. 2022 Sep 19;39:102440. doi: 10.1016/j.csite.2022.102440

The experimental study of dehumidification and regeneration processes in a fin and tube liquid desiccant system

Wisnu Indrawan 1, Arnas Lubis 1, Nasruddin 1, MI Alhamid 1,
PMCID: PMC9484105  PMID: 40477785

Abstract

Significant focus has been placed on improving Indoor Air Quality (IAQ) due to the emergence of the large-scale severe acute respiratory syndrome (SARS) virus epidemic in the air conditioning system of buildings. There is also a need for an adequate air ventilation system that balances energy needs with air quality. This led to the discovery of liquid desiccants which have the ability to enhance air quality and lower primary energy usage as an alternative to the standard air dehumidification technology. Therefore, this study was conducted to investigate the dehumidification and regeneration processes in a Fin and tube liquid desiccant system. This involved flowing air horizontally while the ionic liquid flowed through the cooling or heating coil vertically downward to create a cross-flow fin and tube configuration. In the testing process, we obtained measurements of relative humidity and dry bulb temperature inlet and outlet from ducting by varying the input parameters. Moreover, the differential humidity ratio of the inlet and output process for the dehumidification and regeneration was observed to be essential for the dehumidifier performance indices. The experimental result showed that the system absorbed a humidity ratio of 5.5 g/kg during the dehumidification process and released 10.7 g/kg during regeneration.

Keywords: Dehumidification, Liquid desiccant, Ionic liquid, Indoor air quality, Regenerator

1. Introduction

Hot and humid air is one of the reasons excess energy is required to operate the HVAC system [1] which consumes approximately 20%–40% of the total energy used in a building [[2], [3], [4]]. Meanwhile, the vapor compression systems designed based on ASHRAE 62 and 90 standards are commonly used in HVAC dehumidifiers [[5], [6], [7]]. This is associated with the ineffectiveness of traditional systems it managing latent loads in buildings with high moisture content because of the difficulty they have in dealing with humid and hot environments, thereby, making the air in the room become moist when the cooling coil is turned off. Moreover, much attention has been placed on improving Indoor Air Quality (IAQ) at the end of the last decade due to the large-scale outbreak of the Severe Acute Respiratory Syndrome (SARS) virus in the air conditioning system of buildings [1,8]. It is also considered important because 374,329 confirmed cases of COVID-19 and 12,064 deaths were recorded in the U.S by the U.S. CDC as of April 7, 2020 [9] and the figure continued to increase. Scientific briefs reported that the particle of the virus was predominantly transmitted through exhalation sneeze and contact routes [10]. Moreover, existing data showed that the virus was also discovered in the ventilation systems of the hospital rooms COVID-19-infected patients are placed in China [9,10].

The contacts through the virus particles or droplets from human sneeze into the environmental flow were found to be playing an essential role in the transmission of the infection. This led to a current study on one of the mass transfers between the droplets and the surrounding air as well as the investigation of droplet longevity under different ambient variables such as temperature and relative humidity [11]. The findings showed that the ambient relative humidity plays an important influence in calculating droplet longevity [12] such that an increase in the humidity did not necessarily cause a reduction in the lifetime of the droplet [[12], [13], [14]]. Moreover, an efficient air ventilation system that balances low energy requirements with excellent IAQ is required when the relative humidity in the air is low [3,12]. This led to the development of liquid desiccants as one of the most promising alternative technologies for efficient dehumidification in the heating and cooling industries [15]. Furthermore, it is possible to dry air using this innovation instead of traditional dehumidification methods which require cooling the air below the dew point temperature.

Several studies have been conducted on the impact of using air conditioning systems with a liquid desiccant to dry air [[16], [17], [18]]. The findings showed that this method absorbs moisture content from the air [19] and does not require cooling below the dew point temperature like the vapor compression cooling system. The liquid desiccants are also not harmful to the environment compared to the application of CFC and HCFC systems because they only require a small amount of energy. This means this technology is a potential addition to the cooling process. Moreover, LiBr and LiCl solutions can be used as liquid desiccants [17]. LiBr solution has been discovered to have a higher density and lower specific heat capacity [20] while the LiCl solution's dehumidification process is better at the same flow rate. It was also reported that they both nearly have identical regeneration performances [21]. However, there are other novel types of liquid desiccant in addition to LiBr, LiCl, and CaCl2 [21], thereby, increasing the interest of several scholars in concentrated bittern solutions as a by-product of salt solution acting on sunlight [20].

The hygroscopic salts found in these goods such as magnesium, calcium, and sodium chloride can be used as a desiccant liquid [20]. Therefore, this study was conducted to identify the content of these salts, except for sodium chloride, to be used in cooling systems [1]. Several studies have been conducted on the properties of liquid desiccants and a large body of literature has experimental and theoretical data on air conditioning systems designed using desiccants [8]. This led this study to focus on heat and mass transfer in a cleansed dehumidifier or regenerator through an experimental test and theoretical study. Moreover, the dehumidification of air using a consistent solution has been demonstrated through experiments and theoretical research. The findings showed that the liquid containing hygroscopic salts have a consistent salt reduction which is suitable for air conditioning applications or drying processes [22,23].

The development of a new liquid desiccant dehumidifier with ionic liquid as well as fin and tube for internal cooling and heating process at different configurations in buildings was shown in literature reviews to have the ability of improving performance and reducing energy consumption in HVAC systems. However, its application is still required in several other systems.

The goal of this experiment is to investigate the utilization of an ionic liquid in the internally cooled dehumidifier and internally heated regeneration fin and tube liquid desiccant at HVAC. The specific focus is to understand the effectiveness of the dehumidification and regeneration process as well as the influence of different inlet parameters such as the ionic liquid temperature, airflow rate, and liquid desiccant flow rate on their performance.

2. Materials and methods

2.1. Experimental setup

The materials used for the experiment include measurement devices, a fresh airflow duct, centrifugal blower input, condenser, exhaust stream duct, fin and tube, and heater as indicated in Fig. 1 . The absorber and regenerator processes required installing a cooling coil and a heating coil in the middle of the duct such that the heating coil was maintained at 150 W electric heaters and the cooling coil at 300 W condenser. Moreover, Type K thermocouples were attached to the NI 9213 module and a data logger device was also applied to measure air temperatures in each section (NI-c DAQ -9174). The accuracy of the temperature sensor was ±0.01C. Furthermore, the fresh air velocities across the cooling and heating coils varied between 0.1 and 0.3 m/s and were measured at the center of the duct using a hot wire anemometer Lutron AM-4234 with an accuracy of ±0.3 m/s. At each point, the air relative humidity was also measured using the Rh sensor PR-3002-WS-N01 with an accuracy of ±3% and recorded using the NI 9203 module connected to a data acquisition device (N.I. cDAQ-9174). The experimental setup is presented in Fig. 4 while the detailed information on the device is indicated in Table 4. The ranges of the operational parameters used in this study are also listed in Table 2. It is important to note that the system was first operated at its original condition for each group of the experiment and data were later collected by changing the condition of a parameter within its range while the others are kept constant.

Fig. 1.

Fig. 1

The schematic diagram for Liquid Desiccant Dehumidifier.

Fig. 4.

Fig. 4

Experimental setup.

Table 4.

Specification of parameters and different measurement devices.

Parameters Devices Accuracy Resolution and Range
Va,r,out, Va,p,out Lutron AM – 4234SD ± (1% + 0.3 m/s) 0.1 m/s, 0.2 m/s ∼ 5 m/s
Tchw,out, Tchw,in, Thw,in, Thw,out, Ts,p,out, Ts,p,in, Ts,r,out, Ts,r,in, Ttank,p, Ttank,r Thermocouple K ±2.2 °C −270 °C–1370 °C
RH a,r,in, RH a,r,out, RH a,p,in, RH a,p,out PR-3002-WS-N01 ±3% RH 0%RH ∼ 100%RH
Ta,p,in,Ta,p,out,Ta,r,in, Ta,r,out PR-3002-WS-N01 ±0.5 °C −40 °C ∼ +80 °C
F chw,in, F hw,in, F s,r,in, and F s,p,in YFS - 301 ±3% 0.3–10 (L\ min)
E.C. p, E.C. r Conductivity Probe K 1.0 ± 2% 5–200.000 μ S

Table 2.

The fin and tube dehumidifier and regenerator experimental range.

Condition m a (g/s) ta,in( °C) m s (kg/s) ts,in( °C) Xin (%) T chw,in T hw,in V in
Dehumidification 3–11 27–28 0.4–0.6 15–20 50–60 12–19 0.1–0.3
Regeneration 4–9 26–29 0.5–0.6 38–60 50–60 30–60 0.1–0.3

The fresh air absorber (process) side was cooled and dehumidified by passing through a cooling coil device with flowing chilled water and a strong liquid desiccant solution sprayed over the whole cooling coil surface. The combined heat and mass transfer process occurred in the air and desiccant solution flow direction such that the sprayed desiccant solution absorbed moisture from the process air when they were in contact in the cooling coil. It is important to note that the design supply airflow rate for both the dehumidifiers and regenerators in this experiment was 0.225 m2/s. Meanwhile, on the regenerator side, the air from the centrifugal blower was heated and regenerated by passing through a heating coil device containing flowing heated water, and the entire surface of the heating coil was sprayed with a weak liquid desiccant solution and this released the moisture from the liquid desiccant in the regeneration air when they were in contact.

2.2. Thermophysical ionic liquid properties

Common desiccants, such as trimethylene glycol, are flammable and detrimental to the surrounding environment. The apparent disadvantages of common desiccants such as CaCl2, LiCl, LiBr, and their mixtures, including their tendency to crystallize, corrosiveness towards metals, and environmental pollution, outweigh the advantage of their relatively low vapor pressure. Due to their characteristics, ionic liquids (IL) are currently the subject of extensive research [24]. IL are molten salts containing organic cations and inorganic anions that exist at room temperature. Researchers have examined numerous applications, such as synthetics, catalysts, lubricants, separating agents, and electrolyte materials. However, ionic liquids have not been the subject of any research to date. IL remain liquid at room temperature and exhibit excellent fluidity over a wide temperature range. In addition, they have very low vapor pressure, and some of them are non-corrosive. All of these characteristics make IL useful for dehumidification in liquid desiccant air conditioning systems [24]. This experiment utilized IL possessing the thermophysical properties shown in Table 1 . In general, IL had excellent solubility with a variety of organic compounds, low volatility, and high thermal and chemical stability, which made them suitable for absorption processes such as those found in liquid desiccant systems.

Table 1.

Thermophysical properties of ionic liquid in the present study compared with other ionic liquids in the literature study.

Ionic Liquid IL mass fraction X, % Temperature T, °C Density
ρ, kg.m−3
Viscosity μ, Pa.s Thermal Conductivity
λ, W.m−1. K −1
Spesific Heat
Cp, kJ.kg −1. K−1
Present work 0–80 25 997–1154 0.001–0.032 0.607–0.274 1.7–4.2
[HEA]La [25], ∼99 25 1201.785 0.255 1.8
[BHEA]La [25], ∼99 25 1218.433 0.236 1.78
[THEA]La [25], ∼99 25 1235.933 0.226 1.75
[EMIm]Ac [26] 80 20 1100.82 0.022 0.27 2.35
[EMIM][FSI] [27] ∼99 15 1451.11 0.026
[BMPYR][FSI] [27] ∼99 15 1314.74 0.078
[MPEG550 (bim)][Tf2N] [28] 70 25 1285.4 0.28
[MPEG750 (bim)][Tf2N] [28] 70 25 1251.5 0.37
[BMIm] [PF6] [29] 99 20 1371.1
[BMMIm] [Cl] [30] 98 20 998.2
[Mmim](MeO)2 PO2 [31] 55 59.85 0.65

With the exception of [EMIm]Ac from F.F. Zhang et al. and [BMMIm] [Cl] from Anuja Jain et al. the IL used in the present study has a lower density than other IL listed in Table 1. Except for [EMIM][FSI] and [BMPYR][FSI] from F.F. Zhang et al. the viscosity of the IL in this study is lower than all of those listed in Table. Due to its low density and viscosity, the IL utilized in this experiment has a low pumping expense.

2.3. Performance dehumidification and regeneration

Fig. 2 shows the structured fin and tube used as a control volume (CV) with heat and mass transfer interactions between the liquid desiccant and humid air. The enthalpy of the air regeneration and process was calculated using EES (Engineering Equation Solver) as follows:

ha = f (T,ω,P) (1)

Fig. 2.

Fig. 2

The energy balance of the structured fin and tube used as a control volume of a. Regeneration b. Process.

The humidity ratio for in-process and regeneration was also later determined as follows:

ωa = f (Rh, T) (2)

The specific heat of solution and chilled water were determined using the following equations:

Cp s = f (T, X) (3)
Cp water = f (T, x) (4)

The concentration of ionic liquid was calculated as follows [32,33]:

X = f (EC, T) (5)

The moisture removal and regeneration rates also known as the performance analysis of dehumidification process and regeneration presented in Equations (6), (7)) respectively are the indices commonly used to evaluate the dehumidification and regeneration processes associated with the use of liquid desiccants [16,17,34]. Detail dimensions of the fin and tube heat exchanger were described in Table 3, and Fig. 3 Shown the fin and tube at using in this study.

m w,p = m a,p. (ω a,p,in - ω a,p,out) (6)
m w,r = m a,r. (ω a,p,out - ω a,p,in) (7)

Table 3.

Dimensions of fin and tube heat exchanger.

Parameter Dimension
Number of tube columns (horizontal array) 2
Number of tube rows (vertical array) 5
Fin thickness 2 × 10−4 m
Fin pitch 2 × 10−3 m
Tube outer wall diameter 1.4 × 10−2 m
Tube wall thickness 1.3 × 10−3 m
Tube horizontal pitch 3 × 10−2 m
Tube vertical pitch 3 × 10−2 m

Fig. 3.

Fig. 3

Liquid desiccant dehumidifier fin and tube.

2.4. Uncertainty analysis and repeatability

The uncertainty analysis was conducted to assess the consistency of the dependent parameters, and the measurement points were based on the standard deviation of each sensor. Moreover, the calculated parameters associated with the mass flowrates of each operating parameter were determined through Eq (9) [35], and the measuring point was determined through Eq (10) [36] values obtained are presented in Table 5 .

U=U(Ux,Uy) (8)
σU2=(UUx)2σUx2+(UUy)2σUy2 (9)
U(xi) =ix3 (10)

where Ux … Uy are different independent parameters while U is the dependent parameter, and the accuracy of each sensor device is. ix

Table 5.

Point of measurement at Experimental Condition.

Measurement point Value Calculated parameters Value
Temperature (°C) Mass flowrate Air (kg/s)
Ts,p,in 15.5 ± 1.27 m a_p_in 0.34 ± 0.4
Ts,p,out 15.7 ± 1.27 m a_r_in 0.91 ± 0.4
Ta,p,in 29.7 ± 1.27 Mass flow rate Ionic Liquid (kg/s)
Ta,p,out 26.8 ± 1.27 m s_p_in (0.5 ± 0.1) x 10−1
T c,hw,in 10.2 ± 1.27 m s_r_in (0.53 ± 0.1) x 10−1
T c,hw,out 12.8 ± 1.27 Mass flowrate Chilled Water (kg/s)
T tank,p 24.4 ± 1.27 m chw_in (0.56 ± 0.008)
Ta,r,in 29.5 ± 1.27 m hw_in (0.1 ± 0.004)
Ta,r,out 31.5 ± 1.27
Ts,r,in 38.1 ± 1.27
T,s,r,out 37.4 ± 1.27
T tank,r 37.8 ± 1.27
T ht, in 38.4 ± 1.27
T ht, out 38.2 ± 1.27
Relative Humidity (%)
Rh p, in 73.3 ± 1.7
Rh p,out 62.4 ± 1.7
Rh r,in 72.6 ± 0.017
Rh r,out 79.9 ± 0.017
Electrical Conductivity (mS)
EC p 11.1 ± 0.01
EC r 21.5 ± 0.01
Flow (l/m)
F s,p,in 2.57 ± 5.7
F c,w,in 3.42 ± 5.7
F s,r,in 2.88 ± 5.7
F ht,in 6.52 ± 5.7
Velocity (m/s)
V a,p,out 0.1 ± 0.05
V a,r,out 0.3 ± 0.05

The Reapitibility of the experiments has also been checked, and one of the observations of Rh p,out for two different runs is shown in Fig. 5 [37].

Fig. 5.

Fig. 5

Reapitibility of Rh p,out.

3. Results and discussion

3.1. Fin and tube liquid desiccant performance

The chilled water temperature in the experiment was set to be constant at 10 °C for the dehumidification process while the input hot water was constant at 36 °C for the regeneration process. The solution and air outlet temperature slightly decreased due to heat transfer into chilled water which increased its output temperature compared to its inlet temperature. Moreover, the relative humidity output also slightly decreased due to mass transfer from the air inlet to the solution inlet as indicated in Fig. 6 c and Fig. 6e.

Fig. 6.

Fig. 6

The Effect of Inlet parameters at regeneration and dehumidification on performance.

The solution and air outlet temperature for the regeneration slightly increased due to heat transfer from hot water to solution and air, thereby, leading to a reduction in the output temperature of the hot water compared to its inlet temperature. Meanwhile, the relative humidity output slightly decreased due to mass transfer from the air inlet to the solution inlet as presented in Fig. 6d and f.

The dehumidification performance was determined using Equation (6) and the moisture removal rate of the air inlet process was found to be 0.0018 g/kg. According to Liu et al. [16,17], the concentration of liquid desiccant can affect dehumidification and regeneration performance and this was further confirmed by the constant values of these parameters as presented in Fig. 6g and a. Meanwhile, the regeneration performance was determined using Equation (7) and the moisture release rate of the air inlet was found to be 0.039 g/kg with the concentration and performance of the regeneration process observed to slightly increase as shown in Fig. 6h and b.

3.2. Effects of inlet parameters on the humidity ratio regeneration and dehumidification process

3.2.1. Airflow rate

Fig. 7 shows the relationship between air mass flow rate and humidity ratio associated with the mass transfer performance during the dehumidification process. It was discovered that there is a difference between the humidity ratio input and output processes and the regeneration was also observed to have decreased due to the increase in air mass flow rate. Moreover, the decreasing moisture content in the air inlet caused the Δ Humidity ratio to reduce. Humidity ratio on the regeneration side decreases from the first variation of airflow rate with a value of 6.54 g/kg to the last variation of airflow rate with a value of 4.55 g/kg. In the dehumidification process, the Humidity ratio decreases from the initial variation of air flow rate with a value of 5.55 g/kg to the final variation of air flow rate with a value of 5.12 g/kg.

Fig. 7.

Fig. 7

Effects of the airflow rate parameters on the dehumidification process and regenerator performance.

3.2.2. Desiccant flow rate

The effect of liquid desiccant flow rate on dehumidification and regeneration is presented in Fig. 8 and it was discovered that an increase in the flow rate of the solution used in the dehumidification process caused a significant increment in the difference between the humidity ratio of the incoming and outgoing air. Meanwhile, an increase in the flow rate of the solution used in the regeneration reduced the humidity ratio between the inlet and outlet air. Humidity ratio on the regeneration side decreases from the first variation of flow rate solution regeneration with a value of 10.74 g/kg to the last variation of flow rate solution regeneration with a value of 6.18 g/kg. Humidity ratio in the dehumidification process increases from the initial variation of flow rate solution process with a value of 2.06 g/kg to the final variation of flow rate process with a value of 4.6 g/kg.

Fig. 8.

Fig. 8

Effects of the flow solution parameters on the dehumidification process and regenerator performance.

3.2.3. Liquid desiccant inlet temperature

The effect of ionic liquid temperature on the humidity ratio in the dehumidification process is presented in Fig. 9 and the findings showed that a smaller ionic liquid temperature led to a greater Humidity ratio. This is due to the increase in the surface vapor pressure of the liquid and a reduction in the average vapor pressure difference between the air and ionic liquid in the dehumidifier as the temperature of the ionic liquid increases [34]. This phenomenon caused a high humidity ratio outlet and subsequently led to a low water vapor content. This simply means there was a decrease in water vapor levels when the ionic liquid temperature increased.

Fig. 9.

Fig. 9

Effects of the liquid desiccant temperature on the dehumidification process and regenerator performance.

Fig. 9 also shows that higher regenerator temperature produced a higher humidity ratio because a lot of water vapor was released from the ionic liquid, thereby, increasing the outlet water vapor content. Humidity ratio on the regeneration side increases from the first variation of flow rate solution regeneration with a value of 4.59 g/kg to the last variation of flow rate solution regeneration with a value of 9.15 g/kg. Humidity ratio in the dehumidification process decreases from the initial variation of flow rate solution process with a value of 5.54 g/kg to the final variation of flow rate process with a value of 3.36 g/kg.

3.3. Psychometric profile diagram of dehumidification process and regenerator

3.3.1. Psychometric profile diagram in the dehumidification process

The psychometric profile diagram for the ionic liquid temperature of the dehumidification process at 15.5 °C is presented in Fig. 10 where the outlet parameters used when the experiment was first conducted are indicated in Point 1 and those after the experiment was completed at Point 11. The detailed information on this profile is explained in the following Table 6 .

Fig. 10.

Fig. 10

Psychometric profile at ionic liquid temperature 15.5 °C in the process outlet air.

Table 6.

Dehumidification performance at different variations of Ts,p, out 15.5.°C

T a,p, out (°C) Rh a,p, out (%) h a,p, out (kJ/kg) ωa,p,out (g/kg)
27.6 81.72 76.5 19.1
27.4 78.8 74 18
26.8 73.5 68.6 16.3
26.7 71.4 67 15.7
26.6 71.3 66.6 15.6
26.5 71.2 66.2 15.5
26.5 69 64.9 15
26.4 68.5 64.3 14.8
26.4 68.1 64.1 14.7
26.3 68 63.7 14.6
26.2 64 61.6 13.8

Points 1 to 11 show a decrease in the humidity ratio by 5.3 (g/kg) water vapor content as confirmed in Fig. 10 that the air entering Ta,p, out at Point one has 19.1 (g/kg) humidity ratio and 76.5 (kJ/kg) enthalpy but 13.8 (g/kg) and 61.6 (kJ/kg) respectively at Point 11. Moreover, Table 6 shows that the enthalpy slightly decreased due to heat transfer from inlet air to inlet solution and chilled water.

3.3.2. Psychometric profile diagram in the regeneration process

The psychometric profile diagram for the ionic liquid temperature of the regeneration process at 38 °C is presented in Fig. 11 . It is also important to note that Point one shows the outlet parameters when the experiment was first conducted while Point 11 indicates the parameters after the completion of the experiment. The detailed information on this profile is explained in the following Table 7 .

Fig. 11.

Fig. 11

Psychometric profile at ionic liquid temperature 38 °C in the regeneration outlet air.

Table 7.

Dehumidification performance for the variation of the Ts,r,out 38.°C

T a,r,out (°C) Rh a,r,out (%) h a,r, out (kJ/kg) ωa,r,out (g/kg)
27.8 77.9 77.9 19.5
29.2 85.1 85.1 21.7
30 87.1 87.1 22.2
30 88.9 88.9 22.7
30.5 88.3 88.3 22.5
30.8 89.2 89.2 22.7
31.2 91 91 23.3
31.3 91.5 91.5 23.4
31.3 91.4 91.4 23.3
31.1 90 90 22.9
31.1 89.7 89.7 22.8

Points 1 to 11 show an increase in the humidity ratio by 3.3 (g/kg) water vapor content and this was further confirmed by Fig. 11 that the air entering Ta,r, out in Point one has a 19.5 (g/kg) humidity ratio and 77.9 (kJ/kg) enthalpy and these increased to 22.8 (g/kg) and 89.7 (kJ/kg) respectively in Point 11. It was also discovered that the enthalpy slightly increased due to the heat transfer from inlet hot water to inlet air and solution.

3.4. Comparison of inlet and outlet humidity ratio in the dehumidification process

Table 8 summarizes the trends concerning the impacts of inlet parameters on the delta humidity ratio of the current cross-flow absorber (process) as well as the experimental results reported for the counter-flow process in previous studies. The inlet settings generally have similar effects on the current cross-flow performance and counter-flow designs with exceptions mainly associated with the difference in the parameter range. For example, the delta humidity ratio increased with the desiccant flow rate in this study. It is also important to note that Richard Jayson Varela used a fin and tube with a larger volume and surface area and the comparison of the results to the present study showed that the application of a larger volume can increase the effectiveness of dehumidification in the liquid desiccant.

Table 8.

Comparison of other studies related to dehumidifier.

Reference Liquid Desiccant Inlet Parameter
Air Inlet Parameter
Δ ω process (g/kg)
Type Air – Solution flow configuration T,s (°C) X (%) Flow rate (l/min) Flow rate (kg/s) Temp °C
Goswami [38] LiCl Packed – bed 30.1 33.9 6.273 1.214 30.3 3.9
Jain et al. [39] TEG Shell and Tube 21.8 92.2 0.052 0.051 21 4.21
Mago Goswami [40] LiCl Random Packing 27–30 35 0.35–0.51 0.6–0.7 26–29 2 to 4
Pietruschka et al. [41] LiCl Structure Packing 27 43 1.67 3.3 26 4.2
CaCl2 Structure Packing 27 43 1.67 3.3 26 5.7
Zurigat et al. [42] TEG Structure Packing by wood 31 95.6 0.23 1.73 30.6 3
Richard Jayson Varela [43] IL Fin – Tube
Volume:
8 × 10−3 m3
Surface Area:
0.08 m2
17.5 75 0.06 34 11
Present Study Ionic Liquid (I.L.) Fin – Tube
Volume:
675 × 10−6 m3
Surface Area:
225 × 10-4 m2
15 5969 2.5 0.008 2829 5.5

4. Conclusions

This study showed that a liquid desiccant dehumidifier with ionic liquid as well as fin and tube can be applied on a large scale as indicated by the experimental results. It was also discovered that a greater ionic liquid temperature in the dehumidification process led to a smaller Δ ω a,p as indicated by the different 15.5 °C, 17.4 °C, and 19.4 °C temperatures that produced 5.27 g/kg, 3.42 g/kg, 3.36 g/kg humidity ratio respectively. Meanwhile, for the regeneration, an increase in the ionic liquid temperature was observed to have caused an increment in the Δ ω a,r. This was evident in the 3.2 g/kg, 5.36 g/kg, and 9.15 g/kg humidity ratios recorded for 38.1 °C, 40.9 °C, and 55.4 °C ionic liquid temperatures respectively. Moreover, a larger air mass flow rate in the dehumidification process produced a smaller humidity ratio as indicated by 5.55 g/kg, 5.25 g/kg, and 5.12 g/kg humidity ratios for 3.31 g/s, 5.88 g/s, and 10.44 g/s mass flow rates respectively. The situation is different for the regeneration process such that a higher air mass flow rate was observed to have led to a higher humidity ratio as evident by the 6.54 g/kg, 4.96 g/kg, and 4.55 g/kg humidity ratio values respectively recorded for 4.36 g/s, 6.86 g/s, and 8.66 g/s air mass flow rates. Furthermore, it was also discovered that a greater ionic liquid flow in the dehumidification process led to a better Δ ω a,p as indicated by the different 80 l/h, 100 l/h, and 150 l/h flow rate humidity ratio, respectively. Moreover, for the regeneration, an increase in the ionic liquid flow rate was observed to have caused a decrement in the Δ ω a,r. This was evident in the 10.74 g/kg, 8.62 g/kg, and 6.18 g/kg humidity ratios recorded for 80 °C, 100 °C, and 150 °C ionic liquid temperatures, respectively.

Credit author statement

Wisnu Indrawan Conceptualization, Methodology, Experimental, Writing - Original Draft. Arnas Lubis: Methodology, Writing - Review & Editing. M. Idrus Alhamid: Validation, Supervision, Original Idea. Nasruddin: Supervision.

Declaration of competing interest

The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.

Acknowledgement

The authors would like to express their gratitude to Universitas Indonesia, Depok, Indonesia for the financial support under PUTI Q2 Program Research Grant 2020 with contract number BA-717/UN2. RST/PPM.00.03.01/2021.

Nomenclature

ω

Humidity Ratio (g/kg)

m˙a

Massflowrate air (kg/s)

v

Velocity of air (m/s)

ρudara

Mass jenis udara (kg/m3)

mS

Millisiemens

m˙s

Mass flowrate solution (kg/s)

m˙(chw)

Mass flowrate chilled water (kg/s)

m˙(hw)

Mass flowrate hot water (kg/s)

T

Temperature (oC)

Δ

Delta (Difference of inlet and outlet, and vice versa)

Special Character

F

Flowrate (l/m)

EC

Electrical Conductivity (mS)

Subscript

a

(air)

a,p, in

(Fresh air prosses input)

a,p, out

(Fresh air prosses output)

a,r, in

(Fresh air regeneration input)

a,r, out

(Fresh air regeneration output)

s,p, in

(Solution process inlet)

s,p, out

(Solution process outlet)

s,r, in

(Solution process inlet)

s,r, out

(Solution process outlet)

tank, p

(Tank in process system)

tank, r

(Tank in regeneration system)

chw

(Chilled water inlet)

hw

(Hot Water inlet)

X

(Concentration)

Data availability

Data will be made available on request.

References

  • 1.Gurubalan A., Maiya M.P., Geoghegan P.J. A comprehensive review of liquid desiccant air conditioning system. Appl. Energy. 2019:254. [Google Scholar]
  • 2.Nasruddin, et al. Solar absorption chiller performance prediction based on the selection of principal component analysis. Case Stud. Therm. Eng. 2019;13 [Google Scholar]
  • 3.Siricharoenpanich A., et al. Effect of cooling water loop on the thermal performance of air conditioning system. Case Stud. Therm. Eng. 2019;15 [Google Scholar]
  • 4.Kim B.-J., Dong H.-W., Jeong J.-W. Applicability of an organic Rankine cycle for a liquid desiccant-assisted dedicated outdoor air system in apartments. Case Stud. Therm. Eng. 2021;28 [Google Scholar]
  • 5.Buker M.S., Riffat S.B. Recent developments in solar assisted liquid desiccant evaporative cooling technology—a review. Energy Build. 2015;96:95–108. [Google Scholar]
  • 6.Cheng Q., Zhang X. Review of solar regeneration methods for liquid desiccant air-conditioning system. Energy Build. 2013;67:426–433. [Google Scholar]
  • 7.Fekadu G., Subudhi S. Renewable energy for liquid desiccants air conditioning system: a review. Renew. Sustain. Energy Rev. 2018;93:364–379. [Google Scholar]
  • 8.Rafique M.M., Gandhidasan P., Bahaidarah H.M.S. Liquid desiccant materials and dehumidifiers – a review. Renew. Sustain. Energy Rev. 2016;56:179–195. [Google Scholar]
  • 9.Zheng W., et al. COVID-19 impact on operation and energy consumption of heating, ventilation and air-conditioning (HVAC) systems. Advances in Applied Energy. 2021;3 [Google Scholar]
  • 10.Berry G., et al. A review of methods to reduce the probability of the airborne spread of COVID-19 in ventilation systems and enclosed spaces. Environ. Res. 2022;203 doi: 10.1016/j.envres.2021.111765. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 11.Gómez-Castro F.M., et al. Review of indirect and direct solar thermal regeneration for liquid desiccant systems. Renew. Sustain. Energy Rev. 2018;82:545–575. [Google Scholar]
  • 12.Chen L.D. Effects of ambient temperature and humidity on droplet lifetime - a perspective of exhalation sneeze droplets with COVID-19 virus transmission. Int. J. Hyg Environ. Health. 2020;229 doi: 10.1016/j.ijheh.2020.113568. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 13.Wen T., et al. Development of a novel quasi-3D model to investigate the performance of a falling film dehumidifier with CFD technology. Int. J. Heat Mass Tran. 2019;132:431–442. [Google Scholar]
  • 14.Luo Y., et al. Application of CFD model in analyzing the performance of a liquid desiccant dehumidifier. Energy Proc. 2016;88:491–497. [Google Scholar]
  • 15.Crofoot L., Harrison S. Performance evaluation of a liquid desiccant solar air conditioning system. Energy Proc. 2012;30:542–550. [Google Scholar]
  • 16.Liu X.H., et al. Experimental investigation of the heat and mass transfer between air and liquid desiccant in a cross-flow regenerator. Renew. Energy. 2007;32(10):1623–1636. [Google Scholar]
  • 17.Liu X.H., et al. Experimental study on mass transfer performances of cross flow dehumidifier using liquid desiccant. Energy Convers. Manag. 2006;47(15-16):2682–2692. [Google Scholar]
  • 18.Alhamid M.I., et al. Operation strategy of a solar-gas fired single/double effect absorption chiller for space cooling in Indonesia. Appl. Therm. Eng. 2020:178. [Google Scholar]
  • 19.Zhang T., et al. Experimental analysis of an internally-cooled liquid desiccant dehumidifier. Build. Environ. 2013;63:1–10. [Google Scholar]
  • 20.Chen X., et al. Recent progress in liquid desiccant dehumidification and air-conditioning: a review. Energy. Built. Environ. 2020;1(1):106–130. [Google Scholar]
  • 21.Gurubalan A., Simonson C.J. A comprehensive review of dehumidifiers and regenerators for liquid desiccant air conditioning system. Energy Convers. Manag. 2021:240. [Google Scholar]
  • 22.Alahmer A., Alsaqoor S., Borowski G. Effect of parameters on moisture removal capacity in the desiccant cooling systems. Case Stud. Therm. Eng. 2019;13 [Google Scholar]
  • 23.Ghosh K.K., et al. Experimental investigations on indirect contact type liquid desiccant cooling systems for high latent heat load application. Case Stud. Therm. Eng. 2022;31 [Google Scholar]
  • 24.Luo Y., et al. Dehumidification performance of [EMIM]BF4. Appl. Therm. Eng. 2011;31(14-15):2772–2777. [Google Scholar]
  • 25.Faraji S., et al. Experimental studies on thermophysical properties of protic ionic liquids for thermal energy storage systems. J. Energy Storage. 2022;54 [Google Scholar]
  • 26.Zhang F.F., et al. Thermophysical properties and water sorption characteristics of 1-ethyl-3-methylimidazolium acetate ionic liquid and water binary systems. Int. Commun. Heat Mass Tran. 2021;127 [Google Scholar]
  • 27.Havlová M., Dohnal V. Phase equilibria and thermophysical properties of aqueous solutions of two bis(fluorosulfonyl)imide-based ionic liquids. Fluid Phase Equil. 2021:547. [Google Scholar]
  • 28.Pei Y., et al. Physicochemical properties and thermal-responsive phase separation of poly(ethylene glycol)-based ionic liquids. J. Mol. Liq. 2022:360. [Google Scholar]
  • 29.Jamal M.A., et al. Explication of molecular interactions between leucine and pharmaceutical active ionic liquid in an aqueous system: volumetric and acoustic studies. J. Mol. Liq. 2022:360. [Google Scholar]
  • 30.Jain A., Zodape S.P. Solvation properties of 1-butyl 2, 3-dimethyl imidazolium chloride ionic liquid in aqueous and aqueous glycine solutions at different temperatures using volumetric and compressibility parameters. J. Mol. Liq. 2022:363. [Google Scholar]
  • 31.Abbasi M., et al. Thermophysical and rheological properties of sorbitol + ([mmim](MeO)2PO2) ionic liquid solutions: solubility, density and viscosity. Food Chem. 2020;320 doi: 10.1016/j.foodchem.2020.126566. [DOI] [PubMed] [Google Scholar]
  • 32.Gong Y., et al. Thermodynamic performance assessment of ammonia/ionic liquid based half-effect absorption refrigeration cycle. Case Stud. Therm. Eng. 2021;25 [Google Scholar]
  • 33.Pająk M., Hubkowska K., Czerwiński A. Improved hydrogen sorption properties of Pd in protic and aprotic ionic liquids effected by superacid addition. J. Alloys Compd. 2022;903 [Google Scholar]
  • 34.Liu J., et al. Experimental analysis of an internally-cooled/heated liquid desiccant dehumidifier/regenerator made of thermally conductive plastic. Energy Build. 2015;99:75–86. [Google Scholar]
  • 35.Kline S.J. Describing uncertainty in single sample experiments. Mech. Eng. 1953;75:3–8. [Google Scholar]
  • 36.Zakharov I.P., Botsyura O.A. Calculation of expanded uncertainty in measurements using the kurtosis method when implementing a bayesian approach. Meas. Tech. 2019;62(4):327–331. [Google Scholar]
  • 37.Bhandari P., Prajapati Y.K. Influences of tip clearance on flow and heat transfer characteristics of open type micro pin fin heat sink. Int. J. Therm. Sci. 2022;179 [Google Scholar]
  • 38.Fumo N., Goswami D. Study of an aqueous lithium chloride desiccant system: air dehumidification and desiccant regeneration. Sol. Energy. 2002;72(4):351–361. [Google Scholar]
  • 39.Sanjeev J., et al. Proceedings of ACRECONF. Allied Publishers; New Delhi: 2003. Drift and wetting characteristics of falling film absorber and regenerator; pp. 16–25. [Google Scholar]
  • 40.Mago P., Goswami D.Y. International Solar Energy Conference. American Society of Mechanical Engineers; 2001. A study of the performance of a hybrid liquid desiccant cooling system using lithium chloride. [Google Scholar]
  • 41.Pietruschka D., et al. Experimental performance analysis and modelling of liquid desiccant cooling systems for air conditioning in residential buildings. Int. J. Refrig. 2006;29(1):110–124. [Google Scholar]
  • 42.Zurigat Y., Abu-Arabi M., Abdul-Wahab S. Air dehumidification by triethylene glycol desiccant in a packed column. Energy Convers. Manag. 2004;45(1):141–155. [Google Scholar]
  • 43.Varela R.J., et al. Experimental performance of a three-fluid desiccant contactor using a novel ionic liquid. Appl. Therm. Eng. 2022:210. [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Data Availability Statement

Data will be made available on request.


Articles from Case Studies in Thermal Engineering are provided here courtesy of Elsevier