Abstract
Since the World Health Organization announced the COVID-19 pandemic, indoor airflows became a synonym for virus super-spreaders and the focus point for the scientific community and professional associations across the globe, disrupting all daily life dimensions. Europe's quick response to control the disease led the REHVA board to address mitigation guidelines, reassessed by each member association's following national specifics. The present study aims to quantify the energy consumption and CO2 emissions of “large office” buildings in top-five European economies under the COVID-19 guidelines under the post-pandemic telework forecast. Methodology resorted to a standard model under Building Energy Simulation assessment to compare prior and posterior scenarios. The latter displays a tendency to increase energy and CO2 emissions in all locations, in the first form 10.18% (Rome) to 69.48% (Paris); and second 5.80% (Rome) and 120.61% (Paris), which will affect national energy production and imports, urban pollution and business competitiveness. On a different scope, future HVAC guidelines need to address the incoming figures, particularly in highly dense urban areas. Also, to comply with the goals set by the Paris Accord.
Keywords: Covid-19, Guidelines, Europe, Office buildings, RHEVA, Energy efficiency, Energy consumption, CO2 emissions
Terminology
- AHU
Air Handling Unit
- AICVF
Association des Ingénieurs et techniciens en Climatique, Ventilation et Froid
- AiCARR
Associazione Italiana Condizionamento dell'aria, Riscaldamento Refrigerazione
- ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers
- ATECYR
Asociación Técnica Espańola de Climatización y Refrigeración
- BACS
Building Automation and Control System
- BEM
Building Energy Model
- BES
Building Energy Simulation
- CAR
Chinese Association of Refrigeration
- CIBSE
Chartered Institution of Building Services Engineers
- CO2e
CO2 emissions
- DCV
Demand Controlled Ventilation
- ECDC
European Centre for Disease Prevention and Control
- EU-OSHA
European Agency for Safety and Health at Work
- EUI
Energy Use Intensity
- HEPA
High Efficiency Particulate Air (filter)
- HVAC
Heating, Ventilation, and Air Conditioning
- IAQ
Indoor air quality
- PNNL
Pacific Northwest National Laboratory
- PPM
Parts per million (mg/kg)
- REHVA
Federation of European Heating, Ventilation, and Air Conditioning Associations
- SBS
Sick Building Syndrome
- SHGC
Solar Heat Gain Coefficient
- SWH
Service Water Heating
- UVGI
Ultraviolet Germicidal Irradiation
- U-value
Rate of heat transmission through a unit area of a constructive solution (W/(m2·k))
- WHO
World Health Organization
- VDI-TGA
VDI Verein Deutscher Ingenieure e.V.
Introduction
The SARS-CoV-2 infection spreads as typical influenza. People infected with COVID-19 release compromised droplets by breathing or touching surfaces spreading the disease. The virus tends to persist for extended periods suspended on air upon low ventilation rates and on surfaces due to poor cleaning (Rivera et al., 2020). The severity of the disease has a lower impact on people under 40 years old, the leading working force group in Europe; people over that age or with debilitated immune systems can suffer severe health consequences and even die (World Health Organization, 2021).
The COVID-19 pandemic guidelines
On the verge of lifting lockdown restrictions, the European governments raised doubts about the best practices to follow in HVAC systems to make healthier and safer working environments and prevent the virus dissemination while complying with commitments and policies to lessen energy consumption and CO2 emissions (CO2e). The concerns fell on large buildings with a vast concentration of people, e.g., offices, malls, medical facilities, especially ensuring health and safety through HVAC systems tuning. The burden was on the shoulders of the major international and European technical organizations and professional associations, who made a continuous effort to publish updated knowledge on mitigation guidelines (COVID-19 guidelines). The most relevant field works driven from the Sick Building Syndrome (SBS) and SARS-CoV-1, and now SARS-CoV-2 recent studies, as follows:
-
•
February 3, 2020, Chinese Association of Refrigeration (CAR), “Suggestions on the safe use of air conditioning (heating) in response to the new corona pneumonia epidemic after work during the Spring Festival;”
-
•
March 17, 2020, Federation of European Heating, Ventilation and Air Conditioning (REHVA), “How to operate HVAC and other building service systems to prevent the spread of the coronavirus (SARS-CoV-2) disease (COVID-19) in workplaces;”
-
•
March 19, 2020, World Health Organization (WHO), “Getting your workplace ready for COVID-19: How COVID-19 spreads”; and,
-
•
May 18, 2020, American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) “The ASHRAE's epidemic task force & ASHRAE guidance for protecting building occupants from covid-19 and other infectious diseases”.
The study resorts to the above measures and recommendations for general office buildings operation and work environments framed by international institutions in five European economies: Germany (DE); United Kingdom (UK); France (FR); Italy (IT); and Spain (SP).
Europe's leading institutions' guidelines against COVID-19 dissemination
The REHVA, European Agency for Safety and Health at Work (EU-OSHA), European Centre for Disease Prevention and Control (ECDC), and WHO published guidelines to set up the new day-to-day, primarily to guarantee safety, health, and infection from the virus spread limited to public gatherings, and remote work (see Appendix A, Table A1).
REHVA started to publish by mid-March 2020 (1.0), followed by updates in April (2.0) and August (3.0). The fourth version focused on the building's safe reopening, setting ventilation aspects, space/circulation use, and other equipment related to the mitigation guidelines. The latest update (4.1), published on April 15, 2021, summarizes all versions, requiring:
-
-
one hour of ventilation before and after building use capable of renewing the indoor air three times;
-
-
recommends adjusting the CO2 to 550 ppm under controlled ventilation systems nominal speed; and,
-
-
demands the adding permeable membranes to heat exchangers and enthalpy plate exchangers in heat recovery systems (Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021).
The ECDC took the effort to publish guidelines addressing daily life aspects and work environment settings related to HVAC systems and AHU to mitigate COVID-19 spreading, from planes to buildings (European Centre for Disease Prevention and Control (ECDC), 2020), in line with all countries' strategies. All guidelines primarily focus on the “ventilation” settings, along with “open-window” demands, resort to the highest fresh air intake at maximum airflow rate, and air cleaning with improved filter racquets (Rivera et al., 2020). Notwithstanding special measures, guidelines promote “social distancing” rules and telework policies, user hygiene, and other sanitizing routines.
The selected European countries' pandemic guidelines
Although ECDC (European Centre for Disease Prevention and Control (ECDC), 2020) and EU-OSHA (European Agency for Safety and Health at Work (EU-OSHA), 2020) members, the assessed countries do not equally comply despite all being safety- and health-focused. All in line with local /national engineering association recommendations, some are fulfilled by non-EU institutions guidelines, like WHO and ASHRAE, (see Table A2, Appendix A), such as:
-
•
Germany, DE - VDI Verein Deutscher Ingenieure e.V. (VDI-TGA): “ISO/PAS 45005:2020-12 - Occupational health and safety management - General guidelines for safe working during the COVID-19 pandemic”, December 2020 (International Standard Organization (ISO), 2020);
-
•
England, UK - Chartered Institution of Building Services Engineers (CIBSE): “COVID-19 Ventilation Guidance. Version 4”; October 2020 (Chartered Institution of Building Services Engineers (CIBSE), 2020);
-
•
France, FR - Association des Ingénieurs et techniciens en Climatique, Ventilation et Froid (AICVF): “Document guide REHVA COVID-19 V2. Comment faire fonctionner et utiliser les installations sanitaires et de conditionnement des bâtiments afin d'éviter la propagation du coronavirus (Covid-19) et du virus (SRAS-CoV-2) sur les lieux de travail”, April 2020 ( Association des Ingénieurs et techniciens en Climatique, 2020)1 ;
-
•
Italy, IT - Associazione Italiana Condizionamento dell'aria, Riscaldamento Refrigerazione (AiCARR): “AiCARR position on HVAC system operation during SARS-COV-2-19 emergency”, April 2020 (Associazione Italiana Condizionamento dell`aria, 2020a); “Protocol for risk reduction of SARS-CoV2-19 diffusion with the aid of existing air conditioning and ventilation systems”, March 2020 (Associazione Italiana Condizionamento dell`aria, 2020b); and,“Gli impianti e la diffusione del SARS-CoV2-19 nei luoghi di lavoro”, February 2020 (Associazione Italiana Condizionamento dell`aria, 2020); and;
-
•
Spain, SP – Asociación Técnica Espańola de Climatización y Refrigeración (ATECYR): “Guía de ATECYR de recomendaciones de operación y mantenimiento de los sistemas de climatización y ventilación para edificios de uso sanitario para la prevención del contagio por COVID-19”, May 2020 (Asociación Técnica Española de Climatización y Refrigeración (ATECYR), 2020).
Overall, the mentioned guidelines present a set of common recommendations for all countries focusing on natural ventilation increase with open windows policies; frequent maintenance and filtration upgrade of HVAC systems; increase of fresh air intake by mechanical means; avoid or decrease air recirculation and heat recovery; and advise for social distancing and indoor occupancy reduction. However, they differ between countries in specific parameters.
The UK and IT associations push to increase airflow rates and halt recirculation. The AICARR (IT) takes a general approach, underlining the importance of cleaning and sanitizing filters and humidification coils, switching off the system in the last 10 min before procedures, pushing for opening windows, and shutting doors to avoid cross-ventilation under favorable weather. The CIBSE (UK) is technical-oriented, focusing on HVAC recirculation rates and airflow settings. France and Spain's associations opt for a similar strategy. The AICVF (FR) has a cross approach, adding the open-window timeframe from 10 to 15 min twice a day and limiting the airflow speed to 0.4 m/s, while the ATECYR (SP) opt for a generic stand, avoiding setting limits, pushing instead for an additional air flush before and after building use plus vacant hours, sets ventilation levels for toilets, frame heat recovery leaks, demands fans spin and temperatures control continuously to avoid dew points. The VDI-TGA (DE) differs from the rest by publishing “natural” and “mechanical” ventilation guidelines in different sections. On natural timeframes, windows open for 3 min in winter, 10 min in summer, and 20 min to ventilate spaces between occupation and assesses indoor CO2 levels due to a raised fresh air mixture. On mechanical, recommends HEPA portable filters and UV-C radiation to sanitize AHU filters and devices surfaces (European Centre for Disease Prevention and Control (ECDC), 2020). The latter aligns with the ASHRAE Epidemic Task Force document (American Society of Heating, 2021a). Table A2 in Appendix A provides a detailed description of the recommendations per country.
Pre- and post-COVID-19 operation guidelines on ventilation
REHVA is a non-mandatory European entity represented by national associations to enable knowledge sharing and draft broader guidelines. Each member has the liberty to add climate and energy specifics. Table 1 (below) shows REHVA 4.1 (Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021) and WHO (World Health Organization (WHO), 2021) identical guidelines on ventilation main aspects. As the pandemic unfolds, guidelines went into a detail and refinement process, contributing to other guidelines updates, e.g., REHVA's CO2 monitoring, HEPA filters, and standard airflow rates.
Table 1.
REHVA (4.1) and WHO (2021) guidelines (Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021; World Health Organization (WHO), 2021).
| Operation | REHVA | WHO | ≠ | |
|---|---|---|---|---|
| Ventilation | Outside Air (OA) | 100% | 100% | = |
| Re-entrainment | 0% | 0% | = | |
| ERV/Exhaust Air Transfer Rate (EATR) – EN 16798-3:2017 | >5% | >3% | 2% | |
| Outdoor air rate per person (l/s) – EN 16798-3:2017 | a/8 – 10 - CO2 < 400 ppm | 10 | 0–2 | |
| Outdoor air rate per area (l/s) | 4 - CO2 < 550 ppm | – | – | |
| IAQ monitoring systems | yes | yes | = | |
| Air distribution | Mechanical | no interchange of occupants between rooms | no interchange of occupants between rooms | = |
| Natural (+ Mechanical) | 15 min between use | 15 min between use | = | |
| Unoccupied times | 2 h at normal speed before and after CO2 < 550 ppm | 2 h at normal speed before and after | – | |
| Intake / Exhaust safe distance (people and animals) | – | 2 m / 4 m | – | |
| Filtration and Disinfection | Outdoor air filter – EN ISO 16890-1:2016 | ePM1 80% (F8) | MERV 14/F8 filters | = |
| HEPA Filter | Yes (2–5 ACH) | Yes | – | |
| UVGI (in-duct and upper-room) | UV-C | – | – | |
| Indoors settings | Temperature Range (Brelih, Mar. 2013) (a) | 20–26 °C (EN 15251:2007)/- | – | – |
| Relative Humidity Range (Brelih, Mar. 2013) (a) | 30% r.h.in winter/- 70% r.h.in summer/- | – | – |
(a) REHVA guideline mentions the “temperature” and “relative humidity” issues as non-relevant for SARS-COV-2 dissemination. Therefore, the authors adopted the values mentioned by Brelih (2013) on REHVA Journal Vol 50/2.
Depends on the assessed country, see Appendix A, Table A2.
Remote work in Europe's post-COVID-19
Today, company leaders reflect on synergies to reduce running costs while ensuring the workers' comfort — telework trends to address both goals while realizing space to ensure workplace health and safety. Auditors of leading companies step up to survey national markets on telework engagement in the post-COVID-19 era. During the pandemic in Europe, the IWG Global Workspace Survey/Survey Snapshot published a report in March 2020, interviewing 15,000 businesspeople across 80 nations about the critical drivers for flexible work. The results show that half of the workforce spends 2.5 labor days in the office; where 85% confirm a rise in productivity has flexibility result; 4/5 confirm readiness to work under a hybrid week; 65% of businesspeople agree in model capacity to reduce logistics costs; 65% of interviewed concluded productive increases in tailored work environment align with workers expectations and needs (IWG International Workplace Group, 2019) (see Chart 1 below).
Chart 1.
Pre-COVID-19 - Assessed countries towards flexible work (IWG International Workplace Group, 2019).
On November 23, 2020, the McKinsey Global Institute published a report on hybrid work after the lockdowns concerning 2000 tasks under 800 jobs in nine countries, including the targeted countries (except Italy. The study concludes that hybrid work will not be universal, somewhat reserved to the highly educated depending on online terminals, favoring (>50%) finance and insurance (US 76–86%), management (US 68–78%), scientific and technical support (62–75%), information technology and telecommunications (US 58–69%), and education (US 33–69%). Overall, it will first reflect on the developed economies followed by the emerging markets (Lund et al., 2020) (see Chart 2 below).
Chart 2.
Post-COVID-19 - Assessed countries for the hybrid work model (Lund et al., 2020).
Lastly, in August 2020, the Joint Research Centre of the European Commission and Eurofound studied the potential of telework in Europe (excluding the UK) and the risk of digital asymmetries, and delivery similar figures: DE 38%; FR 39%; IT 37%; and SP 34% (Sostero et al., 2020).
Research gap and purpose
As restrictions ease, COVID-19 experiences should tackle the upcoming social development or crisis. Likewise, it guarantees the economy's growth and population's well-being and helps countries comply with international commitments to reduce energy consumption and increase efficiency. The COVID-19 guidelines design paves the road to telework/hybrid work, framing the “new normal,” with health and safety in mind (Pang, 2020). Nevertheless, researchers empirically agree on building overconsumption under COVID-19 guidelines, opening the field to quantification (American Society of Heating, 2021a; American Society of Heating, 2020; Cutler & Summers, 2020; Mo et al., 2020; Nadel, 2020; Taylor Engineering, 2020).
European commerce and services buildings take, on average, 40% of all intensive energy when compared to residential, the latter between 250 kWh/m2 to 180 kWh/m2( 2 ). Therefore, any ventilation and acclimatization change impacts consumption by large. Furthermore, if space “per person” increases to ensure occupants' social distance according to Europe's 25–40% telework predictions on full running building, it will press all energy consumption, although compensated by the cuts in commuting (Sostero et al., 2020).
Ultimately, the authors develop a method to quantify the energy-related to COVID-19 mitigation guidelines (usable energy consumption and CO2e — percentual and absolute values) on “large offices” HVAC systems framed by the forecasted telework to assess countries and users' desirable safety and health. The outcomes show the tendency to energy overconsumption, which should trigger regulators' awareness of future HVAC operation settings in working environments under the research framed context.
Literature review
HVAC systems have the capacity to blow air at high rates promoting virus propagation, as concluded in China, at Wuhan's restaurants due to low airflow rate, and in South Korea, at a local call center due to related to air recirculation and filtration efficiency (Park et al., 2020). Guo et al. (Guo et al., 2021) and ASHRAE (American Society of Heating, 2021b) synthesized and detailed information on virus propagation through the ventilation system. The ASHRAE's “Epidemic Task Force. Building Readiness” (American Society of Heating, 2021a) guideline become a reference by sharing complex HVAC's systems and AHU's settings information on a user-friendly webpage. Elsaid & Ahmed (2021) underlined the importance of indoor air quality and its impact on long-term health, which WHO started to rose in the 1980s, mainly related to climate change, temperatures rising and air pollution, and HVAC systems incorrect use and maintenance: ideal conditions to virus spreading across rooms, especially considering its airborne virus nature. The Epidemic Task Force study suggests in general rooms: avoid air recirculation; the use of 100% outside air; >5-meter distance between exhaust and intake; to halt crossflows between rooms; the introduction of nanofibrous air filters instead of HEPA's; rooms and restrooms under negative pressure (>2.5 Pa or, ideally, >5 Pa); to limit pollution particles in filters; to regulate corridors use; >12 times air renovation per hour under 400 PPM; to set room temperature between 25° and 27 °C at 50% to 70% relative humidity, and; underlines the efficacy of UVGI on filters. In high-risk rooms, advises: higher rates of ventilation when occupied and lower when not; the use of filters > MERV14, F8, or ePM1 (0.1–1.0 mm) capable of removing 98% of airborne particles; the cleaning of HVAC systems (1% hypochlorite); to avoid free fans; to keep temperature > 21 °C and 40% of relative humidity; and AHU sanitation under 75 °C for 45 min plus 15–20 min UVGI to ensure tight maintenance, properly residuals treatment and control HVAC parameters (Elsaid & Ahmed, 2021).
Zheng et al. (2021) assessed the virus transmission in enclosed spaces by comparing the recommendations of HVAC guidelines and their impact on energy efficiency and concluded the tendency to main measurements converge, as increasing outdoor air ratio, operation schedules extension, balance negative and positive pressures to avoid cross airflows plus HEPA filters and UV-C. The same authors ran a case study in China and realized an increase of 128% in HVAC energy consumption. Besides, they suggest indoor air quality (IAQ) control and infection risks assessment, as followed by mentioned entities through particles per million (PPM) monitoring. Cortiços & Duarte assessed the energy consumption, CO2e, and operations costs under pre- and post-COVID-19 scenarios on the US high-rise office building and concluded that post figures do not always surpass the previous. They depend on climate conditions where zones above “mixed-humid” classification tend to pressure the relative energy use intensity by 21.72% on average and below the trend inverts by 11.92% on average (Cortiços & Duarte, 2021). Wang & Wang (2020) assessed the carbon dioxide emissions and energy efficiency of COVID-19 impact and concluded that developed countries would reassure the international commitments to control CO2 with a higher success than the developing countries. Due to the latter older production technologies dependency, when compared to the ongoing global economic evolution, e.g., free trading, telework, and e-commerce. Nevertheless, individuals with higher incomes account for higher CO2e, followed by those of middle-income. Zhang et al. (2021) studied the COVID-19 impacts on energy variables: consumption, market, renewables, climate effects, and policy. As lockdowns shifted daily life, halting commuting/transport and C&S buildings use to residential, the authors raise the possibility of energy higher prices due to unbalance between demand and consumption. Pan et al. (2021) rethought the redesign of future HVAC systems and concluded that COVID-19 mitigation guidelines would ensure future workplace pandemic readiness where buildings should integrate the engineering's training and practice on efficient energy use and the users' comfort by maintaining outdoor higher air rate, design flexibility, backup fans, the possibility to disengage the heat recovery, and extra filtration options. Guo et al. (2021) compared the US, Europe, Japan, and China guidelines, and concluded by the persistency of three measures, namely the resort to outdoor ventilation (100%), increased airflow (≥10 l/s), and upgraded filtration. REHVA and ASHRAE add two hours of pre-and post-occupation air flush, plus HEPA filters, air cleaners, filters maintenance updated, and negative pressure in restrooms. Although, REHVA does not acknowledge temperature or relative humidity changes. The Society of Heating, Air-Conditioning, and Sanitary Engineers of Japan (SHASE) stands out by setting temperatures (17–28 °C) and relative humidity (40–70%), among others. Heat recovery leakage has different figures across all guidelines. CAR alone advises against the use of rotary heat exchangers. Brugger et al. (2021) realize that efficiency is critical to reduce the energy demand by 2050 based on simulations to measure energy consumption patterns. The author elect's digitalization, quality standards, and craft policies to support energy efficiency and improve society's life quality, especially work and leisure. Drawing the worst scenario with emissions rising 40%, and best reducing 67%, according to 2021 figures, both by 2050. Moeckel (2017) projected the telework impacts and concluded its dependency on powerful internet connections through microfiber and satellite. Technologies will change transportation needs and land use upon new applications, such as online cyber gloves surgical interventions. The pandemic's lessons will transform the workplace by empowering telework, disrupting personal/worker relations, social distancing and safety, and supporting healthier working environments.
The Europe Commission's Joint Research Group (JRC) (2021) published a study on work conditions before and after COVID-19 and forecasted the telework impact. It underlines the experience success and the engagement of institutions, services, and employees, despite the difference between member states' levels of digitalization and infrastructure. The experience produced positive outcomes, which helped frame telework in the EU, although the “long-term” mode stills raise questions. Nevertheless, the European Commission started to design policies to promote telework to tackle contemporary problems, e.g., climate change, energy harvesting/production, and pollution. The document quotes Eurofound (2020) that 40% of labor work will be performed under remote work. However, JRC does not surpass 25% forecasts; both compared to 15% before pre-COVID-19 (Milasi et al., 2021). The European Parliament Research Service under Kiss (2021), triggered by the pandemic, assessed 24 initiatives to regulate future telework across member-states, which can help to mitigate state-level energy management and the global climate crisis. The stay-at-home orders provided governments with the knowledge to mitigate today's problems while promoting higher safety and healthy environments on universal health care costs. It also underlines the need for infrastructure renovation to support incoming digitalization and automation, empowered by artificial intelligence, and continuous professional education and staff technical training. Moreover, it finalizes by requesting member-states to prepare to deal with future threats, as COVID-19 virus and strains. The hybrid work model will likely become the “new normal,” working some days at home and others at the workplace, probably without an individualized station/place. The gathered knowledge will help companies' managers to trust and promote remote work, which releases space to support social distance, safety, and healthy environments for users (Hogan et al., 2020).
Finally, the EU signed and ratified the Paris Accord. The post-COVID-19 lessons inevitable pressures the energy supply; after the drop by (−)4%, in 2020 rose by (+)0,5% (2021 comparing e to 2019 figures) (Sönnichsen, 2021). The knowledge economies like Europe (1%) and the US (0.75%) invested in renewables to compensate for the growing energy demand, but even more in China (1.85%) and India (0.65%) (2021 relative to 2019 levels) (Statista, 2021).
Methodology
Energy simulation process
The team assessed the energy performance under a Building Energy Simulation (BES) (Cipriano et al., 2015; Hong et al., 2017; Shiel et al., 2018) on a Building Energy Model (BEM) (see Table 3 and Fig. 1 below) to compare the disrupted performance in COVID-19 HVAC operating conditions before (pre—C19) and after (post-C19) the pandemic.
Table 3.
Standard EU “large office” building model formal features (Kemna, 2014; Stefanutti, 2016).
| Model features | |
|---|---|
| Height | 36 m |
| Volume | 45,000 m3 |
| Gross area | 15,042 m2 |
| Floor area | 1253.50 m2 |
| Floor height | 3 m |
| Envelope surface area | 9929.5 m2 |
| Opaque surface area | 8194.30 m2 |
| Glazed surface area | 1735.2 m2 |
| Surface/volume ratio | 0.25 |
Fig. 1.
Isometric perspective of the standard EU “large office” BEM geometry. Modeled by the authors following Kemna description (Kemna, 2014; Stefanutti, 2016).
The study resorts to cove.tool web-based software (cove.tool, 2021). The cove.tool is a LEED-approved energy simulation software with an intuitive interface that has proven to aid field experts in designing strategies targeting energy efficiency in new and existing buildings with more than 10,000 accesses during working hours.3 According to Forouzandeh et al. (Forouzandeh et al., 2021) study on energy simulation software, cove.tool falls into the Normative Calculation Method category, which estimates energy consumption using the statistical method with an empirical or pre-simulated dataset. Plus, the tool is compliant with the EN 156034 and ISO 137905 (Ahuja, 2020) calculation methodologies and proved its reliability at the developers' validation tests, showing a 5% deviation on office buildings compared with the industry benchmark EnergyPlus (Aguirre, 2020). The software offers a vast array of outputs per carrier, such as annual energy use intensity (EUI) per field and CO2e, which proved to be fundamental for the development and purpose of this study, accordingly with the following steps:
-
•
The first step starts by designing the BEM in the Sketchup software with a direct geometry upload link6 to cove.tool energy simulation software;
-
•
The second step performs an annual energy simulation in five European cities (Berlin, London, Paris, Rome, and Madrid), which were selected for being the capitals of the European countries with the highest gross domestic product (Clark, 2021) (see Table 2 below);
-
•
The third step consists of uploading the energy-related data inputs (envelope and systems specifications) into the software interface. The climate data is automatically imported depending on the nearest weather station in each location;
-
•
The fourth step continues under the cove.tool analysis by applying the ASHRAE 2019-2/IECC Equivalent Energy Code standards for “Office Building” and;
-
•
The fifth and final step happens through the assessment of ten simulations, two for each location, upon the same number of reports for posterior consideration and comparison, describing the EUI on “cooling”, “heating”, “lighting”, “plugs and equipment”, “pumps”, “SWH”, and environmental impact in “CO2 emissions” (see Appendix A, C).
Table 2.
Simulated location features.
| City, Country | Latitude (a) | Köppen-Geiger climate classification (Peel et al., 2007) | Country GDP (€ billion) (Clark, 2021) |
|---|---|---|---|
| Berlin, DEU | 52.5170 | Cold, no dry season, warm summer (Dfb) | 3449.05 |
| London, UK | 51.5156 | Temperate, no dry season, cold summer (Cfb) | 2525.09 |
| Paris, FRA | 48.8567 | Temperate, no dry season, hot summer (Cfa) | 2425.71 |
| Rome, ITA | 41.8933 | Temperate, dry summer, hot summer (Csa) | 1787.66 |
| Madrid, SPA | 40.4167 | Arid, steppe, cold (BSk) | 1245.33 |
(a) Consulted in www.maps.ie on May 13, 2021.
Standard EU “large office” building model
A prototype/archetype model is an abstraction that summarizes specific building features (parameters) related to the selected building typology, defined by its shape and geometry, envelope specifications, systems, and usage/schedules. Combining the prototype model with parametric experiments allows to evaluate the energy performance of a specific building type (Korolija et al., 2013). Kemna report for the European Commission (Kemna, 2014) frames the standard EU “large office” building archetype geometric features (pp. 52) that serve as the research BEM baseline to simulate a building in operation before the COVID-19 uprising (pre-C19 scenario) and under the guidelines in a posterior period (post-C19 scenario)(see Table 3 and Fig. 1 below).
The model baseline consists of a parallelepiped shape with 109 × 11.5 × 36 m split by 12 levels above ground. The building envelope presents an evenly distributed 20% glazing and 80% opaque surface ((Kemna, 2014), p. 61), with a thermal “mass” type of concrete grey finish color.7 The model's longer side is south-oriented in all locations to enable comparison accuracy.
The absence of a ratified EU “large office” building prototype that covers more than geometric features in the selected countries (except UK in 2013 (Korolija et al., 2013), and Italy in 2011 (Fabrizio et al., 2011)) led the authors to resort to the Pacific Northwest National Laboratory (PNNL) “ANSI/ASHRAE/IES Standard 90.1-2020 - Prototype Building Model Package” (Pacific Northwest National Laboratory, 2020), specifically the “Large Office” building prototype8 (see Appendix A) to build the baseline concerning “systems” specifications. The envelope specifications (U-values and SHGC) vary according to the national code requirements of each country (see Table 4 below), as well as the “systems” inputs (see Table 5 below). The latter follows upgraded data from supplementary sources.
Table 4.
Summary of the building model envelope features according to national code requirements.
| Envelope features | Berlin, DE ((Bundesgesetzblatt, Aug. 2020), p. 1769) | London, UK ((HM Government, 2016), p. 27) | Paris, FR ((Ministére du Logement et de l’Habitat Durable, 2017), pp. 2–4) | Rome, IT (Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021; Ministero dello Sviluppo Economico, 2015) | Madrid, SP ((Ministerio de Fomento, 2019), pp. 15–17) |
|---|---|---|---|---|---|
| Roof (U-value) | 0.2 | 0.18 | 0.30 | 0.26 | 0.35 |
| Wall Ext (U-value) | 0.28 | 0.26 | 0.34 | 0.29 | 0.41 |
| Wall Int (U-value) | n/a | n/a | 0.5 | n/a | 0.65 |
| Slab GF (U-value) | 0.35 | 0.22 | 0.37 | 0.29 | 0.65 |
| Glazing (U-value) | 1.3 | 1.6 | 1.9 | 1.8 | 1.8 |
| Glazing (SHGC) | 0.6 | 0.4 | 0.15 | 0.35 | 0.58 [a] |
[a] The SP Thermal code limits the solar factor to 0.58 for south-oriented glazing covering 20% of the envelope surface (Ministerio de Fomento, 2009) (p. 7).
Note: National climate zones: Paris zone H1a; Rome zone D, Madrid zone D3.
Table 5.
Summary of the building model systems considering the PNNL-ASHRAE's “Large Office” prototype and countries' national code standards.
PNNL-ASHRAE prototype standards (Pacific Northwest National Laboratory, 2020) and ASHRAE documentation = Italic data.
Main source references = Black color.
Supplementary sources = (a, f).
| Model systems and schedules | Berlin, DE ((Bundesgesetzblatt, 2020), p. 1770) | London, UK ((HM Government, 2016), p. 27) | Paris, FR (Ministére du Logement et de l’Habitat Durable, 2017), Pt. Art. 4-8 | Rome, IT (European Agency for Safety and Health at Work (EU-OSHA), 2020; Ministero dello Sviluppo Economico, 2015) | Madrid, SP (Ahuja, 2020; Brelih, 2013; Cipriano et al., 2015; Ministerio de Fomento, 2019; Nadel, 2020) |
|---|---|---|---|---|---|
| HVAC heating system | Gas-fired boiler* | ||||
| HVAC cooling system | Water-cooled centrifugal chiller* | ||||
| HVAC distribution system | VAV terminal box with a hot-water reheating coil* | ||||
| Chiller efficiency (cooling) | 0.56 kW/ton (e) | SEER = 3.6 | EER = 3 | EER = 2.5 | EER = 2.6 |
| Boiler efficiency (heating) | min. 0.80 (e) | 0.91 | 0.909 | 0.95 | 0.90 |
| SWH system efficiency | 0.80 (d) | 0.91 | 0.86 | 0.85 | 0.80 (d) |
| Lighting power density (occupied) | 10.76 W/m2 | 12.00 W/m2 (Korolija et al., 2013) | 10.76 W/m2 | 15.00 W/m2 ((Guo et al., 2021), p. 3) | 10.00 W/m2 |
| Lighting power density (unoccupied) | 0.22 W/m2 (c) | 0.22 W/m2 (c) | 0.22 W/m2 (c) | 0.22 W/m2 (c) | 0.22 W/m2 (c) |
| Plug and equipment's power density | 18.04 W/m2 | 15.00 W/m2 (Korolija et al., 2013) | 18.04 W/m2 | 10.00 W/m2 ((Fabrizio et al., 2011), p. 3) | 18.04 W/m2 |
| Occupation density | 18.09 m2/person | 9.00 m2/person (Korolija et al., 2013) | 18.09 m2/person | 16.66 m2/person ((Fabrizio et al., 2011), p. 3) | 18.09 m2/person |
| Sensors (daylight & occupation) | yes | yes | yes | no | yes |
| Air tightness | 1.1 m3/(m2hr) (a) | 3 m3/(m2hr) | 1.1 m3/(m2hr) (a) | 1.1 m3/(m2hr) (a) | 9 m3/(m2hr) |
| Outdoor air rate (person) | 11.11 l/s ((Rochard, 2015), p. 54) | 10 l/s (Korolija et al., 2013) | 2.5 l/s (b) | 2.5 l/s (b) | 2.5 l/s (b) |
| Outdoor air rate (area m2) | 1.11 l/s ((Rochard, 2015), p. 54) | 0.43 l/s | 0.43 l/s | 0.43 l/s | 0.43 l/s |
| Heat recovery efficiency | 60% ((Rochard, 2015), p. 59) | 70% | 75% (f) | 73% ((Stefanutti, 2016), p. 74) | 75% ((Asociación Técnica Española de Climatización y Refrigeración (ATECYR) & Instituto para la Diversificación y Ahorro de la Energía (IDAE), 2012), p. 61) |
| Heating set-point (°C) | 21.00 ((Rochard, 2015), p. 54) | 22.00 (Korolija et al., 2013) | 21.12 | 18.00 ((Costanzo et al., 2016), p. 11) | 20.00 |
| Heating set back (°C) | 15.56 | 12.00 (Korolija et al., 2013) | 15.56 | 15.56 | 17.00 |
| Cooling set-point (°C) | 24.00 ((Rochard, 2015), p. 54) | 24.00 (Korolija et al., 2013) | 27.00 | 26.00 ((Costanzo et al., 2016), p. 11) | 25.00 |
| Cooling set-back (°C) | 29.44 | 28.00 (Korolija et al., 2013) | 29.44 | 29.44 | 27.00 |
(a) EN 15242 ((CEN & CENELEC, 2007), Pt. Annex B, Table B1) “Multifamily, non-residential except industrial”.
(b) ANSI/ASHRAE Standard 62.1-2019 ((American Society of Heating & American National Standards Institute (ANSI), 2019), pp. 19, Table 6-1).
(c) ANSI/ASHRAE/IES Standard 90.1-2019 ((American Society of Heating et al., 2019), pp. 165, Table 9.3.1-1).
(d) ANSI/ASHRAE/IES Standard 90.1-2019 ((American Society of Heating et al., 2019), pp. 155, Table 7.8).
(e) ANSI/ASHRAE/IES Standard 90.1-2019 (American Society of Heating et al., 2019), Chiller values in p.129 at full load; Boiler values in p.133.
(f) Not specified in French national code. Resorted to the value suggested by Eurovent experts in 2019 ((European Industry Association (Eurovent) et al., 2019), p. 20) for sensible heat and moisture recovery exchangers concerning the revision of Commission Regulation (EU) n. 1253/2014 (Ventilation Units).
*Same systems in Italian prototype according to Fabricio et al. (Fabrizio et al., 2011).
Plus, to reach scientific accuracy, the authors added the following parameters to the model baseline:
-
•
Occupants' metabolic rate of 1.1 met (sitting and typing) ((American Society of Heating, American National Standards Institute (ANSI), 2017a), pp. 6, Table 5.2.1.2);
-
•
Building automation and control system (BACS) standard class C following EN 15232-1 (CEN & CENELEC, 2017);
-
•
100% mechanical ventilation with ePM1/M5 or similar filtration scheme ((American Society of Heating, American National Standards Institute (ANSI), 2017b), pp. 29, Table 12-1); and
-
•
Activated Demand Control Ventilation (DCV).
In addition, the study considers the following values concerning the outdoor air percentage (%OA) for each location: 35.50% DE; 72.10% UK; 24.33% FR; 25.87% IT; 24.33% SP: values calculated by formula (a) ((TSI, 2013), p. 5) and the parameters stated in Table 5 (above):
| (a) |
Where:
%OA = Recommended outdoor air percentage (%); AR person = Outdoor air rate per person (m3/h); Occ max = Maximum number of occupants; TotalAF = Total air flow in the building (m3/h).
For service water heating (SWH), the baseline considers a natural gas-fired boiler9 that fuel a 1135.62 litters tank with a temperature set-point of 60 °C ((Pacific Northwest National Laboratory, 2020), Pt. DOE Building Description).
Post-COVID-19 inputs
The post-C19 scenario contains a range of measures intended to emulate a building's operation in the post-pandemic era (see Table 6 below) against the baseline pre-C19 as described in Fig. 1, Table 4, and Table 5 (above).
Table 6.
Summary of the building model systems in post-C19 scenarios.
| Inputs | Berlin, DE | London, UK | Paris, FR | Rome, IT | Madrid, SP |
|---|---|---|---|---|---|
| HVAC heating system | Gas-fired boiler | ||||
| HVAC cooling system | Water-cooled centrifugal chiller | ||||
| HVAC distribution system | VAV terminal box with a hot-water reheating coil | ||||
| Chiller efficiency (cooling) | 0.56 kW/ton | SEER = 3.6 | EER = 3 | EER = 2.5 | EER = 2.6 |
| Boiler efficiency (heating) | min. 0.80 | 0.91 | 0.909 | 0.95 | 0.90 |
| SWH system efficiency | 0.80 | 0.91 | 0.86 | 0.85 | 0.80 |
| Lighting power density (occupied) | 10.76 W/m2 | 12.50 W/m2 | 10.76 W/m2 | 15.00 W/m2 | 10.00 W/m2 |
| Lighting power density (unoccup) | 0.22 W/m2 | 0.22 W/m2 | 0.22 W/m2 | 0.22 W/m2 | 0.22 W/m2 |
| Plug and equipment's power density | 18.04 W/m2 | 15.00 W/m2 | 18.04 W/m2 | 10.00 W/m2 | 18.04 W/m2 |
| Occupation density | 29.15 m2/person | 14.86 m2/person | 29.61 m2/person | 28.65 m2/person | 27.37 m2/person |
| Sensors (daylight & occupation) | yes | yes | yes | no | yes |
| Air tightness | 1.1 m3/(m2hr) | 3 m3/(m2hr) | 1.1 m3/(m2hr) | 1.1 m3/(m2hr) | 9 m3/(m2hr) |
| Outdoor air rate (person) | 15.00 l/s | 15.00 l/s | 15.00 l/s | 15.00 l/s | 12.50 l/s |
| Outdoor air rate (area m2) | 2.00 l/s | 2.00 l/s | 2.00 l/s | 2.00 l/s | 2.00 l/s |
| Heat recovery efficiency | suspended | suspended | suspended | suspended | suspended |
| Heating set-point (°C) | 21.00 | 22.00 | 21.12 | 18.00 | 20.00 |
| Heating set back (°C) | 15.56 | 12.00 | 15.56 | 15.56 | 17.00 |
| Cooling set-point (°C) | 24.00 | 24.00 | 27.00 | 26.00 | 25.00 |
| Cooling set-back (°C) | 29.44 | 28.00 | 29.44 | 29.44 | 27.00 |
| Two-hour air flush (pre-and-post occupation) | Yes | No | Yes | No | Yes |
| UVGI devices | In-duct | Upper-room in-duct | No | No | In-duct |
Notes:
• BACS upgraded to class B;
• A mix of mechanical plus natural ventilation (27/7);
• Air recirculation disabled;
• DCV disabled;
• Filtration upgrade to ePM1 70% (F8) filters.
The telework standard served as an effective measure to control the pandemic (European Agency for Safety and Health at Work (EU-OSHA), 2020; European Centre for Disease (ECDC) Prevention and Control, 2020), for which its implementation success appears to shape today and future work environments (Lund et al., 2020; Sostero et al., 2020). In this way, Sostero et al. ( Sostero et al., 2020) forecast a telework potential ranging between 34% and 39% in most of the studied countries (DE 38%; FR 39%; IT 37%; and SP 34%); while the Mckinsey report (Lund et al., 2020) state a 39.5% average for the UK.10 These figures mean a post-C19 occupation density “per person” of 29.15 m2 (DE); 14.86 m2 (UK); 29.61 m2 (FR); 28.65 m2 (IT); and 27.34 m2 (SP).
The HVAC system operation guidelines advocate the increase of outdoor airflow, raise of ventilation rates, and limit, or even suppress air recirculation (Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021; European Centre for Disease Prevention and Control (ECDC), 2020; World Health Organization (WHO), 2021; World Health Organization (WHO), 2020; World Health Organization (WHO), 2020). The post-C19 scenario simulation considers a mix of natural and mechanical ventilation (24/7 running) and suspends air recirculation and heat recovery mode (Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021; European Centre for Disease Prevention and Control (ECDC), 2020; World Health Organization (WHO), 2021). During unoccupied hours, the guidelines maximize the outdoor air to ensure air dilution under deactivated DCV (World Health Organization (WHO), 2020). Adds a pre-and post- two-hour air-flush schedule11 on workdays in Berlin, Paris, and Madrid (European Centre for Disease Prevention and Control (ECDC), 2020). Also, the outdoor air rate “per person” rises to 15 l/s (except Madrid with 12.5 l/s (Asociación Técnica Española de Climatización y Refrigeración (ATECYR), 2020)) and “per area” to 2.0 l/s, following REHVA guidelines ((Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021), p. 18) (see Appendix A, Table A1).
With no evidence regarding the virus life cycle and to guarantee indoor thermal comfort for users, RHEVA does not recommend adjusting the temperature and humidity levels (Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021), despite other sources stating that higher indoor temperature and relative humidity reduce the virus survivability, while lower figures (e.g., RH < 40%) exhibit the opposite effect (Ahlawat et al., 2020). For those reasons, the authors kept the pre-C19 indoor conditions for each location unchanged (see Table 5 above).
The guidelines recommend installing ultraviolet germicidal irradiation devices (UVGI) as a complementary measure to HVAC tuning. Cavallini et al. highlight the efficiency of this kind of installation when combined with high air renewal rates to diminish the virus spreading and infections odds (Cavallini et al., 2020). REHVA 4.1 guidelines suggest the application of an “upper-room” or an “in-duct” strategy to disable airborne viruses12 (Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021). Nevertheless, national guidelines push for in-duct in DE and SP, and upper-room and in-duct in UK, while FR and IT do not approach the issue (see Appendix A, Table A2). The upper-room UV light enables viruses anhelation in the indoor air near compartments ceiling, while the “in-duct” performs similar disinfection but inside HVAC equipment's or components (e.g., AHU's; ducts) (American Society of Heating, 2020; Jones & Ivanovich, 2020).
The upper room installments prove their effectiveness in deactivating the aerosolized SARS-CoV-2 virus by resorting to a UV-C light at 254 nm wavelength. It is suitable for situations where higher ventilation rates seem impossible to achieve (Beggs & Avital, 2020). The use of UVGI devices implies an increase in “lighting” EUI.
According to Riley and Nardell (Riley & Nardell, 1989) and Martin et al. (Martin et al., 2008) research on medical facilities, the upper room ratio accounts for 30 W (nominal input) per every 18.58 m2. However, the US Department of Health and Human Services guideline (US-DHHS) ((U.S. Department of Health & et al., 2009), p. VIII)13 points out a figure of 1.83 W/m2 for rooms with a 2.4 m ceiling height. Other sources, like Philips Lighting ((van den Kerkhoff & van Dijk, 2020), p. 26), refer to a value ranging from 0.2 to 0.5 W/m2 for a wide spectrum of airborne microorganisms. Given the presented figures, the authors adopted the latter source's most conservative value of 0.5 W/m2 considering the most recent lamp technology (lamp model Philips UV-C TUV T8 55 W HO) and its assessment date (2020) (van den Kerkhoff & van Dijk, 2020), in London, UK following the existing lighting schedule.
To target the microbial agents that proliferate in HVAC coils surfaces (in-duct systems), the recommended UV-C light irradiance ranges from 50 μW/cm2 to 100 μW/cm2, or 0.69 W/m2 (7.5 W/ft2) consumption to meet ASHRAE's14 requirements (Fencl, 2013a; Jones & Ivanovich, 2020). According to Fencl's benchmark, a 27,000 CFM system (45,873.29 m3/h) can have a 6 × 9 ft. coil with 5.01 m2 (54 ft2) surface (Fencl, 2013b). Based on the same criteria, the authors calculated 3 coils of the same dimension for Berlin (ventilation requirements of 136,166.4 m3/h), and Madrid (ventilation requirements of 133,054.4 m3/h), and 4 coils for London (ventilation requirements of 160,926.4 m3/h) considering the BEM gross area and post-C19 occupation density, and outdoor air rate “per person” and “per area” (see Table 5 above). All resulted in a UV-C light consumption of 1215 W for Berlin and Madrid, and 1620 W for London. According to Martin Jr. et al., a 24/7 lamps operation at low irradiation levels inhibit the formation and development of microorganisms keeping the coil clean (Martin et al., 2008). Assuming the in-duct UV-C light installment recommendation, the annual EUI increased by 10,643.40 kW in Berlin and Madrid, and 14,191.20 kW in London.
Another post-C19 measure oversees the filtration system update up to the ePM10/F8 standard or above, following the REHVA guidelines (Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021). The authors considered an ePM10 50% (M5)15 filter baseline in the pre-C19 scenario, upgrading it to an ePM1 70% (F8)16 under the post- C19 scenario following WHO recommendations ((World Health Organization (WHO), 2021), p. 11). The average pressure drop is 42.30 Pa for an ePM1 filter and 30.63 Pa for the ePM10, according to the formula below (b) ((European Industry Association (Eurovent) et al., 2019), p. 6):
| (b) |
Where:
Δpi = Average of the pressure drops of an air filter measured before and after the dust loading step i (Pa); M x = Amount of L2 dust fed to the test filter following ISO 16890-3 (g); i = number of the dust loading steps; n = total number of dust loading steps used to feed the amount of test dust M x to the air filter (n ≥ 8); Δm i = dust increment fed to an air filter during loading step i (g).
The annual energy consumption portion related to air filters pressure drop represents 479.17 W/yr to ePM1 and 346.92 W/yr to ePM10, meaning an extra consumption of 132.25 W/yr, calculated with the formula below (c) ((European Industry Association (Eurovent) et al., 2019), p. 4):
| (c) |
Where:
W = Yearly energy consumption (W); q v = Air volume flow rate at filter (m3/s); Δp = Average pressure drop of an air filter (Pa); t = Time of operation (h); η = Efficiency of a fan for the transmission of electrical energy into energy content of the air flow field. According to Eurovent17 ((European Industry Association (Eurovent) et al., 2019), p. 4) q v = 0.944 m3/s, t = 6000 h/a, and η = 0.5.
The building HVAC operates with 3 AHUs following the same baseline used and validated by the UV-C lamps assessment, which leads to 15 high-performance bag filters18 (twelve 594 × 594 mm, and three 292 × 594 mm) to cover a coil with the same dimension surface area: 1.829 m × 2.743 m (6 ft. × 9 ft). By adding up the 15 filters, the “annual consumption portion filter drop” equals 132.25 W/yr in energy surplus per coil. In total, the filtration upgrade increases the “fans” EUI by 5.95 kW/yr.
Finally, according to ASHRAE, the SHW temperature should be set above 60 °C to avoid the probability of virus manifestation (American Society of Heating, 2021a), which the authors kept unchanged. Table 6 (below) summarizes the actions previously described.
Reliability
The HVAC operation and cleaning guidelines applied to medical facilities have become the new standard for complex buildings under AHU. The focus of those measures falls on safety and health rather than energy consumption — precisely the knowledge gap that this research intends to address.
The BES reliability depends on the BEM quality, which gathers its geometry from other reviewed and published sources in Europe. The “large office” standard building formal features follow Kemna's baseline research as a BEM standard ((Kemna, 2014), pp. 52, Fig. 12). The five steps methodology addresses the pandemic mitigation measures under the telework project figures on EUI and CO2e levels.
Due to the sparse data concerning envelopes, systems, and usage/schedules on EU “large office,” except the UK in 2013 (Korolija et al., 2013) and IT in 2011 (Fabrizio et al., 2011), and to assure the model reliability, the authors opted for a peer-reviewed model. The study recurs to the Pacific Northwest National Laboratory (PNNL) “ANSI/ASHRAE/IES Standard 90.1-2020 - Prototype Building Model Package” (Pacific Northwest National Laboratory, 2020), specifically the “Large Office” building prototype19 HVAC “systems” and “usage and schedules” information to fulfill the EU model missing points (see Annex A).
Study limitations
The study fulfills the gaps with other valid contributions and exhibits the following limitations:
-
•
The Kemna report (Kemna, 2014) bounds a 0.2 window-to-wall ratio, not considering the climate particularities or the local architectural style of office buildings;
-
•
The limited number of cities;
-
•
The software limitations of cove.tool, demanding additional calculations like the energy consumption portion related to air filters pressure drop and UVGI devices;
-
•
The study did not follow the contribution of national renewables energy sources;
-
•
The lack of an “official” RHEVA approved EU building prototype package covering also systems and schedules, despite some national endeavors as followed by the UK and IT;
-
•
The standard EU “large office” (Kemna, 2014) BEM applied in every location does not acknowledge building regionalism features, despite the tendency towards a uniform architecture style present in office buildings;
-
•
Some national requirements or guidance lack in the details for the “systems” inputs, forcing the use of third-party sources, e.g., PNNL-ASHRAE's building prototype;
-
•
The forecasted “telework” figures follow different studies (Lund et al., 2020; Sostero et al., 2020), recurring to distinct methodologies and approaches. Nevertheless, the presented figures are fairly supported and similar;
-
•
The non-consideration of costs involved in HVAC/AHU upgrades, e.g., filtration and UVGI devices.
Results
Data analysis
The following data and its interpretation consider the relative values between pre-and-post-C19 scenarios outcomes.
Energy consumption
The simulation results show the impact of institutional guidelines on how the post-pandemic scenario affects the annual building energy consumption pattern in all locations (see Table 7 above and Chart 3 below):
-
•
The EUI increases in the post-C19 scenario, on average, by 34.38% (45.24 kWh/m2yr) considering all locations;
-
•
Rome shows the slightest increase, consuming more 10.18% than the pre—C19, while Paris exhibits the highest with a 69.48% difference;
-
•
In absolute numbers, a building located in London displays the highest relative consumption, adding 63.65 kWh/m2yr, followed by Paris with 62.60 kWh/m2yr. Rome has the lowest increase with only 8.18 kWh/m2yr.
-
•
When assessing a post-C19 scenario under full occupation versus forecasted telework, the outcomes show, on average, an energy consumption increase of 1.36% in all locations. Rome displays the lowest difference (+0.43%) and London the highest (+2.82%).
Table 7.
Usable energy consumption per location in pre-and-post-C19 scenarios.
| City, Country | Energy consumption (kWh/m2yr) |
Variation difference |
||
|---|---|---|---|---|
| Pre-C19 | Post-C19 | Absolute value (kWh/m2yr) | Percentual | |
| Berlin, DEU | 153.36 | 195.12 | +41.76 | +27.23% |
| London, UK | 163.37 | 227.02 | +63.65 | +38.96% |
| Paris, FRA | 90.10 | 152.70 | +62.60 | +69.48% |
| Rome, ITA | 80.37 | 88.55 | +8.18 | +10.18% |
| Madrid, SPA | 192.20 | 242.23 | +50.03 | +26.03% |
Chart 3.
Usable energy consumption per location in pre-and-post-C19 scenarios.
The results reflect the total energy consumption due to “heating” EUI weight on the whole: an average of 1.95% for “cooling” against 51.50% “heating. However, Rome stands below the average with “heating” and “cooling” EUI figures accounting for 7.80% and 11.36%, respectively. On the opposite side, Madrid and London stand above the “heating” EUI average, reaching 65.96% and 67.70%, respectively, of the total EUI.
Table 8 (above) displays the opposite trends for office building heating and cooling energy consumption under post-C19 measures:
-
•
The “heating” EUI tends to increase across all locations. Nonetheless, Berlin, London, and Madrid alone show an average value of 50.75%, while in Paris and Rome, the demand for heating goes, respectively, around 3.4 times and 23 times above the pre-C19 baseline;
-
•
The “heating” average in all locations increases 41.99 kWh/m2yr. However, Rome presents the lowest overconsumption of 9.62 kWh/m2yr (lowest value), while in London it reaches the highest with 58.75 kWh/m2yr;
-
•
On the “cooling” side, the EUI exhibit cuts in all locations, on average, by 57.94%, but Paris alone reaches 93.96%, and London 83.33%. The lowest percentual difference falls in is the warmer city of Madrid with 24.94%;
-
•
Nonetheless, the reduced “cooling” absolute values difference is not comparable with the “heating” EUI; on the contrary, an average of 1.51 kWh/m2yr is cut back in all locations. Rome displays the highest difference, consuming less 4.09 kWh/m2yr, while London the lowest, with less 0.28 kWh/m2yr.
Table 8.
Cooling and heating EUI per location in pre-and-post-C19 scenarios.
| City, country | Cooling (kWh/m2yr) |
Heating (kWh/m2yr) |
Variation difference (kWh/m2yr | %) |
|||
|---|---|---|---|---|---|---|
| Pre-C19 | Post-C19 | Pre-C19 | Post-C19 | Cooling | Heating | |
| Berlin, DEU | 1.96 | 1.17 | 78.70 | 117.48 | −0.79 | -40.31% | +38.78 | +49.28% |
| London, UK | 0.30 | 0.02 | 94.95 | 153.70 | −0.28 | -93.33% | +58.75 | +61.87% |
| Paris, FRA | 1.49 | 0.09 | 23.56 | 79.84 | −1.40 | -93.96% | +56.28 | +238.88% |
| Rome, ITA | 11.00 | 6.91 | 0.44 | 10.06 | −4.09 | -37.18% | +9.62 | +2186.36% |
| Madrid, SPA | 4.05 | 3.04 | 113.25 | 159.78 | −1.01 | -24.94% | +46.53 | +41.09% |
Concerning “lighting” EUI, the post-C19 measures induce overconsumption of 6.11% in Berlin (DE), 6.84% in Madrid (SP), and up to 11.16% in London (UK). The remaining locations do not present any variation in this parameter. The same applies to “plug and equipment,” “pumps” and “SWH” EUI elsewhere.
The “fans” EUI follows an overconsumption behavior (see Chart 4 below):
-
•
The average energy consumption increases by 36.63% considering all locations except Paris, with a threefold increase under the post-C19 scenario;
-
•
On average, the “fans” EUI absolute figures rise 4.20 kWh/m2yr considering all locations. Again, Paris shows the highest difference, consuming more 7.72 kWh/m2yr, while Rome has the lowest overconsumption with 2.65 kWh/m2yr;
-
•
The post-C19 measures on “fans” EUI impact a Paris building three times more than in Rome.
Chart 4.
Fans EUI per location in pre-and-post-C19 scenarios.
CO2 emissions
The CO2e depend on countries' energy production mix; therefore, they tend to follow the energy consumption behavior (see Table 9 above):
-
•
The CO2e increase in every location under the post-C19 scenario, on average, by 39.17%; however, Rome presents the lowest relative value of 5.80%, while Paris has the highest with 120.61%;
-
•
Rome presents the lowest absolute value, increasing its emissions by 19.90 Tonne/CO2e/yr, whereas London adds 175.90 Tonne/CO2e/yr. On average, the CO2e rise by 120.12 Tonne/CO2e/y considering all locations;
-
•
When assessing a post-C19 scenario under full occupation versus forecasted telework, the results show an average CO2e rise of 1.46%, considering all locations. Madrid displays the lowest difference (+0.54%) and London the highest (+2.54%).
Table 9.
CO2 emissions per location in pre-and-post-C19 scenarios.
| City, country | CO2e (Tonne/CO2e/yr) |
Variation difference |
|
|---|---|---|---|
| Pre-C19 | Post-C19 | (Tonne/CO2e/yr | %) | |
| Berlin, DE | 560.90 | 670.60 | +109.70 | +19.56% |
| London, UK | 527.80 | 703.70 | +175.90 | +33.33% |
| Paris, FR | 130.50 | 287.90 | +157.40 | +120.61% |
| Rome, IT | 343.00 | 362.90 | +19.90 | +5.80% |
| Madrid, SP | 832.30 | 970.00 | +137.70 | +16.54% |
Discussion
The study outcomes reflect an overall energy and CO2e increase in standard EU “large office” buildings located in five European capitals under post-pandemic and telework scenarios. The findings align with literature that forecasted a rise in energy consumption of HVAC systems, although based upon empirical assumptions (American Society of Heating, 2021a; American Society of Heating, 2020; Cutler & Summers, 2020; Mo et al., 2020; Nadel, 2020; Taylor Engineering, 2020), and recent studies show similar tendencies (Zheng et al., 2021) on analogous latitudes (≥ 40°) and climates (Cortiços & Duarte, 2021). In a broader range, based on new societal trends, Brugger et al. (2021) predict an energy demand rise of up to 40% (in its worst-case scenario) by 2050.
The study follows institutional HVAC guidelines to tackle the virus spread. The work of Elsaid & Ahmed (2021) and Zheng et al. (2021) advocate and validate HVAC systems measures, such as UVGI devices installation, filtration upgrade, and higher ventilation rates under 100% outdoor air. The COVID-19 guidelines will craft the future of HVAC systems by ensuring operation safety until becoming the new standard (Pan et al., 2021).
The post-C19 scenario increases the annual energy consumption, on average, by 34.38% (+45.24 kWh/m2yr), and CO2e by 39.17% (+120.61 Tonne/CO2e/yr) in all locations. However, the “heating” weight surpasses the “cooling” on total usable energy consumption, representing, on average, 51.55% and reaching 67.70% in London. Therefore, part of the overall energy increase relates “heating” EUI increments in all locations. Cortiços & Duarte (Cortiços & Duarte, 2021), under a similar methodology, found a similar pattern in the US context applied to “high-rise” office buildings.
Nonetheless, the outcomes differ in range and location. Berlin, London, and Madrid present an average “heating” EUI overconsumption of 50.75%, Paris 238.88% (+56.28 kWh/m2yr), while Rome registers the lower absolute value of 9.62 kWh/m2yr against the pre-C19 scenario. Despite the overall tendency, Cortiços & Duarte (2021) calculated smaller variations in “heating” EUI between 35.66% to 46.05% in “mixed” to “cold” climates for the US context. Following the “heating” pattern, the “fans” EUI increase in all locations, on average, by 4.20 kWh/m2yr (+71.72%), where Paris displays the highest value with 7.72 kWh/m2yr, three times higher than the baseline.
Zheng et al. (2021) study presented similar results on “ventilation” following the same principles, as-window policy, increase of natural ventilation, increment of outdoor air rate “per person” and “per area,” DCV disabling, filtration upgrade impact, and the 2 h air-flush schedule before and after work (Paris, Madrid, and Berlin). These recommendations tend not only to increase “fans” EUI, as forecasted by Nadel (2020), but also the amount of energy lost per airflow requiring additional energy for heating. Plus, air recirculation and heat recovery shutdown push office buildings into higher heating demand under harsh winters locations. The UVGI strategies also contribute to increase the overall energy consumption, adding 0.71 kWh/m2yr in Berlin (DE) and Madrid (SP) and 1.41 kWh/m2yr in London (UK), which in turn is reflected in the “lighting” EUI.
The “cooling” EUI drops in all locations, on average, by 1.51 kWh/m2yr (−57.94%), reaching its lowest expression in Rome (IT) with 4.09 kWh/m2yr (−37.18%). The above-cited measures increase the outside air flow rate, promoting free cooling strategies during hot seasons, consequently cutting on “cooling” EUI.
The literature confirms the expectations and certainties of telework tendencies and policies in Europe (Hogan et al., 2020; Milasi et al., 2021), sustained by state-of-the-art technology (Moeckel, 2017), as well as the ability to pressure buildings' energy consumption patterns under higher area per person to ensure social distance policies and promote safer and healthier environments. The telework forecast presented by Sostero et al. (Sostero et al., 2020) and Lund et al. (Lund et al., 2020) studies points to a 34% to 39% cut in building occupation with expected impacts in some HVAC settings (e.g., outdoor air rate “per person”) and internal gains reduction. Consequently, when assessing a post-C19 scenario without telework against the forecasted figures, the EUI and CO2e increase by 1.36% and 1.46%, respectively, under the latter. When combined with “open-window” policies, these measures reduce the cooling energy demand, which is beneficial in the summertime or in hot to warm climates. The opposite effect occurs during wintertime or under cold climate locations, aggravating the already significant “heating” EUI.
Finally, the study outcomes do not comply with environmentally friendly policies; on the contrary, it collides with the international agreement's goals, such as the Paris Accord, signed and ratified by several countries, including the five assessed to control and reduce CO2e (Wang & Wang, 2020). The research frames the future energy consumption and CO2e under common forecasted scenarios, contributing with knowledge that aims to rethink the “large office” buildings' role.
Research international impact
The European assessed energy consumption and CO2e figures represent a global concern that extends the discussion wherever the context applies: knowledge base societies, safety and health concerns, and COVID-19 guidelines. Despite the overall “health above energy efficiency” approach in large indoor spaces, the numbers created a commitment, ensuring energy efficiency measures without compromising workers' health. Nevertheless, the forecasted telework figures could disrupt the global energy stability and environmental goals.
The study methodology and approach have the potential to anticipate scenarios in the international sphere. Although, results differ from climate conditions, energy patterns and prices, and HVAC guidelines. The authors underline the WHO's effort (March 22, 2021) to improve and simplify its guideline helping its members to comply with desirable conditions to protect general public safety and health without undervaluing energy efficiency and CO2e.
Conclusions
The COVID-19 pandemic forced changes in working environments, leading to the most prominent global work experience; the remote work (telework). The experience resulted in the so-called “new normal,” a new vision that disrupted past routines, consequently enlarging the average telework numbers in Europe from 5.4% to 25/40% (Fana et al., 2020; Milasi et al., 2021). The European countries started to draw new regulations and policies to accommodate and empower the “new normal” through investments in digital networks by cable, land radio frequencies, or satellite (Kiss, 2021).
The scientific community, environmental associations, and governments raised concerns about a wave of energy overconsumption due to the HVAC systems COVID-19 mitigation measures enforcement, circumscribed to office buildings/telework and third-party logistics (Tenailleau et al., 2021).
The study authors looked at the capitals of Europe's top five economies, aiming to understand and quantify the EUI and CO2e impact of the guidelines published by international entities and ratified by their national counterparts. The study resorted to a BES methodology (Cipriano et al., 2015; Hong et al., 2017; Shiel et al., 2018) and an EU “large office” archetype model (Kemna, 2014) to assess pre-and-post-COVID-19 scenarios, where the latter also comprises the telework forecast for each assessed country.
The average outcomes display an overall increasing tendency in all locations; with EUI increments ranging from 10.18% or 8.18 kWh/m2yr (Rome) to 69.48% or 62.60 kWh/m2yr (Paris); and CO2e between 5.80% or 19.90 t/CO2e/yr (Rome) and 120.61% or 157.40 t/CO2e/yr (Paris). The “heating” and “cooling” EUI differ in behavior. The first exhibits an increasing tendency, while the second shows reductions in all locations showing that places with temperate to hot climates benefit from the guideline's implementation. In contrast, the opposite is true for cold climates or harsh winters. The forecasted remote work figures upon post-C19 HVAC settings worsen the energy consumption and CO2e in all locations.
The COVID-19 mitigation measures related to the HVAC system (airflow rates and operation schedules) and the open-window and telework forecasts represent the most effective way to decrease the virus spread and increase indoor air quality. However, this pressures the energy consumption and CO2e, compromising the overall buildings performance. The latter should awake the decision-makers designing future guidelines to dynamically adjust HVAC settings to lessen the impact on “heating” EUI, particularly in cold climates or northern latitudes.
Europe's telework forecast points to 25% to 40% (Milasi et al., 2021). On one side, these numbers disrupt social fabrics and push for new consumption patterns: directly, pressuring residential (by 15% in the UK) and non-residential buildings' energy consumption; and indirectly, adding home deliveries resources and transforming commuting patterns. On the other, the energy savings due to daily commuting cuts could counterbalance the higher consumption of the above examples (Crow & Millot, 2020) aligned with the study results. The balance remains unknown but opens a research opportunity.
Ultimately, because every human action impacts the climate, forecasting is needed to perceive the long-term effect. The study authors aim to raise awareness of guidelines design consequences on energy and emissions following the Paris Accord and other commitments. As the COVID-19 disrupter fades out and telework grows, weighted adjustments are needed to address the nowadays issues of safety and health, concerns, energy efficiency, and CO2e.
Declaration of competing interest
The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper. Moreover, the manuscript has not been published and is not under consideration for publication elsewhere.
Acknowledgment
The authors acknowledge the Fundação para a Ciência e Tecnologia (FCT – Portugal) for the financial support granted to the research project UIBD/04008/2020, the Research Centre for Architecture, Urbanism and Design (CIAUD) of the Lisbon School of Architecture, Universidade de Lisboa, and the cove.tool team for providing an educational version of the software and their readiness in assisting us pursue our research goals.
As published by the European Commission page, accessed on July 14, 2021, at https://ec.europa.eu/energy/eu-buildings-factsheets_en.
As presented by the webpage, accessed on July 21, 2021, at https://www.cove.tools/testimonials.
EN 15603:2008 - Energy performance of buildings - Overall energy use and definition of energy ratings.
ISO 13790:2008 - Energy performance of buildings - Calculation of energy use for space heating and cooling.
Concrete material emissivity coefficient (ε) = 0.85. Consulted in https://www.engineeringtoolbox.com/emissivity-coefficients-d_447.html.
Available at https://www.energycodes.gov/sites/default/files/documents/ASHRAE901_all.zip. The xml file “Large Office” contains the prototype description.
The efficiency value varies according to location.
Average value obtained from the “theoretical maximum” and “effective potential” from the Exhibit 3 (Lund et al., 2020).
Despite being recommended by WHO and RHEVA guidelines (Federation of European Heating & Ventilation and Air Conditioning Associations (REHVA), 2021; World Health Organization (WHO), 2021; World Health Organization (WHO), 2020) only German, French, and Spanish guidelines recommend it at a national level.
Heilingloh et al. recommend the use of portable UV-C devices for nine minutes at a dosage of 1.048 mJ/cm2 to inactivate the virus on surfaces (Heilingloh et al., 2020). The research does not contemplate internal layout or furniture configuration and, therefore, dismiss this recommendation.
US Department of Health and Human Services guideline “Environmental control for tuberculosis: basic upper-room ultraviolet germicidal irradiation guidelines for healthcare settings”, date 2009 (U.S. Department of Health & et al., 2009).
ASHRAE Handbook—HVAC Applications - Chapter 62 - Ultraviolet Air and Surface Treatment (2019).
According to the Robatherm classification chart ((Robatherm, 2018), p. 3).
Filters recommended efficiencies by Eurovent ((European Industry Association (Eurovent) et al., 2020), pp. 11–15) considering an outdoor air category 2 (ODA) “outdoor air with high concentrations of particulate matter” Table 1; and an supply air category 2 (SUP) “rooms for permanent occupation” for ePM1 filter; and SUP 5 for the ePM10 filter baseline.
“As a laboratory test method, the average pressure drop is determined from a loading of the filter according to ISO 16890-3 using a synthetic test dust specified in ISO 15957 as L2 (AC Fine). According to this guideline fine dust filters are rated with an efficiency ePM10 ≥ 50%.” ((European Industry Association (Eurovent) et al., 2019), p. 4).
Consulted in Airclean Manufacturer (Airclean Manufacturer, 2021).
Available at https://www.energycodes.gov/sites/default/files/documents/ASHRAE901_all.zip. The mml file “Large Office” contains the prototype description.
Supplementary data to this article can be found online at https://doi.org/10.1016/j.esd.2022.04.006.
So far uses the April 3, 2020, REHVA 2.0 guidelines standards. Available at https://aicvf.org/comite-international/actualites/document-guide-rehva-covid-19/.
Tutorial and plugin available at https://www.cove.tools/sketchup-plugin
Appendix A. Supplementary data
Supplementary material
References
- Aguirre M. Cove.tool Help Center: How does Cove.tool compare to Energy Plus. 2020. http://help.covetool.com/en/articles/2422877-how-does-cove-tool-compare-to-energy-plus [Online]. Available.
- Ahlawat A., Wiedensohler A., Mishra S.K. An overview on the role of relative humidity in airborne transmission of SARS-CoV-2 in indoor environments. Aerosol and Air Quality Research. 2020;20(9):1856–1861. doi: 10.4209/aaqr.2020.06.0302. [DOI] [Google Scholar]
- Ahuja S. What is the simulation engine being used? 2020. http://help.covetool.com/en/articles/2301606-what-is-the-simulation-engine-being-used
- Airclean Manufacturer . Airclean; 2021. HVAC high performance bag filter - M5, M6, F7, F8 and F9 EN 779:2012.https://www.airclean.co.uk/bag-filters/high-performance-bag-filters/ [Google Scholar]
- American Society of Heating, Refrigerating and Air-Conditioning Engineers A.S.H.R.A.E. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE); 2020. ASHRAE position document on infectious diseases.https://www.ashrae.org/file%20library/professional%20development/learning%20portal/instructor-led%20training/online%20instructor-led/airborne-infectious-diseases.pdf [Online]. Available. [Google Scholar]
- American Society of Heating, Refrigerating and Air-Conditioning Engineers A.S.H.R.A.E. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE); 2021. ASHRAE Epidemic Task Force. Building Readiness.https://www.ashrae.org/file%20library/technical%20resources/covid-19/ashrae-building-readiness.pdf [Online]. Available. [Google Scholar]
- American Society of Heating, Refrigerating and Air-Conditioning Engineers A.S.H.R.A.E. ashrae.org; 2021. Coronavirus (COVID-19) response resources from ASHRAE and others.https://www.ashrae.org/technical-resources/resources [Google Scholar]
- American Society of Heating, Refrigerating and Air-Conditioning Engineers A.S.H.R.A.E. ashrae.org; May 07, 2020. ASHRAE offers COVID-19 building readiness/reopening guidance.https://www.ashrae.org/about/news/2020/ashrae-offers-covid-19-building-readiness-reopening-guidance [Google Scholar]
- American Society of Heating, Refrigerating and Air-Conditioning Engineers A.S.H.R.A.E., American National Standards Institute (ANSI) ANSI/ASHRAE Standard 55-2017 - Thermal environmental conditions for human occupancy. 2017. https://ashrae.iwrapper.com/ASHRAE_PREVIEW_ONLY_STANDARDS/STD_55_2017 [Online]. Available.
- American Society of Heating, Refrigerating and Air-Conditioning Engineers A.S.H.R.A.E., American National Standards Institute (ANSI) ANSI/ASHRAE Standard 52.2-2017 - Method of testing general ventilation air-cleaning devices for removal efficiency by particle size. 2017. https://ashrae.iwrapper.com/ASHRAE_PREVIEW_ONLY_STANDARDS/STD_52.2_2017 [Online]. Available.
- American Society of Heating, Refrigerating and Air-Conditioning Engineers A.S.H.R.A.E., American National Standards Institute (ANSI) ANSI/ASHRAE Standard 62.1-2019 - Ventilation for acceptable indoor air quality. 2019. https://ashrae.iwrapper.com/ASHRAE_PREVIEW_ONLY_STANDARDS/STD_62.1_2019 [Online]. Available.
- American Society of Heating, Refrigerating and Air-Conditioning Engineers A.S.H.R.A.E., Illuminating Engineering Society of North America (IES) American National Standards Institute (ANSI) ANSI/ASHRAE/IES Standard 90.1-2019 - Energy efficiency standard for buildings except low-rise residential buildings. 2019. https://ashrae.iwrapper.com/ASHRAE_PREVIEW_ONLY_STANDARDS/STD_90.1_2019 [Online]. Available.
- Association des Ingénieurs et techniciens en Climatique Ventilation et Froid A.I.C.V.F. Association des Ingénieurs et techniciens en Climatique, Ventilation et Froid (AICVF); 2020. Document guide REHVA COVID-19 V2. Comment faire fonctionner et utiliser les installations sanitaires et de conditionnement des bâtiments afin d’éviter la propagation du coronavirus (Covid-19) et du virus (SRAS-CoV-2) sur les lieux de travail’.https://aicvf.org/comite-international/actualites/document-guide-rehva-covid-19/ [Online]. Available. [Google Scholar]
- Associazione Italiana Condizionamento dell`aria Riscaldamento Refrigerazione AiCARR. 1st ed. Associazione Italiana Condizionamento dell`aria, Riscaldamento Refrigerazione (AiCARR); Milan, Italy: 2020. AiCARR position on HVAC system operation during SARS-COV-2-19 emergency. Accessed: Jul. 13, 2021. [Online]. Available: https://www.aicarr.org/Documents/Normativa/COVID19/200406_PP_AICARR_COVID-19%20ENG.pdf. [Google Scholar]
- Associazione Italiana Condizionamento dell`aria Riscaldamento Refrigerazione AiCARR. Associazione Italiana Condizionamento dell`aria, Riscaldamento Refrigerazione (AiCARR); 2020. Protocol for risk reduction of SARS-CoV2-19 diffusion with the aid of existing air conditioning and ventilation systems.https://www.aicarr.org/Documents/Normativa/COVID19/200318_AICARR%20PROTOCOL_HVAC_COVID19_DEF_ENG.pdf [Online]. Available. [Google Scholar]
- Associazione Italiana Condizionamento dell`aria Riscaldamento Refrigerazione AiCARR. Associazione Italiana Condizionamento dell`aria, Riscaldamento Refrigerazione (AiCARR); Feb. 2020. Gli impianti e la diffusione del SARS-CoV2-19 nei luoghi di lavoro.https://www.aicarr.org/Documents/Normativa/COVID19/200313_AICARR_SARSCOV2_19.pdf [Online]. Available. [Google Scholar]
- Asociación Técnica Española de Climatización y Refrigeración (ATECYR) Asociación, Técnica Espańola de Climatización y Refrigeración (ATECYR); 2020. Guía de ATECYR de recomendaciones de operación y mantenimiento de los sistemas de climatización y ventilación para edificios de uso sanitario para la prevención del contagio por COVID-19.https://www.atecyr.org/docs/uploads/1588938441_Recomendaciones%20Atecyr%20sobre%20el%20Covid%2719%20a%207%20de%20mayo%202020.pdf [Online]. Available. [Google Scholar]
- Asociación Técnica Española de Climatización y Refrigeración (ATECYR) Instituto para la Diversificación y Ahorro de la Energía (IDAE) vol. 9. Instituto para la Diversificación y Ahorro de la Energía (IDAE); Madrid: 2012. Guía Técnica. Ahorro y recuperación de energia en instalaciones de climatización. Accessed: Jul. 15, 2021. [Online]. Available: https://energia.gob.es/desarrollo/EficienciaEnergetica/RITE/Reconocidos/Reconocidos/Gu%C3%ADas%20t%C3%A9cnicas/Guia_Climatizacion_Ahorro.pdf. [Google Scholar]
- Beggs C.B., Avital E.J. Upper-room ultraviolet air disinfection might help to reduce COVID-19 transmission in buildings: A feasibility study. PeerJ. Oct. 2020;8 doi: 10.7717/peerj.10196. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Brelih N. Thermal and acoustic comfort requirements in European standards and national regulations. The REHVA European HVAC Journal. Mar. 2013;50(2):16–19. Accessed: Jun. 22, 2021. [Online]. Available: https://www.rehva.eu/rehva-journal/chapter/thermal-and-acoustic-comfort-requirements-in-european-standard-and-national-regulations. [Google Scholar]
- Brugger H., Eichhammer W., Mikova N., Dönitz E. Energy Efficiency Vision 2050: How will new societal trends influence future energy demand in the European countries? Energy Policy. May 2021;152 doi: 10.1016/j.enpol.2021.112216. [DOI] [Google Scholar]
- Bundesgesetzblatt . ‘Law to standardize energy saving law for buildings and to amend other laws (Gesetz zur Vereinheitlichung des Energieeinsparrechts für Gebäude und zur Änderung weiterer Gesetze)’, Bundesgesetzblatt Teil I, no. 37. Aug. 2020. p. 1728. Accessed: May 13, 2021. [Online]. Available: http://www.bgbl.de/xaver/bgbl/start.xav?startbk=Bundesanzeiger_BGBl&jumpTo=bgbl120s1728.pdf. [Google Scholar]
- Cavallini A., Busato F., Pregliasco F. Remarks on the air recirculation in HVAC systems during the SARS-CoV-2 outbreak: The case of all-air ducted plants (Approfondimenti sugli impianti a tutt’aria con ricircolo durante la pandemia SARS-CoV-2) AiCARR Journal. 2020;63(4):50–55. Accessed: Jul. 13, 2021. [Online]. Available: http://www.aicarrjournal.org/cont/journals-articles/830/volume-september-remarks-recirculation-hvac-systems-3541allasp1.pdf. [Google Scholar]
- CEN, CENELEC EN 15242. Ventilation for buildings - Calculation methods for the determination of air flow rates in buildings including infiltration. 2007. https://standards.iteh.ai/catalog/standards/cen/8969d887-dcd6-41fe-9327-d2373c3c378b/en-15242-2007 [Online]. Available.
- CEN, CENELEC EN 15232-1. Energy performance of buildings - Impact of building automation, controls and building management. 2017. https://standards.iteh.ai/catalog/standards/cen/d9e4b452-93a7-4b7e-b8f8-90e37adddbc2/en-15232-1-2017 [Online]. Available.
- Chartered Institution of Building Services Engineers (CIBSE) CIBSE; Oct. 23, 2020. COVID-19 ventilation guidance.https://www.cibse.org/knowledge/knowledge-items/detail?id=a0q3Y00000HsaFtQAJ [Online]. Available. [Google Scholar]
- Cipriano J., Mor G., Chemisana D., Pérez D., Gamboa G., Cipriano X. Evaluation of a multi-stage guided search approach for the calibration of building energy simulation models. Energy and Buildings. Jan. 2015;87:370–385. doi: 10.1016/j.enbuild.2014.08.052. [DOI] [Google Scholar]
- Clark D. Statista.com; Feb. 12, 2021. Gross domestic product (GDP) at current market prices of selected European countries in 2019.https://www.statista.com/statistics/685925/gdp-of-european-countries/ [Google Scholar]
- Cortiços N.D., Duarte C.C. Energy and Buildings; Jun. 2021. COVID-19: The impact in US high-rise office buildings energy efficiency; p. 111180. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Costanzo E., Martino A., Varalda G.M., Antinucci M., Federici A. ‘EPBD implementation in Italy’, Status in December 2016. Dec. 2016. http://epbd-ca.eu/wp-content/uploads/2018/08/CA-EPBD-IV-Italy-2018.pdf [Online]. Available.
- cove.tool . cove.tool; Atlanta, GA, USA: 2021. cove.tool - Sustainable building design. [Win/Mac]. Available: https://www.cove.tools/ [Google Scholar]
- Crow D., Millot A. IEA; Dec. 06, 2020. Working from home can save energy and reduce emissions. But how much? – Analysis.https://www.iea.org/commentaries/working-from-home-can-save-energy-and-reduce-emissions-but-how-much [Google Scholar]
- Cutler D.M., Summers L.H. The COVID-19 pandemic and the $16 trillion virus. JAMA. Oct. 2020;324(15):1495–1496. doi: 10.1001/jama.2020.19759. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Elsaid A.M., Ahmed M.S. Indoor air quality strategies for air-conditioning and ventilation systems with the spread of the global coronavirus (COVID-19) epidemic: Improvements and recommendations. Environmental Research. Aug. 2021;199 doi: 10.1016/j.envres.2021.111314. [DOI] [PMC free article] [PubMed] [Google Scholar]
- European Agency for Safety and Health at Work (EU-OSHA) EU-OSHA; Dec. 22, 2020. COVID-19: Back to the workplace adapting workplaces and protecting workers. [Google Scholar]
- European Centre for Disease (ECDC) Prevention and Control . Mar. 2020. Considerations relating to social distancing measures in response to the COVID-19 epidemic. [Google Scholar]
- European Centre for Disease Prevention and Control (ECDC) European Centre for Disease Prevention and Control (ECDC), Stockholm; Oct. 2020. Heating, ventilation and air-conditioning systems in the context of COVID-19: First update.https://www.ecdc.europa.eu/sites/default/files/documents/Heating-ventilation-air-conditioning-systems-in-the-context-of-COVID-19-first-update.pdf [Online]. Available. [Google Scholar]
- European Industry Association (Eurovent) AISBL, IVZW, INPA . 4th ed. vol. 4. European Industry Association (Eurovent); Brussels, Belgium: 2019. Eurovent 4/21. Energy efficiency evaluation of air filters for general ventilation purposes. 21 vols. [Online]. Available: https://eurovent.eu/sites/default/files/Eurovent%20REC%204-21%20-%20Energy%20Efficiency%20Evaluation%20of%20air%20filters%20for%20general%20ventilation%20purposes%20-%20Fourth%20Edition%20-%202019%20-%20EN.pdf. [Google Scholar]
- European Industry Association (Eurovent) AISBL, IVZW, INPA . 3rd ed. vol. 4. European Industry Association (Eurovent); Brussels, Belgium: 2020. Eurovent 4/23. Selection of EN ISO 16890 rated air filter classes for general ventilation applications. [Online]. Available. [Google Scholar]
- European Industry Association (Eurovent) AISBL, IVZW, INPA . European Industry Association (Eurovent); Brussels, Belgium: Mar. 2019. Eurovent consolidated Position Paper concerning Revision of Commission Regulation (EU) No 1253/2014 (Ventilation Units). Scope: Non-residential ventilation units. [Online]. Available. [Google Scholar]
- Fabrizio E., Guglielmino D., Monetti V. Build up - The European portal for energy efficiency in buildings. 2011. Italian benchmark building models: The office building; p. 8. [Online]. Available: http://www.buildup.eu/sites/default/files/content/ITALIAN%20BENCHMARK%20BUILDING%20MODELS.pdf. [Google Scholar]
- Fana M.T., Torrejón S., Urzi Brancati C., Fernández-Macias E. European Commission; 2020. The COVID confinement measures and EU labour markets. [DOI] [Google Scholar]
- Federation of European Heating. Ventilation and Air Conditioning Associations (REHVA) Federation of European Heating, Ventilation and Air Conditioning Associations (REHVA); 2021. COVID-19 guidance document version 4.1. How to operate HVAC and other building service systems to prevent the spread of the coronavirus (SARS-CoV-2) disease (COVID-19) in workplaces.https://www.rehva.eu/fileadmin/user_upload/REHVA_COVID-19_guidance_document_V4.1_15042021.pdf Accessed: Mar. 22, 2021. [Online]. Available. [Google Scholar]
- Fencl F. Rightsizing UV-C lamps for HVAC applications. HPAC Engineering. 2013 https://www.hpac.com/air-conditioning/article/20927323/rightsizing-uvc-lamps-for-hvac-applications [Google Scholar]
- Fencl F. ES Engineered Systems; 2013. Illuminating Info: UV-C For HVAC.https://www.esmagazine.com/articles/96161-illuminating-info-uv-c-for-hvac?v=preview [Google Scholar]
- Forouzandeh N., Tahsildoost M., Zomorodian Z.S. A review of web-based building energy analysis applications. Journal of Cleaner Production. Jul. 2021;306 doi: 10.1016/j.jclepro.2021.127251. [DOI] [Google Scholar]
- Guo M., Xu P., Xiao T., He R., Dai M., Miller S.L. Review and comparison of HVAC operation guidelines in different countries during the COVID-19 pandemic. Building and Environment. 2021;187 doi: 10.1016/j.buildenv.2020.107368. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Heilingloh C.S., et al. Susceptibility of SARS-CoV-2 to UV irradiation. American Journal of Infection Control. Oct. 2020;48(10):1273–1275. doi: 10.1016/j.ajic.2020.07.031. [DOI] [PMC free article] [PubMed] [Google Scholar]
- HM Government . Conservation of fuel and power in new buildings other than dwellings. vol. L2A. 2016. Approved Document L2A, 2013 edition (with 2016 amendments) Accessed: May 17, 2021. [Online]. Available: https://assets.publishing.service.gov.uk/government/uploads/system/uploads/attachment_data/file/540328/BR_PDF_AD_L2A_2013_with_2016_amendments.pdf. [Google Scholar]
- Hogan S.K., Lucker J., Robertson R., Shafer F. Deloitte Insights; Jul. 19, 2020. If these walls could talk getting the workplace of tomorrow right.https://www2.deloitte.com/us/en/insights/focus/technology-and-the-future-of-work/workplace-of-the-future.html Online]. Available. [Google Scholar]
- Hong T., Kim J., Jeong J., Lee M., Ji C. Automatic calibration model of a building energy simulation using optimization algorithm. Energy Procedia. May 2017;105:3698–3704. doi: 10.1016/j.egypro.2017.03.855. [DOI] [Google Scholar]
- International Standard Organization (ISO) ISO/PAS 45005:2020-12 - Occupational health and safety management - General guidelines for safe working during the COVID-19 pandemic. 2020. https://www.beuth.de/de/technische-regel/iso-pas-45005/333967937 Disponível em.
- IWG International Workplace Group . IWG; Mar. 2019. The IWG Global Workspace Survey Welcome to Generation Flex – the employee power shift.https://assets.regus.com/pdfs/iwg-workplace-survey/iwg-workplace-survey-2019.pdf [Online]. Available. [Google Scholar]
- Jones D., Ivanovich M. UV-C for HVAC air and surface disinfection. 2020 ed. Air Movement and Control Association International (AMCA); 2020. pp. 2–11. [Online]. Available. [Google Scholar]
- Kemna R. ‘Average EU building heat load for HVAC equipment’, Van Holsteijn en Kemna B.V. (VHK), Brussels, Belgium, Specific contract No. ENER/C3/412-2010/15/FV2014-558/SI2.680138 with reference to Framework Contract ENER/C3/412-2010. Aug. 2014.. https://ec.europa.eu/energy/sites/ener/files/documents/2014_final_report_eu_building_heat_demand.pdf [Online]. Available.
- Kiss M. European Parliamentary Research Service (EPRS); Feb. 2021. The future of work. Trends, challenges and potential initiatives.https://www.europarl.europa.eu/RegData/etudes/BRIE/2021/679097/EPRS_BRI(2021)679097_EN.pdf Online]. Available. [Google Scholar]
- Korolija I., Marjanovic-Halburd L., Zhang Y., Hanby V.I. UK office buildings archetypal model as methodological approach in development of regression models for predicting building energy consumption from heating and cooling demands. Energy and Buildings. May 2013;60:152–162. doi: 10.1016/j.enbuild.2012.12.032. [DOI] [Google Scholar]
- Lund S., Madgavkar A., Manyka J., Smit S. McKinsey Global Institute; Nov. 23, 2020. What's next for remote work: An analysis of 2,000 tasks, 800 jobs, and nine countries.https://www.mckinsey.com/featured-insights/future-of-work/whats-next-for-remote-work-an-analysis-of-2000-tasks-800-jobs-and-nine-countries [Online]. Available. [Google Scholar]
- Martin S., Jr., Bahnfleth W.P., Jr., Dunn C., Jr., Freihaut J., Jr., Lau J., Jr., Davidovic-Nedeljkovic A., Jr. Ultraviolet germicidal irradiation. Current best practices. ASHRAE Journal. 2008:28–36. Accessed: Jul. 15, 2021. [Online]. Available: https://energia.gob.es/desarrollo/EficienciaEnergetica/RITE/Reconocidos/Reconocidos/Gu%C3%ADas%20t%C3%A9cnicas/Guia_Climatizacion_Ahorro.pdf. [Google Scholar]
- Milasi S., Fernandez E., Gonzalez-vazquez I. Joint Research Center; 2021. Telework in the EU before and after the COVID-19: Where we were, where we head to.https://ec.europa.eu/jrc/sites/default/files/jrc120945_policy_brief_-_covid_and_telework_final.pdf [Online]. Available. [Google Scholar]
- Ministére du Logement et de l’Habitat Durable Arrêté du 22 mars 2017 modifiant l'arrêté du 3 mai 2007 relatif aux caractéristiques thermiques et à la performance énergétique des bâtiments existants. Journal Officiel de la République Française. 2017:26. vol. sur 118. [Online]. Available: https://www.legifrance.gouv.fr/eli/arrete/2017/3/22/LHAL1614615A/jo/texte. [Google Scholar]
- Ministerio de Fomento . Ministerio de Fomento; 2009. Documento Básico HE. Ahorro de energía.https://www.afme.es/phocadownload/Codigo_Tecnico_de_la_Edificacion/DB-HE.pdf [Online]. Available: http://www.buildup.eu/sites/default/files/content/ITALIAN%20BENCHMARK%20BUILDING%20MODELS.pdf. [Google Scholar]
- Ministerio de Fomento . Ministerio de Fomento; 2019. Documento Básico HE. Ahorro de energía.https://www.codigotecnico.org/pdf/Documentos/HE/DBHE.pdf [Online]. Available. [Google Scholar]
- Ministero dello Sviluppo Economico . Ministero dello Sviluppo Economico; 2015. Appendice A (Allegato 1, Capitolo 3). Descrizione dell’edificio di referimento e parametri di verifica.https://www.mise.gov.it/images/stories/normativa/DM_requisiti_minimi_appendiceA.pdf [Online]. Available. [Google Scholar]
- Mo F., et al. Royal Institution of Chartered Surveyors; May 15, 2020. COVID-19 recovery guidelines for buildings - China practice.https://www.rics.org/globalassets/rics-website/media/news/covid19/covid-19-recovery-handbook-for-buildings---china-practice.pdf Online]. Available. [Google Scholar]
- Moeckel R. Working from home: Modeling the impact of telework on transportation and land use. Transportation Research Procedia. Jan. 2017;26:207–214. doi: 10.1016/j.trpro.2017.07.021. [DOI] [Google Scholar]
- Nadel S. American Council for an Energy-Efficient Economy (ACEE); 2020. Reducing COVID-19 risks in commercial buildings without wasting energy.https://www.aceee.org/blog-post/2020/10/reducing-covid-19-risks-commercial-buildings-without-wasting-energy [Google Scholar]
- Pacific Northwest National Laboratory . US Department of Energy (DOE); American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE); 2020. ANSI/ASHRAE/IES Standard 90.1-2020 - Prototype building model package.https://www.energycodes.gov/901-prototype-building-models-complete-package [Online]. Available. [Google Scholar]
- Pan Y., Du C., Fu Z., Fu M. Re-thinking of engineering operation solutions to HVAC systems under the emerging COVID-19 pandemic. Journal of Building Engineering. Nov. 2021;43 doi: 10.1016/j.jobe.2021.102889. [DOI] [Google Scholar]
- Pang P.C. Connecting knowledge & people. mondaq; 2020. The new normal: Shifting Chinese workplace policies during COVID-19. https://www.mondaq.com/china/employment-and-workforce-wellbeing/966966/the-new-normal-shifting-chinese-workplace-policies-during-covid-19 (accessed Mar. 25, 2021) [Google Scholar]
- Park S., Kim Y., Lee S., Liu B., Kim C. Coronavirus disease outbreak in call center, South Korea. Emerging Infectious Diseases. Aug. 2020;26(8):1666–1670. doi: 10.3201/eid2608.201274. [Online]. Available. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Peel M.C., Finlayson B.L., McMahon T.A. Updated world map of the Köppen-Geiger climate classification. Hydrology and Earth System Sciences. Oct. 2007;11(5):1633–1644. doi: 10.5194/hess-11-1633-2007. [DOI] [Google Scholar]
- Riley R.L., Nardell E.A. Clearing the air: The theory and application of ultraviolet disinfection. American Review of Respiratory Disease. 1989;139:1286–1294. doi: 10.1164/ajrccm/139.5.1286. [DOI] [PubMed] [Google Scholar]
- Robatherm . Robatherm; 2018. 49 instead of 9 filter classes – The air filter standard ISO 16890 in an overview.https://www.robatherm.com/de/system/files/robatherm_ISO16890_eng.pdf [Online]. Available. [Google Scholar]
- Rochard U. ‘Etude comparative des réglementations thermiques des bâtiments et labels à l’échelle européenne’, Pouget Consultants, Angers, France, 13C754. 2015. https://librairie.ademe.fr/urbanisme-et-batiment/2035-etude-comparative-des-reglementations-thermiques-des-batiments-et-labels-a-l-echelle-europeenne.html [Online]. Available.
- S. J. JJ. Rivera D.N., Herrera V.L., Morwitzer M.J., Creager H.M., Santarpia G.W., Crown K.K., Brett-Major D.M., Schnaubelt E.R., Broadhurst M.J., Lawler J.V., Reid S.P., Lowe Aerosol and surface contamination of SARS-CoV-2 observed in quarantine and isolation care. Scientific Reports. 2020 Jul 29;10(1) doi: 10.1038/s41598-020-69286-3. Dec. 08, 2020. [Online]. Available. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Shiel P., Tarantino S., Fischer M. Parametric analysis of design stage building energy performance simulation models. Energy and Buildings. Aug. 2018;172:78–93. doi: 10.1016/j.enbuild.2018.04.045. [DOI] [Google Scholar]
- Sönnichsen N. Statista; Jun. 11, 2021. Global primary energy demand change 2019-2021.https://www.statista.com/statistics/1242753/change-in-global-energy-demand/ [Google Scholar]
- Sostero M., Milasi S., Hurley J., Fernandez-Macías E., Bisello M. ‘Teleworkability and the COVID-19 crisis: A new digital divide?’, European Commission, Eurofound, JRC, Brussels, Belgium, JRC Technical Report - A Joint European Commission–Eurofound Report. May 2020. https://ec.europa.eu/jrc/sites/default/files/jrc121193.pdf [Online]. Available.
- Statista . Statista; 2021. Projected percentage change in primary energy demand in selected countries worldwide in 2021 relative to 2019 levels, by energy source.https://www.statista.com/statistics/1243592/change-in-primary-energy-demand-globally-by-fuel-and-country/ [Google Scholar]
- Stefanutti L. RCI Digital Magazine. vol. 09. Sep. 2016. La direttiva ErP per le unità di ventilazione; pp. 70–76. no. NORMATIVA. Accessed: Jul. 15, 2021. [Online]. Available: https://www.systemair.com/fileadmin/user_upload/systemair-b2b/Local/Italy/Pubblicazioni/2016_09_rci_2016_008_int_070-076.pdf. [Google Scholar]
- Taylor Engineering Taylor Engineering COVID-19 White Paper. 2020. https://taylorengineers.com/wp-content/uploads/2020/05/TE-COVID19-White-Paper.pdf [Online]. Available.
- Tenailleau Q.M., Tannier C., Vuidel G., Tissandier P., Bernard N. Assessing the impact of telework enhancing policies for reducing car emissions: Exploring calculation methods for data-missing urban areas – Example of a medium-sized European city (Besançon, France) Urban Climate. Jul. 2021;38 doi: 10.1016/j.uclim.2021.100876. [DOI] [Google Scholar]
- TSI . TSI; 2013. Percent outdoor air (%OA) calculation and its use. Application note TI-138.https://tsi.com/getmedia/5e5e04c6-f29d-4a92-80f6-2287f97c29db/Percent-Outdoor-Air-App-Note-(TI-138)-US [Online]. Available. [Google Scholar]
- U.S. Department of Health &. Human Services (HHS) Centers for Disease Control and Prevention (CDC) National Institute for Occupational Safety and Health (NIOSH) U.S. Department of Health and Human Services; 2009. Environmental control for tuberculosis: Basic upper-room ultraviolet germicidal irradiation guidelines for healthcare settings. [DOI] [Google Scholar]
- van den Kerkhoff P., van Dijk E. ‘UV-C disinfection for air, surfaces and water. UV-C market, applications and offering’, presented at the Signify Webinars (Philips Lighting) 2020. https://www.assets.signify.com/is/content/PhilipsLighting/Assets/signify/global/20200617-uvc-external-webinar.pdf [Online]. Available.
- Wang Q., Wang S. Preventing carbon emission retaliatory rebound post-COVID-19 requires expanding free trade and improving energy efficiency. Science of the Total Environment. Dec. 2020;746 doi: 10.1016/j.scitotenv.2020.141158. [DOI] [PMC free article] [PubMed] [Google Scholar]
- World Health Organization WHO coronavirus (COVID-19) dashboard. May 24, 2021. https://covid19.who.int [Online]. Available.
- World Health Organization (WHO) World Health Organization; Geneva: 2021. Roadmap to improve and ensure good indoor ventilation in the context of COVID-19, World Health Organization. Accessed: Mar. 22, 2021. [Online]. Available: https://www.who.int/publications/i/item/9789240021280. [Google Scholar]
- World Health Organization (WHO) Coronavirus disease (COVID-19): Ventilation and air conditioning in public spaces and buildings. Jul. 29, 2020. https://www.who.int/news-room/q-a-detail/coronavirus-disease-covid-19-ventilation-and-air-conditioning-in-public-spaces-and-buildings# [Online]. Available.
- World Health Organization (WHO) World Health Organization (WHO); Mar. 19, 2020. Getting your workplace ready for COVID-19: How COVID-19 spreads. Schools, businesses and institutions.https://www.who.int/publications/m/item/getting-your-workplace-ready-for-covid-19-how-covid-19-spreads [Online]. Available. [Google Scholar]
- Zhang L., Li H., Lee W.-J., Liao H. COVID-19 and energy: Influence mechanisms and research methodologies. Sustainable Production and Consumption. Jul. 2021;27:2134–2152. doi: 10.1016/j.spc.2021.05.010. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Zheng W., et al. COVID-19 impact on operation and energy consumption of heating, ventilation and air-conditioning (HVAC) systems. Advances in Applied Energy. Aug. 2021;3 doi: 10.1016/j.adapen.2021.100040. [DOI] [Google Scholar]
Associated Data
This section collects any data citations, data availability statements, or supplementary materials included in this article.
Supplementary Materials
Supplementary material