines. The total Cl2 concentration varied widely at each system and was ≤ 0.1 mg Cl2/L at least once at each plant and was non-detect in one sample. For groundwater systems that use chemical disinfection, EPA requires a detectable Cl2 residual throughout the distribution system, and many states require a residual above a specified limit. Illinois EPA previously required a minimum free Cl2 residual of 0.2 mg/L or a minimum total Cl2 residual of 0.5 mg/L throughout the distribution system for all public water systems, and in 2019, increased the minimum free Cl2 and total Cl2 residuals to 0.5 mg/L and 1.0 mg/L, respectively (Ill. Admin. Code 2019). Maintaining a greater total Cl2 residual likely is necessary in chloraminated systems, such as the systems presented here, to achieve the intended effects of a detectable residual (AWWA 2013, Great Lakes-Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers 2012). These systems sometimes had difficulty achieving a total Cl2 residual in the FW sample, which could negatively impact water quality in the distribution system.
Fig. 6.
Free and total chlorine concentrations in routine finished water (FW) samples from Systems (A) A, (B) B, (C) C, and (D) D. n.d.: non-detect.
System A had the widest range in total Cl2 residual, ranging from 0.06–4.1 mg Cl2/L. System A had the lowest and most consistent AS sample total NH3 (0.02 ± 0.01 mg N/L), but the FW sample total NH3 ranged from 0.02–1.1 mg N/L (Fig. 2A). The FW sample total NH3 is influenced by the AS concentration, the bypass stream, and chlorination. The lowest total Cl2 residuals occurred in the March 2012 and July 2012 samples (Fig. 6A), and they coincided with the lowest FW sample total NH3 (Fig. 2A). It is possible that the plant was operating very near the breakpoint during these two sampling events, meaning that the applied Cl2 dose was very close to the amount needed to oxidize the free NH3 present, so both the total NH3 and Cl2 in the FW sample were minimal. This process is discussed in more detail below. For Systems B-D, there was no apparent trend between the total Cl2 residual and total NH3 concentration in the FW samples. Other factors, such as temperature and the presence of other oxidant demands like natural organic matter, may have contributed to the observed range in total Cl2 residuals.
A water treatment plant (e.g., Systems A-D) that feeds a constant free Cl2 dose but experiences large, temporal free NH3 concentration fluctuations may experience a variable Cl2 residual type and concentration. As an illustration, Fig. 7 shows a theoretical breakpoint curve for System A, which has pH 7.8 and a 465 mg/L as CaCO3 alkalinity, assuming that a constant free Cl2 dose of 4 mg Cl2/L is applied while the free NH3 concentration changes from 0.25–4 mg N/L at 1 hour after free Cl2 addition (Wahman 2018). For an initial free NH3 concentration between 0.3 mg N/L to 1 mg N/L, the simulated total Cl2 residual varies from 0.3 mg Cl2/L to 4 mg Cl2/L and switches from being present as free Cl2 to monochloramine even as the free Cl2 dose remains constant at 4 mg Cl2/L. AS free NH3 concentrations at representative points in the service cycle are indicated on the total Cl2 line in Fig. 7. The actual initial free NH3 concentration simulated in the breakpoint curve is unknown because the AS sample does not include bypass water, and the FW sample was collected after chlorination, at which point total NH3 may have been destroyed. Nevertheless, System A may operate in all regions of the breakpoint curve, including at the breakpoint, over the course of one day. The theoretical breakpoint curve helps explain the variability in total Cl2 residuals observed in Fig. 6A and illustrates the challenges of maintaining a target Cl2 residual when the initial free NH3 concentration fluctuates.
Fig. 7.
Theoretical breakpoint curve 1 hour after free chlorine addition for System A: pH 7.8, 465 mg/L as CaCO3 alkalinity, and 4 mg Cl2/L free chlorine dose. Representative points in the service cycle are indicated by X. Ideal plug flow and chemical mixing conditions are assumed.
Similar to System A, the AS sample total NH3 concentrations in Systems B-D that were measured during both the routine sampling events (Fig. 2) and the service cycle profiles (Fig. 4) span 0.3–1 mg N/L, over which the Cl2 residual concentration and speciation can change. The FW total NH3 concentrations tended to be greater in Systems B-D as compared to System A (Fig. 2), but it is possible that they sometimes operated near the breakpoint and at different points along the breakpoint curve.
Operating near the breakpoint is a concern for multiple reasons. First, adequate disinfection might not be achieved. Second, higher concentrations of regulated and unregulated disinfection byproducts may be formed near and past the breakpoint (Schreiber and Mitch 2007, Stefán et al. 2019). Third, the system can switch from operating with a monochloramine residual to a free Cl2 residual, which creates different oxidation reduction potentials and can cause lead release (Copeland and Lytle 2014, Edwards and Dudi 2004). The preferred operating region for chloramine systems is at a Cl2:N mass ratio between 4.5:1 and 5:1 (i.e., before the breakpoint) so that monochloramine is the predominant species and the resulting free NH3 concentration is low to minimize the potential for nitrification (AWWA 2013).
Different concerns arise when the FW free NH3 concentration is high. In the four systems presented here, IX softeners sometimes functioned to increase total NH3 within the plant, resulting in FW sample total NH3 concentrations greater than in the RW sample. As shown in Fig. 7, the free NH3 concentration remaining in solution after chloramination increases as the initial free NH3 concentration increases. The FW free NH3 concentration at Systems B-D often were > 1 mg N/L (Table 2). Free NH3 serves as a growth substrate for biomass to persist in biofilm on pipe walls or in sediment, leading to recurring nitrification episodes (Liu et al. 2019, Pressman et al. 2012). Nitrification in distribution systems can create a host of problems, including loss of total Cl2 residual, regrowth of microorganisms, corrosion, and elevated levels of NO2− (AWWA 2013, Pressman et al. 2012, Wilczak et al. 1996, Zhang et al. 2009).
Thus, operating with a fluctuating free NH3 concentration could be disruptive to the distribution system if not adequately addressed (e.g., by adjusting the Cl2 dose), which in practice is very challenging. A better practice would be to operate the plant to achieve a more consistent FW free NH3 concentration or remove the free NH3 prior to IX softening, for instance through biological treatment.
4. Conclusions
The current study of four full-scale water treatment plants demonstrates that effluent peaking of total NH3 can occur from IX softeners, resulting in a wide range of FW total NH3 concentrations, including concentrations greater than the RW total NH3. The variable total NH3 concentration complicates chlorination and sometimes causes very low total Cl2 residuals. Additionally, it can lead to conditions that may promote increased nitrification in the distribution system. IX softeners are commonly used in groundwater systems in the U.S., but when the groundwater has elevated free NH3 levels, the IX softener can both remove and subsequently release free NH3. This change in treatment performance can occur over short time scales on the order of hours, making it difficult to achieve consistent FW quality. Although free NH3 is not a health concern itself, it impacts disinfectant form and concentration and water quality in the distribution system. Thus, it should be considered in the design and operation of IX softening systems. Management strategies to improve FW quality and increase stability in the distribution system include (beginning with the easiest to implement and progressing towards a more preferred permanent solution): monitoring free NH3, regenerating the IX softeners more frequently based on the effluent free NH3 concentration, implementing staggering and blending strategies to maintain a consistent FW free NH3 concentration, or including an alternative free NH3 removal process, such as biological treatment, prior to IX softening.
Acknowledgements
The authors wish to acknowledge Keith Kelty (retired), Maily Pham, and Eugenia Riddick from the EPA for analyzing water samples. We would also like to acknowledge Rich Weisman and Dan Williams from the EPA for their thorough reviews. We would also like to acknowledge Matthew Pinelli with Oak Ridge Institute for Science and Education for providing public water system data from the SDWIS database. We would like to thank Steve Johnson with Illinois EPA (retired) for connecting us with the participating utilities. Lastly, we would like to thank the participating utilities for collecting samples.
Footnotes
Declaration of Competing Interest
The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.
Notice
The information in this article has been reviewed in accordance with the U.S. Environmental Protection Agency’s (EPA’s) policy and approved for publication. The views expressed in this article are those of the authors and do not necessarily represent the views or the policies of EPA. Any mention of trade names, manufacturers, or products does not imply an endorsement by the U.S. Government or EPA; EPA and its employees do not endorse any commercial products, services, or enterprises.
References
- APHA, AWWA and WEF, 2005. Standard Methods for the Examination of Water and Wastewater, 21st ed Washington. [Google Scholar]
- AWWA, 2013. Manual of Water Supply Practices. Denver, CO, M56, AWWA. [Google Scholar]
- Beler-Baykal B, Cinar-Engin S, 2007. Ion exchange with clinoptilolite to control ammonium in drinking water. Journal of Water Supply: Research and Technology-Aqua 56 (8), 541–547. [Google Scholar]
- Bremer PJ, Webster BJ, Wells DB, 2001. Biocorrosion of copper in potable water. J. - Am. Water Works Assoc. 93 (8), 82–91. [Google Scholar]
- Chen AS, Wang L, Lytle DA, Sorg TJ, 2018. Arsenic/iron removal from groundwater with elevated ammonia and natural organic matter. J. - Am. Water Works Assoc. 110 (3), E2–E17. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Clifford D, Subramonian S, Sorg TJ, 1986. Removing dissolved inorganic contaminants from water. Environ. Sci. Technol. 20 (11), 1072–1080. [Google Scholar]
- Clifford DA, 1982. Multicomponent ion-exchange calculations for selected ion separations. Industrial & Engineering Chemistry Fundamentals 21 (2), 141–153. [Google Scholar]
- Colella C, 1996. Ion exchange equilibria in zeolite minerals. Mineralium Desposita 31 (6), 554–562. [Google Scholar]
- Copeland A, Lytle DA, 2014. Measuring the oxidation-reduction potential of important oxidants in drinking water. J. - Am. Water Works Assoc. 106 (1), E10–E20. [Google Scholar]
- de Vet WW, Kleerebezem R, van der Wielen PW, Rietveld LC, van Loosdrecht MC, 2011. Assessment of nitrification in groundwater filters for drinking water production by qPCR and activity measurement. Water Res. 45 (13), 4008–4018. [DOI] [PubMed] [Google Scholar]
- Edwards MA, Dudi A, 2004. Role of chlorine and chloramine in corrosion of lead-bearing plumbing materials. J. - Am. Water Works Assoc. 96 (10), 69–81. [Google Scholar]
- Ghurye GL, Clifford DA, Tripp AR, 1999. Combined arsenic and nitrate removal by ion exchange. J. - Am. Water Works Assoc. 91 (10), 85–96. [Google Scholar]
- Great Lakes-Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, 2012. Interim Standard - Use of Chloramine Disinfectant for Public Water Supplies. Health Research Inc., Albany, NY. [Google Scholar]
- Illinois Administrative Code tit. 35, §604.725 (2019). [Google Scholar]
- Liu H, Wahman DG, Pressman JG, 2019. Evaluation of monochloramine and free chlorine penetration in a drinking water storage tank sediment using microelectrodes. Environ. Sci. Technol. 53 (16), 9352–9360. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Logsdon GS, Sorg TJ, Clark RM, 1990. Capability and cost of treatment technologies for small systems. J. - Am. Water Works Assoc. 82 (6), 60–66. [Google Scholar]
- Lytle DA, Sorg TJ, Wang L, Muhlen C, Rahrig M, French K, 2007. Biological nitrification in a full-scale and pilot-scale iron removal drinking water treatment plant. Journal of Water Supply: Research and Technology-Aqua 56 (2), 125–136. [Google Scholar]
- Lytle DA, White C, Williams D, Koch L, Nauman E, 2013. Innovative biological water treatment for the removal of elevated ammonia. J. - Am. Water Works Assoc. 105 (9), E524–E539. [Google Scholar]
- Lytle DA, Williams D, Muhlen C, Pham M, Kelty K, Wildman M, Lang G, Wilcox M, Kohne M, 2015. The full-scale implementation of an innovative biological ammonia treatment process. J. - Am. Water Works Assoc. 107 (12), E648–E665. [Google Scholar]
- Odell LH, Kammeyer GJ, Wilczak A, Jacangelo JG, Marcinko JP, Wolfe RL, 1996. Occurrence of nitrification in chloraminated distribution systems. J. - Am. Water Works Assoc. 88 (7), 86–98. [Google Scholar]
- Park S, Bae W, Rittmann BE, 2010. Operational boundaries for nitrite accumulation in nitrification based on minimum/maximum substrate concentrations that include effects of oxygen limitation, pH, and free ammonia and free nitrous acid inhibition. Environ. Sci. Technol. 44 (1), 335–342. [DOI] [PubMed] [Google Scholar]
- Pebesma E, 2018. Simple Features for R: Standardized support for spatial vector data. The R Journal 10 (1), 439–446. [Google Scholar]
- Pressman JG, Lee WH, Bishop PL, Wahman DG, 2012. Effect of free ammonia concentration on monochloramine penetration within a nitrifying biofilm and its effect on activity, viability, and recovery. Water Res. 46 (3), 882–894. [DOI] [PubMed] [Google Scholar]
- R Core Team, 2020. R: A Language and Environment for Statistical Computing, R Foundation for Statistical Computing. Vienna, Austria. [Google Scholar]
- Read EK, Carr L, De Cicco L, Dugan HA, Hanson PC, Hart JA, Kreft J, Read JS, Winslow LA, 2017. Water quality data for national-scale aquatic research: The Water Quality Portal. Water Resour. Res. 53 (2), 1735–1745. [Google Scholar]
- Rittmann BE, Snoeyink VL, 1984. Achieving biologically stable drinking water. J. -Am. Water Works Assoc. 76 (10), 106–114. [Google Scholar]
- Schreiber IM, Mitch WA, 2007. Enhanced nitrogenous disinfection byproduct formation near the breakpoint: Implications for nitrification control. Environ. Sci. Technol. 41 (20), 7039–7046. [DOI] [PubMed] [Google Scholar]
- Smith RM, Martell AE, Motekaitis RJ, 1996. Critical Stability Constants of Metal Complexes Database. National Institute of Technology and Standards, Gaithersburg, MD. [Google Scholar]
- Speitel GE Jr., Kannappan R, Bayer BM, 2011. The nitrification index: A unified concept for quantifying the risk of distribution system nitrification. J. - Am. Water Works Assoc. 103 (1), 69–80. [Google Scholar]
- Stefán D, Erdélyi N, Izsák B, Záray G, Vargha M, 2019. Formation of chlorination by-products in drinking water treatment plants using breakpoint chlorination. Microchem. J. 149, 104008. [Google Scholar]
- Suffet IH, Corado A, Chou D, McGuire MJ, Butterworth S, 1996. AWWA taste and odor survey. J. - Am. Water Works Assoc. 88 (4), 168–180. [Google Scholar]
- U.S. Census Bureau (2020). Census Geocoder. https://geocoding.geo.census.gov/. Accessed on December 4, 2020.
- U.S. Environmental Protection Agency USEPA, 1983. Methods for chemical analysis of water and wastes. Washington D.CEPA-600/14-79-020. [Google Scholar]
- U.S. Environmental Protection Agency USEPA, 1994. Methods for the determination of metals in environmental samples. Washington D.C., EPA-600/14–91-010. [Google Scholar]
- U.S. Environmental Protection Agency USEPA, Washington D.C., EPA-822-F-18-001, 2018. Drinking Water Standards and Health Advisories Tables. Office of Water. [Google Scholar]
- U.S. Environmental Protection Agency USEPA (2020). SDWIS Federal Reports Search. http://ofmpub.epa.gov/apex/sfdw/f?p=sdwis_fed_reports_public. Accessed on December 1, 2020.
- Wahman DG, 2018. Web-based applications to simulate drinking water inorganic chloramine chemistry. J. - Am. Water Works Assoc. 110 (11), E43–E61. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Wang L, Chen AS, Sorg TJ, Fields KA, 2002. Field evaluation of As removal by IX and AA. J. - Am. Water Works Assoc. 94 (4), 161–173. [Google Scholar]
- Wang Y, Kmiya Y, Okuhara T, 2007. Removal of low-concentration ammonia in water by ion-exchange using Na-mordenite. Water Res. 41 (2), 269–276. [DOI] [PubMed] [Google Scholar]
- Wickham H, Averick M, Bryan J, Chang W, D’Agostino McGowan L, François R, Grolemund G, Hayes A, Henry L, Hester J, Kuhn M, Pedersen TL, Miller E, Bache SM, Müller K, Ooms J, Robinson D, Seidel DP, Spinu V, Takahashi K, Vaughan D, Wilke C, Woo K, Yutani H, 2019. Welcome to the tidyverse. Journal of Open Source Software 4 (43), 1686. [Google Scholar]
- Wilczak A, Jacangelo JG, Marcinko JP, Odell LH, Kirmeyer GJ, 1996. Occurrence of nitrification in chloraminated distribution systems. J. - Am. Water Works Assoc. 88 (7), 74–85. [Google Scholar]
- Zhang Y, Griffin A, Rahman M, Camper A, Baribeau H, Edwards MA, 2009. Lead contamination of potable water due to nitrification. Environ. Sci. Technol. 43 (6), 1890–1895. [DOI] [PubMed] [Google Scholar]