Monitoring Porcelain Insulator Condition Based on Leakage Current Characteristics

Ali Ahmed Salem 1, Kwan Yiew Lau 1,*, Mohd Taufiq Ishak 2,*, Zulkurnain Abdul-Malek 1, Samir A Al-Gailani 3, Salem Mgammal Al-Ameri 1, Ammar Mohammed 4, Abdulaziz Ali Saleh Alashbi 4, Sherif S M Ghoneim 5
Editors: Hone-Zern Chen, Albena Paskaleva
PMCID: PMC9504817  PMID: 36143682

Abstract

Insulator monitoring using leakage current characteristics is essential for predicting an insulator’s health. To evaluate the risk of flashover on the porcelain insulator using leakage current, experimental investigation of leakage current indices was carried out. In the first stage of the experiment, the effect of contamination, insoluble deposit density, wetting rate, and uneven distribution pollution were determined on the porcelain insulator under test. Then, based on the laboratory test results, leakage current information in time and frequency characteristics was extracted and employed as assessment indicators for the insulator’s health. Six indicators, namely, peak current indicator, phase shift indicator, slope indicator, crest factor indicator, total harmonic distortion indicator, and odd harmonics indicator, are introduced in this work. The obtained results indicated that the proposed indicators had a significant role in evaluating the insulator’s health. To evaluate the insulator’s health levels based on the extracted indicator values, this work presents the naïve Bayes technique for the classification and prediction of the insulator’s health. Finally, the confusion matrix for the experimental and prediction results for each indicator was established to determine the appropriateness of each indicator in determining the insulator’s health status.

Keywords: porcelain insulator, contamination, leakage current characteristics, classification

1. Introduction

Outdoor insulators are important in electrical power transmission systems. However, the efficiency and health of the insulators are greatly impacted by numerous environmental factors, including wetness and contamination. Outdoor environmental factors, such as contamination and moisture, have a significant impact on insulator effectiveness. Moisture, such as rain and fog, in the presence of pollution reduces the surface resistance of insulators. Surface resistance lowering may result in higher leakage current flowing on the surface and dry band arcing. A large magnitude of leakage currents flowing on the surface over an extended length of time may produce insulator surface deterioration, which might eventually lead to flashover [1,2,3,4,5,6]. The unwanted discharge may result in a flashover phenomenon that leads to electrical grid disruption or even failure [7,8,9]. It is, therefore, crucial to monitor the status of the insulators to ensure that they are fit for purpose [10,11]. This would further strengthen the efficiency of the power grid and decrease its failure probability.

The evaluation of the performance of outdoor insulators continues to be a significant topic in the high-voltage community [12,13,14,15]. The use of the leakage current (LC) parameter in observing the performance of outdoor insulators has been popular and offers many advantages. This is because LC monitoring considers various environmental conditions, such as temperature, humidity, pollution, and rain [16]. Moreover, LC monitoring can be done online on a continuing basis. Examples of LC monitoring techniques include the use of the microwave reflectometer system, which has been used to monitor LC for dry insulator surfaces [17]. However, this type of monitoring system is less cost-effective. The authors in [18] offer an alternative method that uses an antenna to monitor LC on polluted insulators by capturing electromagnetic radiation resulting from partial discharge on the insulator. The advantage of this system is that the components used are not damaged by flashover voltage, as is the case of other systems. To the best of our knowledge, however, this system has yet to be tested under large electromagnetic interference caused by coronas and other effects of high-voltage conductors.

Another issue of interest in the monitoring technique of polluted insulator LC refers to the competence to establish a strong link between the LC and the condition of the insulator under service. Many researchers have offered various approaches to evaluate the physical state of insulators [16,19,20,21]. Improvement in LC-based monitoring is achieved by extracting information from the LC components. The LC statistical results, such as average, maximum, and standard deviation, recommended by [22] were used for evaluating the level of contamination. These researchers suggested that these parameters allow the quantification of the dimensions and density of the contamination layer over the surface of the insulator. Another study [19] assessed the contaminated insulator conditions by evaluating the phase angle between current and voltage signals. According to the results in [19], phase angle differences are a helpful indication for assessing contaminants and humidity fluctuations in a clean environment.

The assessment of the LC signal in the frequency domain through fast Fourier transform (FFT) and wavelet transformations is also a relevant technique used to predict insulators’ pollution status [23,24,25]. Overall, the results have indicated that contaminants on the insulator amplify the harmonic of leakage current components, especially the harmonics in an odd order. The results imply that the contamination leads to the rise of the first and third harmonics and the total harmonic distortion (THD) [26]. The concerned harmonics are the first and third component harmonics under an AC voltage. Accordingly, the study found that increasing these harmonics causes a rise in THD, which changes according to the change in the level of contamination and harmonics of the supplied voltage [27].

Some publications in the literature have proposed several numerical indices to identify the performance of overhead line insulators. As far as we are aware, none of them evaluated the performance of insulators using one specific indicator. In direct connection, acoustic and thermal-based diagnostic methods, such as ultrasonic wave [28] and acoustic fault diagnosis [29], have been used to evaluate the health of overhead lines insulator. However, the performance of these techniques is affected by the acoustic frequency noise generated from the electromagnetic field of the overhead line. Infrared thermal imaging [30] and temperature analysis of infrared insulator images [31] are utilized to diagnose polluted insulators as well. However, these techniques rely only on the thermal behavior of the insulator, which is limited in revealing an accurate insulator state. Although the wireless-based system [32] and network sensors [18] show good performance in monitoring insulator conditions, their high sensitivity to environmental weather, such as dust and rain, influences the accuracy of the results.

It is essential to have an indicator reflecting the condition of the insulators [16,20]. The extraction of the LC components based on the frequency domain to calculate the relevant indicators were performed. For example, the ratio of leakage current’s third to fifth harmonic indicator (fifth/third) was extracted to estimate flashover incidences [27]. The published findings for silicon rubber and glass insulators show good correlation between the magnitude of the contamination and the reading of this indicator. In addition, the literature review demonstrated that no attempt has been made to investigate the insulators’ conditions using indices considering the slope of the signal in the time domain and the odd harmonic components between 0 and 500 Hz for LC. This technique is supposed to yield a more reliable prediction when compared with the other leakage current indicators.

Regarding the classification and prediction of insulator health, the previous work in [33] introduces the support vector machine (SVM) for classifying the condition of the insulator under the effect of the different coating damage modes. The assessment of the contaminated insulators was performed using computer vision in [34] and k-nearest neighbors (k-NN) [35]. The results of these studies indicated that these techniques provide adequate efficiency and accuracy and that they are promising approaches since they are quick and easy to perform. Some researchers have evaluated the conditions of insulators using different artificial intelligence methods, as reported above. However, the application of the naïve Bayes method to estimate the insulator conditions based on the leakage current characteristics has not been investigated, and this will be discussed in our current work.

Our current work contributes to estimating the conditions of porcelain insulators, as follows:

  • Six indicators based on the measured LC characteristics in the time domain and frequency domain, namely, the peak current indicator, phase shift indicator, slope indicator, crest factor indicator, total harmonic distortion indicator, and odd harmonic indicator, were extracted by taking into consideration the significant effect of environmental factors on the performance of the overhead line insulators. Environmental factors, including the soluble deposit density, wetting rate, insoluble deposit density, and contamination ratio of the upper to the lower side of the insulator were taken into consideration while simulating the nature of insulators in service.

  • The classification of the state of insulators based on the proposed indicator values using the naïve Bayes approach was conducted.

  • The comparison of the performance of the proposed indicators using the confusion matrix for the actual insulator conditions and naïve Bayes prediction results was carried out.

The rest of this paper is structured as follows. Section 2 reviews the process of pollution of the insulators and discusses how LC is measured. Section 3 illustrates the proposed leakage current indicator expressions. Section 4 presents the experimental and modeling results. Finally, the conclusion is presented in Section 5.

The advantages of this study are:

  • The proposed indicators are useful to monitor the condition of overhead line insulators in real time.

  • Insulator condition estimation using LC indicators is simple, low cost, and accurate.

  • Applicable for any insulator type and any voltage level.

  • Monitoring insulator conditions on the transmission line (without removing the insulator and without interrupting the power line).

2. Materials and Methods

2.1. Test Sample

The porcelain insulators to be tested were collected from the transmission division of the national network in Malaysia. The selected insulators’ main shape is portrayed in Figure 1. The insulators’ actual specifications are tabulated as in Table 1. In this paper, a single disk of porcelain insulators and a string of three units of porcelain insulators were tested.

Figure 1.

Figure 1

Insulator sample.

Table 1.

Test insulator structure characteristics.

Parameter Symbol Length (cm)
Creepage distance L 32
Insulator height H 14.6
Insulator diameter D 25.5
Rib diameters d 1 19.5
d 2 14.5
d 3 10.5
dc 5

2.2. Test Facilities and Procedures

The IEC-507 standard, namely, “Artificial pollution tests on high-voltage ceramic and glass insulators to be used on AC systems” [36] was referred to while performing the experimental setup. All experiments were carried out in an artificial test chamber with dimensions 50 cm × 50 cm × 75 cm in which the walls were polycarbonate sheets. The chamber was installed with four inlet valves used for spraying insulators under test for the purpose of wetting. Figure 2a shows a schematic diagram for the high-voltage polluted insulator experimental setup. A photograph of the test setup and the equipment used in the high-voltage laboratory is given in Figure 2b. The experimental circuit setup was composed of the following components: A is a transformer (220 V/100 kV, 5 kVA, 50 Hz), B is a capacitive voltage divider, C is the test sample inside the chamber, D is a monitoring system to measure the leakage current, E is a resistive step-down divider (100:1) employed for the measurement of the LC and protection of the DAQ device, and F is a fog generator with a rate controller for wetting.

Figure 2.

Figure 2

(a) Diagram of insulators’ test arrangement; (b) photograph of the insulators under test.

2.3. Wetting and Polluting

Prior to commencing the experiment, traces of grease and dirt were removed carefully for all specimens using alcohol liquid. Next, the insulators were dried for 24 h naturally. The contamination was then applied to the insulator surface based on the solid layer method [37,38,39,40]. The pollution was made up of two types of deposits: soluble deposit density (SDD), which is represented by sodium chloride salt (NaCl), and insoluble deposit density (NSDD), which was represented by kaolin. To prepare the SDD, the required amount of NaCl salt was mixed with 1000 mg of water to establish the pollution solution. Then, a conductivity meter was used to measure the conductivity of the polluted solution σσ at room temperature for three amounts of salt (10 g, 20 g, and 30 g) to compute three levels of SDD. Also, three amounts of kaolin (20 g, 40 g, and 60 g) were used to produce the NSDD levels listed in Table 2. Next, the conductivity of the pollution solution at 20 °C was calculated using Equation (1):

σ20=σσ×1bθ20 (1)

where σ20 and σσ, represent the solution conductivity at 20 °C, and the solution conductivity at the room temperature. θ is the temperature of the solution and b is a temperature-dependent factor that is determined to be 0.02 at = 27.5 °C using Equation (2) [36].

b=3.2×108θ3+1.032×105θ28.272×104θ+3.544×102 (2)

Table 2.

Pollution layer characteristics.

σ20 (S/m) SDD (mg/cm2) NSDD (mg/cm2) Wt (mL/h) Pollution Level
0 0 0 0 Clean
0.39 0.05 0.15 3 Low
0.72 0.1 0.25 6 Medium
1.38 0.2 0.35 9 High

The SDD was calculated based on the IEC 60507 [36] and IEC 60815 [41] standards using Equation (3):

SDD=(5.7×σ20)1.03×VS (3)

where V and S represent the volume of pollution solution, and the insulator surface area, respectively. Meanwhile, Equation (4) was used to calculate NSDD according to the IEC-507 standard [36]:

NSDD=[(wswi)×103]S (4)

where ws and wi are the mass of the filter paper under contamination and under dry conditions, respectively.

As shown in Table 2, three levels were determined for both SSD and NSDD: light, moderate, and high contamination. The sample was then polluted and hung in the test room and left drying for around 1 day to ensure that the polluted insulator was dried. The test room pressure remained constant throughout the experiment, matching the laboratory’s ambient pressure. The temperature in the testing room was roughly 27.9 °C, which was about the same as the indoor temperature in the laboratory. The relative humidity inside the test room was set to 75% and monitored during the testing with the help of a humidity sensor. The spray technique was used to wet the insulator, with six nozzles regularly spaced around the test room wall. A control panel outside the test room was used to automatically calculate the fog flow rate. To achieve the moisture of insulators at different levels, three degrees of wetting rates Wt were applied, i.e., 3 mL/h, 6 mL/h, and 9 mL/h.

Under both uniform and uneven contamination distributions, the porcelain was investigated. Also, three contamination ratios of the upper to the lower side of the insulator (PL/Pu), i.e., 1/3, 1/5, and 1/8, were selected in the uneven contamination case. The upper and lower surfaces of the insulator were polluted separately in the nonuniform pollution case to yield SDDu and SDDL, whereas the overall SDD can be met by Equation (5) [5,40]:

SDD=SDDu×Su+SDDL×SLSu+SL (5)

where Su and SL are the area of the upper and lower surface of insulator, respectively. According to these selected pollution ratios, the SDD of the upper and lower sides (SDDu and SDDu) can be satisfied by Equation (6):

SDDPu=2×SDD1+(PL/Pu), SDDPL=2×SDD1+(Pu/PL) (6)

2.4. Data Monitoring

As illustrated in the experimental setup in Figure 2, the input voltage values were obtained using a divider consisting of two capacitors with a ratio (C1 to C2) of 10,000:1. On the other side of the test chamber, the monitoring system consisted of a data acquisition (DAQ) card, oscilloscope, and a PC, which was used to measure LC. A resistive divider (100:1) was employed, since the DAQ’s input voltage range is just 10 V. During the measurement, the LC data were captured from the divider and then transferred using a DAQ card to the PC. The captured data were saved in a CSV file after being displayed on a graphical user interface of the LabVIEW software. For measurement validation, the oscilloscope was utilized to compare with DAQ data reading. Finally, with the help of MATLAB software, the LC data saved were converted into the frequency domain using FFT.

3. Characteristic Parameter of Leakage Current

In this paper, six characteristics/indices were extracted in both the time and frequency domains of LC to predict the health of polluted insulators.

3.1. Leakage Current Indicators in Time Domain

The time and frequency domain signal of LC was used to derive all the leakage current indicator equations. The formulae presented in this section were used as the indicators of change in LC signal that was affected by the insulator conditions. In the time domain of LC, four indicators were selected. The first and second indicators, which were the peak of leakage current Im (denoted as x1), found based on the absolute value of the current signal, and the phase shift ϕ between the applied voltage and LC (denoted as x2) were extracted from the LC general equation, expressed as in Equation (7) [42]:

I=Imsin(ωt+ϕ) (7)

where ω is the angular frequency equivalent to 2πf, with the value of frequency f in this study 50 Hz. As such, the first two characteristics can be defined as in Equations (8) and (9):

x1=Im (8)
x2=ϕ=ΔtT360° (9)

Figure 3 illustrates how the phase difference ϕ between the applied voltage and LC can be determined for a clean and a polluted insulator. For a clean insulator, the phase difference ϕ between the applied voltage and LC appeared to be nearly 90° (see Figure 3a). As the amount of pollution on the insulator increased, the phase difference ϕ between the applied voltage and LC decreased. Under heavily polluted circumstances, the phase difference ϕ between the applied voltage and LC became nearly zero (see Figure 3b).

Figure 3.

Figure 3

Leakage current and applied voltage phase angle: (a) clean; (b) pollution.

The third indicator x3 was extracted by calculating the slope of the line between two consecutive peaks of LC signal, expressed as in Equation (10):

x3=n=1mynyn1xnxn1=0mΔynΔxn (10)

where ∆yn is the LC difference for adjacent peaks at the nth point for time and ∆xn is the time between these peaks. Figure 4a illustrates how the LC signal slope was calculated. The fourth indicator x4 was obtained from the crest factor, which was calculated by dividing the peak value with the RMS value of the LC waveform, as shown in Figure 4b. As such, x4 is expressed as in Equation (11):

x4=IpeakIRMS (11)
IRMS=1niii2 (12)

where RMS is root mean square, ii is each measured value, and n is the number of measurements.

Figure 4.

Figure 4

(a) Slope curve extracted from leakage current waveform; (b) crest factor indicator extracted from leakage current waveform.

3.2. Leakage Current Indicators in Frequency Domain

The frequency-domain signals of LC for polluted insulators have characteristic features at frequencies below 500 Hz. In this paper, the odd harmonic and total harmonic distortion (THD) of LC under 500 Hz were used to propose indicators for insulator condition assessment. The frequency characteristics of the LC are defined by the x5 and x6 indicators, as in Equations (13) and (14), respectively:

x5=THD=n=2In2I1 (13)
x6=nInI3    n=5,7,9 (14)

where In represent the nth harmonic and n is the odd-order harmonic number.

4. Classification Model

The naïve Bayesian classifier is a classification algorithm based on Bayes’s theorem. Its underlying idea and building approach are more straightforward and simpler than those of support vector machines and neural networks. Furthermore, compared to other algorithms, the naïve Bayesian classifier algorithm suits the approach of this work, and brought great accuracy in classifying the insulator situations. The naïve Bayesian classifier theorem, which is employed in the classification of the suggested LC indicators, is explained in this section. Figure 5 depicts the flowchart of the procedures involved in extracting and categorizing the recommended indicators.

Figure 5.

Figure 5

Data extraction and classification of the proposed indicators.

Naïve Bayesian Classifier

To understand the naïve Bayesian method, consider y to be a collection of samples. Each sample contains n condition characteristics that represent its special traits, as well as one class label. All LC features are assumed to be interrelated in this work, while the class label is assumed to be separated. Assume that all training examples are classified into m classifications and that the class label of each sample changes from {z1, z2, …, zm}. As a result, any sample can be shown as an n-dimensional vector. y = (y1, y2, …, yn) would be a piece of testing data whose class label has to be determined. A naïve Bayesian classifier may compute the posterior probabilities and decide the class label for the new sample based on the previous and class-conditional possibilities of the new sample. A naïve Bayesian classifier uses Equation (15) to characterize the new sample’s class label [43]:

z=argmaxzk,k=1,2,,m{P(zk|y)}=argmaxzk,k=1,2,,mP(zk)P(y|zk)P(y)=argmaxzk,k=1,2,,mP(zk)P(y|zk) (15)

where P(zk) represents the previous probability of the zk class that can be found from P(zk)=Nk/N, Nk is the number of samples within zk class, N is data set size, and P(y|zk) represent the class-conditional probability. The main aim of the naïve Bayesian classifier is to determine P(y|zk) based on the training samples in the zk class.

All features are assumed to be independent by the naïve Bayesian classifier. As a result, the class-conditional probability can be written as in Equation (16):

P(y|zk)=P(y1,y2,,yn|zk)=i=1fP(yf|zk) (16)

To find the class label of y, the Naïve Bayesian classifier can substitute the class-conditional probability with Equation (16) and yield the decision function in Equation (17).

z=argmaxzk,k=1,2,,mnkNi=1fP(yf|zk) (17)

where P(yf|zk)(1fn) is an essential factor in determining the class label of the new sample.

5. Results and Discussion

5.1. Leakage Current Results

The LC findings of uniformly polluted insulators in both time and frequency domains with various SDD levels but fixed NSDD of 0.15 mg/cm2 and Wt of 3 mL/h are shown in Figure 6 and Figure 7. Figure 6 indicates that increased pollution severity causes a considerable rise in LC under specific values of NSDD, Wt, and Pu/PL. The LC increase can be explained by the increase in conductivity of the pollution layer on the insulator’s surface once subjected to wetness. Consequently, the LC flowed from the high voltage terminal to the ground in the form of positively and negatively charged ions. Some spot arcs were observed on occasion under high-contamination conditions, particularly in the existence of moisture. During the flashover, the signal of the LC appeared to be severely distorted, as shown in Figure 6d. Furthermore, when LC increased, the THD and harmonic values increased (see Figure 7), while the phase angle between the current and voltage decreased. The decrease in phase angle between the LC and voltage is due to the resistive current increasing with constant capacitive current. Once the contamination level on the insulator surface was raised, a clear change in the odd harmonics (3rd, 5th, 7th, and 9th) was observed (see Figure 7). As seen in Figure 8, the 3rd harmonic will increase to surpass the 5th, 7th, and 9th harmonics, with a clear increase in the 7th and 9th harmonics. Furthermore, during discharge activity on the insulator’s surface, the 3rd harmonic is often substantially high [44,45].

Figure 6.

Figure 6

Leakage current waveform under NSDD = 0.15 mg/cm2, wt = 3 mL/h and different SDD: (a) SDD = 0.00 mg/cm2; (b) SDD = 0.05 mg/cm2, (c) SDD = 0.12 mg/cm2, (d) SDD = 0.2 mg/cm2.

Figure 7.

Figure 7

FFT of leakage current waveform under NSDD = 0.15 mg/cm2, Wt = 3 mL/h and different SDD: (a) SDD = 0.00 mg/cm2; (b) SDD = 0.05 mg/cm2, (c) SDD = 0.12 mg/cm2, (d) SDD = 0.2 mg/cm2.

Figure 8.

Figure 8

Odd harmonics of leakage current under pollution grading [2].

Table 3 provides the test results of the LC harmonic components’ values (magnitude Im, harmonics, THD, and phase shift angle ϕ) for different pollution levels under uniform pollution distribution for all investigated conditions. Under the clean condition, the 5th and 7th harmonics were greater than the 3rd harmonic. Furthermore, there were no signs of flashover. The LC rose marginally as the wetting rate increased when the clean insulators were tested under a specific NSDD. This indicates that wetting the insulator surface caused the flow of the charges from the high-voltage terminal to the ground to rise noticeably.

Table 3.

LC characteristics for insulators under different contamination degree for uniform distribution.

Single Insulator under 11 kV 3 Unit Insulator String under 33kV
SDD NSDD Wt Im 3rd 5th 7th 9th THD ϕ Im 3rd 5th 7th 9th THD ϕ
0.00 0 0 1.807 0.005 0.020 0.012 0.020 7.727 ≈90 1.778 0.005 0.019 0.012 0.019 8.523 ≈ 90
0.15 0 1.975 0.006 0.030 0.010 0.005 7.795 ≈90 1.944 0.006 0.029 0.010 0.005 8.598 86.370
3 4.344 0.030 0.149 0.020 0.008 8.492 87.026 4.276 0.029 0.147 0.019 0.008 9.367 82.100
6 7.109 0.039 0.125 0.079 0.007 8.595 86.956 6.997 0.039 0.123 0.078 0.007 9.481 82.034
9 8.886 0.069 0.168 0.099 0.059 9.190 85.838 8.746 0.068 0.165 0.097 0.058 10.136 80.980
0.25 0 2.172 0.030 0.138 0.020 0.020 7.944 88.802 2.138 0.029 0.136 0.019 0.019 8.762 83.776
3 6.615 0.099 0.405 0.049 0.059 9.064 87.076 6.511 0.097 0.398 0.049 0.058 9.998 82.147
6 8.590 0.107 0.395 0.079 0.069 9.133 87.166 8.454 0.105 0.389 0.078 0.068 10.073 82.232
9 9.577 0.168 0.592 0.099 0.079 9.578 86.277 9.426 0.165 0.583 0.097 0.078 10.565 81.394
0.35 0 4.048 0.057 0.118 0.089 0.089 8.355 88.084 3.984 0.056 0.117 0.087 0.087 9.216 83.098
3 7.306 0.178 0.592 0.049 0.030 9.601 85.888 7.191 0.175 0.583 0.049 0.029 10.590 81.027
6 8.984 0.197 0.627 0.059 0.049 9.853 85.269 8.843 0.194 0.617 0.058 0.049 10.867 80.443
9 10.367 0.326 0.721 0.069 0.089 9.978 84.870 10.203 0.321 0.709 0.068 0.087 11.006 80.066
0.05 0.15 0 5.134 0.089 0.425 0.089 0.039 9.384 82.036 5.053 0.087 0.418 0.087 0.039 10.351 77.392
3 8.886 1.234 3.159 0.592 0.296 11.693 79.152 8.746 1.215 3.110 0.583 0.292 12.897 74.671
6 11.749 1.343 2.962 0.819 0.395 12.904 67.365 11.564 1.322 2.915 0.807 0.389 14.234 63.552
9 15.501 1.777 3.554 0.908 0.760 16.482 57.495 15.257 1.749 3.498 0.894 0.748 18.180 54.241
0.25 0 7.207 0.138 0.553 0.079 0.069 10.174 80.589 7.094 0.136 0.544 0.078 0.068 11.222 76.027
3 12.144 1.402 2.281 0.839 0.652 12.447 66.078 11.953 1.380 2.245 0.826 0.641 13.729 62.338
6 14.711 1.649 2.271 1.382 0.691 14.688 54.142 14.479 1.623 2.235 1.360 0.680 16.200 51.077
9 18.166 1.767 2.281 1.481 0.790 17.179 42.575 17.880 1.739 2.245 1.458 0.777 18.949 40.165
0.35 0 8.984 0.178 0.642 0.128 0.099 11.008 78.164 8.843 0.175 0.632 0.126 0.097 12.142 73.739
3 16.093 1.876 2.488 1.007 0.553 15.248 56.098 15.840 1.846 2.449 0.991 0.544 16.818 52.922
6 20.141 2.172 2.370 1.382 0.889 18.025 40.050 19.824 2.138 2.332 1.360 0.875 19.882 37.783
9 25.769 2.577 3.159 1.185 1.086 21.534 33.154 25.363 2.536 3.110 1.166 1.069 23.752 31.277
0.1 0.15 0 6.319 0.217 0.711 0.109 0.079 9.384 71.058 6.553 0.225 0.737 0.113 0.082 10.444 68.988
3 14.612 3.258 2.666 0.395 0.790 17.522 55.100 15.153 3.379 2.764 0.410 0.819 19.502 53.495
6 16.093 4.048 3.159 0.612 1.185 21.580 38.453 16.688 4.198 3.276 0.635 1.229 24.018 37.333
9 19.055 4.542 4.048 0.938 0.790 26.575 27.106 19.760 4.710 4.198 0.973 0.819 29.578 26.316
0.25 0 7.405 0.316 0.790 0.128 0.207 11.293 75.739 7.679 0.328 0.819 0.133 0.215 12.569 73.533
3 16.982 3.456 3.061 1.027 0.889 24.849 52.415 17.610 3.583 3.174 1.065 0.921 27.657 50.889
6 19.351 5.233 3.653 1.086 0.968 28.861 30.160 20.067 5.426 3.788 1.126 1.003 32.122 29.281
9 23.103 5.628 4.048 1.283 1.086 36.542 25.070 23.958 5.836 4.198 1.331 1.126 40.671 24.340
0.35 0 9.281 0.405 0.790 0.306 0.227 11.327 70.289 9.624 0.420 0.819 0.317 0.235 12.607 68.242
3 19.549 5.529 3.554 1.283 1.580 34.873 39.581 20.272 5.733 3.686 1.331 1.638 38.814 38.428
6 20.141 7.109 4.048 1.481 1.283 39.582 20.589 20.886 7.372 4.198 1.536 1.331 44.055 19.989
9 25.769 6.121 4.147 1.678 1.777 48.052 14.920 26.722 6.348 4.300 1.741 1.843 53.482 14.486
0.2 0.15 0 8.313 0.523 0.948 0.444 0.316 11.339 56.727 8.621 0.543 0.983 0.461 0.328 12.620 55.074
3 26.065 9.478 2.764 2.073 1.481 41.788 32.056 27.029 9.829 2.867 2.150 1.536 46.510 31.122
6 29.027 9.774 2.271 2.567 1.086 47.229 17.545 30.101 10.136 2.355 2.662 1.126 52.566 17.034
9 36.036 10.732 2.271 2.666 1.283 50.029 11.537 37.370 11.129 2.355 2.764 1.331 55.682 11.201
0.25 0 10.169 0.612 0.987 0.622 0.316 12.322 42.455 10.545 0.635 1.024 0.645 0.328 13.714 41.219
3 28.928 9.379 2.764 2.073 1.086 52.155 26.397 29.998 9.726 2.867 2.150 1.126 58.049 25.628
6 32.482 10.762 2.666 2.271 1.185 54.681 10.709 33.684 11.160 2.764 2.355 1.229 60.860 10.397
9 39.393 12.835 3.159 2.370 1.185 61.482 1.038 40.851 13.310 3.276 2.457 1.229 68.429 1.008
0.35 0 10.564 0.642 1.007 0.474 0.494 12.150 32.774 10.955 0.665 1.044 0.491 0.512 13.523 31.820
3 34.950 13.743 2.962 1.185 1.481 59.059 3.912 36.244 14.252 3.071 1.229 1.536 65.732 3.798
6 51.735 15.994 3.456 2.073 1.185 67.768 2.066 53.649 16.586 3.583 2.150 1.229 75.426 2.006
9 64.273 17.673 2.666 1.283 1.678 69.563 0.828 66.651 18.327 2.764 1.331 1.741 77.424 0.804

Table 3 also shows the results of the uniformly polluted insulators with the change in SDD, Wt, and NSDD. Table 3 shows that the LC on a clean insulator’s surface is very low, approximately 1.81 mA for single disk and 1.78 for string insulators. This indicates that under clean circumstances, the performance of the insulators is capacitive. Because of the capacitive property of LC, the phase shift angle between current and voltage will be about 90°. Under the clean and dry scenario, the 5th harmonic is higher than the 3rd harmonic. Generally, the LC component test results in Table 3 show that:

  1. Under dry conditions, surface conductivity was minimal. Therefore, the influence of increasing SDD and NSDD on LC and LC characteristics in this condition was minor.

  2. The LC magnitude grew substantially as the contamination severity of SDD, NSDD, and Wt increased.

  3. As SDD, NSDD, and Wt increased and Pu/PL decreased, odd harmonic values and THD increased. In contrast, the phase angle decreased.

  4. When the Wt was changed for a clean insulator under a specific NSDD, the LC value varies somewhat, as do the temporal and frequency characteristics of the LC.

5.2. Leakage Current Indices Finding

Figure 9 shows the LC indices of a clean (0.00 mg/cm2 of SDD) insulator under different Wt and NSDD. Each indicator demonstrates a unique behavior when the wetting rate and NSDD were changed. Of note, there is no significant difference between different NSDD under the same Wt. The x1, x3, x4, and x5 indices increased with the rise in both the NSDD and Wt. For example, when the Wt was increased from 3 mL/h to 9 mL/h under 0.15 mg/cm2 of NSDD, the x1 increased from 4.2 to 8.88, x3 increased from 0.065 to 0.11, x4 increased from 1.56 to 1.585, and x5 increased from 7.6 to 10.49.

Figure 9.

Figure 9

LC indices of a clean insulator under different Wt and NSDD; (a) x1; (b) x2; (c) x3; (d) x4; (e) x5; (f) x6.

In contrast, the x2 and x6 decreased with the increase in both the Wt and NSDD. For example, when the Wt increased from 3 mL/h to 9 mL/h under NSDD = 0.15 mg/cm2, the x2 decreased from 87.2 to 86.01 and x6 decreased from 5.9 to 4.7.

5.2.1. Indicators Trends under Different SDD

The leakage current indices x1, x3, x4, and x5 under different SDD, NSDD, Wt, and Pu/PL for single and string insulators are presented in Figure 10 and Table 4. The LC indicators of insulators under test increased with the increase in SDD under specific NSDD, Wt, and Pu/PL. On the contrary, the indices x2 and x6 of insulators decreased with the increase in SDD under the same conditions. For example, under NSDD of 0.25 mg/cm2, Wt of 6 mL/h and Pu/PL of 1/3, when SDD was 0.05, 0.1 and 0.2 mg/cm2, the x1 for the single disk insulator corresponded to 12.2, 15.4, and 26.6 mA, respectively. The x1 also increased by 26.2% and 118.03% when the SDD increased from 0.05 to 0.1 mg/cm2 and from 0.1 to 0.2 mg/cm2, respectively. For x6, when the SDD was 0.05, 0.1 and 0.2 mg/cm2, x6 corresponded to 2.69, 1.31, and 0.63 mA, respectively. The LC indicators showed a similar trend and performance for the insulator string under 33 kV with minor variations, as illustrated in Table 5.

Figure 10.

Figure 10

Figure 10

Leakage current indices of uniform polluted insulators under various wetting rate Wt and NSDD: (a) x1; (b) x2; (c) x3; (d) x4; (e) x5; (f) x6.

Table 4.

LC indices of nonuniformly polluted insulators under different Wt and NSDD for 11 kV insulators.

Pu/PL 1/3 1/5 1/8
SDD
mg/cm2
NSDD
mg/cm2
Wt
mL/h
x1 x2 x3 x4 x5 x6 x1 x2 x3 x4 x5 x6 x1 x2 x3 x4 x5 x6
0.05 0.15 0 4.2 84.67 0.14 1.43 7.97 6.96 3.7 86.36 0.13 1.43 7.93 8.42 3.4 86.62 0.13 1.42 7.85 8.99
3 7.3 81.69 0.37 1.52 9.93 3.42 6.3 83.32 0.36 1.52 9.88 3.53 5.9 83.57 0.36 1.51 9.78 3.72
6 9.6 69.53 0.78 1.56 10.96 3.18 8.4 70.92 0.77 1.55 10.91 3.35 7.8 71.13 0.77 1.55 10.79 3.51
9 12.7 59.34 1.03 1.57 14.00 3.04 11.1 60.53 1.02 1.57 13.93 3.07 10.3 60.71 1.01 1.56 13.78 3.45
0.25 0 6 83.17 0.30 1.58 8.64 6.84 5.2 84.84 0.30 1.58 8.60 7.88 4.9 85.09 0.30 1.57 8.51 8.22
3 10.1 68.20 0.69 1.55 10.57 2.82 8.8 69.56 0.69 1.55 10.52 2.96 8.2 69.77 0.68 1.54 10.41 3.08
6 12.2 55.88 1.07 1.56 12.48 2.69 10.7 57.00 1.06 1.56 12.41 2.80 10 57.17 1.05 1.55 12.28 3.02
9 15.1 43.94 3.09 1.58 14.59 2.67 13.2 44.82 3.07 1.57 14.52 2.83 12.3 44.95 3.04 1.57 14.37 2.83
0.35 0 7.4 80.67 0.52 1.59 9.35 6.25 6.5 82.28 0.52 1.59 9.30 7.42 6 82.53 0.51 1.58 9.21 8.30
3 13.3 57.90 0.87 1.56 12.95 2.18 11.6 59.05 0.87 1.55 12.89 2.36 10.8 59.23 0.86 1.55 12.75 2.48
6 16.6 41.33 3.03 1.57 15.31 2.20 14.5 42.16 3.02 1.57 15.23 2.41 13.5 42.29 2.99 1.56 15.08 2.53
9 21.3 34.22 5.63 1.58 18.29 2.12 18.5 34.90 5.60 1.58 18.20 2.30 17.3 35.01 5.55 1.58 18.01 2.40
0.1 0.15 0 5.1 73.33 0.63 1.60 7.97 5.34 4.5 74.80 0.62 1.60 7.93 6.29 4.2 75.03 0.62 1.59 7.85 7.88
3 12 56.87 2.25 1.53 14.88 1.30 10.5 58.00 2.24 1.53 14.81 1.62 9.8 58.18 2.22 1.52 14.65 1.95
6 13.3 39.69 4.69 1.59 18.33 1.33 11.6 40.48 4.67 1.58 18.24 1.50 10.8 40.60 4.62 1.58 18.05 1.68
9 15.7 27.97 8.09 2.22 22.57 1.48 13.7 28.53 8.04 2.22 22.46 1.53 12.8 28.62 7.97 2.21 22.23 1.71
0.25 0 5.9 78.17 0.78 2.42 9.59 5.06 5.1 79.73 0.78 2.42 9.54 5.73 4.8 79.97 0.77 2.41 9.44 7.35
3 13.5 54.10 5.63 1.60 21.11 1.44 11.8 55.18 5.60 1.60 21.00 1.56 11 55.34 5.55 1.59 20.78 1.64
6 15.4 31.13 6.75 2.17 24.51 1.31 13.4 31.75 6.71 2.17 24.39 1.48 12.5 31.84 6.65 2.16 24.14 1.55
9 17.5 25.87 8.58 2.41 31.04 1.31 15.3 26.39 8.53 2.41 30.89 1.56 14.3 26.47 8.45 2.40 30.56 1.60
0.35 0 7.6 72.54 0.79 2.58 9.62 4.16 6.6 73.99 0.79 2.58 9.57 4.70 6.2 74.22 0.78 2.57 9.47 5.90
3 16 40.85 5.15 1.62 29.62 1.16 14 41.67 5.13 1.61 29.47 1.37 13 41.79 5.08 1.61 29.17 1.45
6 16.5 21.25 7.35 2.21 33.62 1.16 14.4 21.67 7.31 2.21 33.45 1.28 13.4 21.74 7.24 2.20 33.10 1.52
9 21.1 15.40 10.35 2.48 40.82 1.20 18.4 15.71 10.29 2.48 40.61 1.23 17.2 15.75 10.20 2.47 40.19 1.41
0.2 0.15 0 6.8 58.55 1.03 2.65 9.63 3.42 5.7 59.72 1.02 2.64 9.58 3.78 5.4 59.90 1.01 2.63 9.48 4.72
3 21.4 33.08 5.88 1.76 35.50 0.67 18.6 33.75 5.85 1.76 35.32 0.76 17.4 33.85 5.79 1.76 34.95 0.91
6 23.8 18.11 7.63 2.38 40.12 0.63 20.7 18.47 7.58 2.38 39.92 0.66 19.4 18.52 7.51 2.37 39.50 0.79
9 29.5 11.91 11.27 2.51 42.50 0.60 25.7 12.14 11.21 2.51 42.28 0.57 24.1 12.18 11.10 2.50 41.84 0.72
0.25 0 8.3 43.82 1.26 2.70 10.47 3.28 7.3 44.69 1.26 2.69 10.41 3.58 6.8 44.83 1.24 2.68 10.30 4.31
3 23.7 27.24 9.56 1.82 44.30 0.71 20.7 27.79 9.51 1.81 44.08 0.72 19.3 27.87 9.42 1.81 43.62 0.76
6 26.6 11.05 11.17 2.46 46.45 0.63 23.2 11.27 11.10 2.45 46.22 0.71 21.7 11.31 11.00 2.44 45.73 0.71
9 32.3 1.07 15.05 2.47 52.22 0.54 28.1 1.09 14.96 2.47 51.96 0.58 26.3 1.10 14.82 2.46 51.42 0.65
0.35 0 8.7 33.83 0.63 2.63 10.32 3.21 7.5 34.50 0.63 2.63 10.27 3.48 7.1 34.61 0.62 2.61 10.16 4.05
3 30.5 4.04 10.36 1.93 50.17 0.56 27.9 4.12 10.30 1.92 49.92 0.64 16.7 4.13 10.20 1.92 49.39 0.78
6 46.2 2.13 12.77 2.49 57.56 0.67 32.9 2.17 12.70 2.49 57.28 0.57 21.4 2.18 12.58 2.48 56.68 0.67
9 52.7 0.00 20.06 2.55 59.09 0.46 45.9 0.00 18.95 2.54 58.79 0.53 42.9 0.00 16.76 2.53 58.18 0.60
Table 5.

LC indices of nonuniformly polluted insulators under different Wt and NSDD for insulator string 33 kV.

Pu/PL 1/3 1/5 1/8
SDD
mg/cm2
NSDD
mg/cm2
Wt
mL/h
x1 x2 x3 x4 x5 x6 x1 x2 x3 x4 x5 x6 x1 x2 x3 x4 x5 x6
0.05 0.15 0 4 79.80 0.15 1.47 8.18 7.21 3.5 81.39 0.14 1.47 8.14 8.72 3.3 81.64 0.14 1.46 8.05 9.31
3 7 76.99 0.39 1.57 10.19 3.54 6 78.53 0.38 1.57 10.14 3.66 5.7 78.77 0.38 1.56 10.03 3.85
6 9.2 65.53 0.83 1.61 11.24 3.29 8.1 66.84 0.82 1.60 11.19 3.47 7.5 67.04 0.82 1.60 11.07 3.64
9 12.2 55.93 1.09 1.62 14.36 3.15 10.6 57.05 1.08 1.62 14.29 3.18 9.9 57.22 1.07 1.61 14.14 3.57
0.25 0 5.8 78.39 0.32 1.63 8.86 7.09 5 79.96 0.32 1.63 8.82 8.16 4.7 80.20 0.32 1.62 8.73 8.52
3 9.7 64.28 0.73 1.60 10.84 2.92 8.4 65.56 0.73 1.60 10.79 3.07 7.9 65.76 0.72 1.59 10.68 3.19
6 11.7 52.67 1.14 1.61 12.80 2.79 10.3 53.72 1.12 1.61 12.73 2.90 9.6 53.88 1.11 1.60 12.60 3.13
9 14.5 41.41 3.28 1.63 14.97 2.77 12.7 42.24 3.26 1.62 14.90 2.93 11.8 42.37 3.23 1.62 14.74 2.93
0.35 0 7.1 76.03 0.55 1.64 9.59 6.48 6.2 77.55 0.55 1.64 9.54 7.69 5.8 77.79 0.54 1.63 9.45 8.60
3 12.8 54.57 0.92 1.61 13.29 2.26 11.1 55.66 0.92 1.60 13.23 2.44 10.4 55.82 0.91 1.60 13.08 2.57
6 15.9 38.95 3.21 1.62 15.71 2.28 13.9 39.74 3.20 1.62 15.63 2.50 12.9 39.86 3.17 1.61 15.47 2.62
9 20.4 32.25 5.97 1.63 18.77 2.20 17.7 32.89 5.94 1.63 18.67 2.38 16.6 33.00 5.89 1.63 18.48 2.49
0.12 0.15 0 4.9 69.11 0.67 1.65 8.18 5.53 4.3 70.50 0.66 1.65 8.14 6.52 4 70.72 0.66 1.64 8.05 8.16
3 11.5 53.60 2.39 1.58 15.27 1.35 10.1 54.67 2.38 1.58 15.20 1.68 9.4 54.84 2.36 1.57 15.03 2.02
6 12.8 37.41 4.98 1.64 18.81 1.38 11.1 38.15 4.95 1.63 18.71 1.55 10.4 38.27 4.90 1.63 18.52 1.74
9 15.1 26.36 8.58 2.29 23.16 1.53 13.1 26.89 8.53 2.29 23.04 1.59 12.3 26.97 8.46 2.28 22.81 1.77
0.25 0 5.7 73.68 0.83 2.50 9.84 5.24 4.9 75.15 0.83 2.50 9.79 5.94 4.6 75.37 0.82 2.48 9.69 7.61
3 12.9 50.99 5.97 1.65 21.66 1.49 11.3 52.01 5.94 1.65 21.55 1.62 10.5 52.16 5.89 1.64 21.32 1.70
6 14.8 29.34 7.16 2.24 25.15 1.36 12.8 29.92 7.12 2.24 25.02 1.53 12 30.01 7.06 2.23 24.77 1.61
9 16.8 24.38 9.10 2.48 31.85 1.36 14.7 24.87 9.05 2.48 31.69 1.62 13.7 24.95 8.97 2.47 31.35 1.66
0.35 0 7.3 68.37 0.84 2.66 9.87 4.31 6.3 69.74 0.84 2.66 9.82 4.87 5.9 69.95 0.83 2.65 9.72 6.11
3 15.3 38.50 5.46 1.67 30.39 1.20 13.4 39.27 5.44 1.66 30.24 1.42 12.5 39.39 5.39 1.66 29.93 1.50
6 15.8 20.03 7.80 2.28 34.49 1.20 13.8 20.42 7.76 2.28 34.32 1.33 12.8 20.49 7.68 2.27 33.96 1.57
9 20.2 14.51 10.98 2.56 41.88 1.24 17.6 14.81 10.92 2.56 41.67 1.27 16.5 14.84 10.82 2.55 41.23 1.46
0.2 0.15 0 6.5 55.18 1.09 2.73 9.88 3.54 5.5 56.29 1.08 2.72 9.83 3.92 5.2 56.46 1.07 2.71 9.73 4.89
3 20.5 31.18 6.24 1.81 36.42 0.69 17.8 31.81 6.21 1.81 36.24 0.79 16.7 31.90 6.14 1.81 35.86 0.94
6 22.8 17.07 8.10 2.45 41.16 0.65 19.8 17.41 8.04 2.45 40.96 0.68 18.6 17.46 7.97 2.44 40.53 0.82
9 28.3 11.23 11.96 2.59 43.61 0.62 24.6 11.44 11.89 2.59 43.38 0.59 23.1 11.48 11.78 2.58 42.93 0.75
0.25 0 8 41.30 1.34 2.78 10.74 3.40 7 42.12 1.34 2.77 10.68 3.71 6.5 42.25 1.32 2.76 10.57 4.47
3 22.7 25.67 10.14 1.88 45.45 0.74 19.8 26.19 10.09 1.87 45.23 0.75 18.5 26.27 9.99 1.87 44.75 0.79
6 25.5 10.41 11.85 2.54 47.66 0.65 22.2 10.62 11.78 2.53 47.42 0.74 20.8 10.66 11.67 2.52 46.92 0.74
9 31 1.01 15.97 2.55 53.58 0.56 26.9 1.03 15.87 2.55 53.31 0.60 25.2 1.04 15.72 2.54 52.76 0.67
0.35 0 8.3 31.89 0.67 2.71 10.59 3.33 7.2 32.52 0.67 2.71 10.54 3.61 6.8 32.62 0.66 2.69 10.42 4.20
3 29.2 3.81 10.99 1.99 51.47 0.58 26.7 3.88 10.93 1.98 51.22 0.66 16 3.89 10.82 1.98 50.67 0.81
6 44.3 2.01 13.55 2.57 59.06 0.69 31.5 2.05 13.47 2.57 58.77 0.59 20.5 2.05 13.35 2.56 58.15 0.69
9 50.5 0.79 21.28 2.63 60.63 0.48 44 0.32 20.11 2.62 60.32 0.55 41.1 0.56 17.78 2.61 59.69 0.62

5.2.2. Indicator Trends under Different NSDD

The differences in the indicators are comparable to the previous case (pollution variation), and changes in the amount of increment/or decrement can be detected. The test findings in Table 5 demonstrate that under constant SDD, Wt, and Pu/PL, increasing the NSDD increases the x1, x3, x4, and x5, but decreases the x2 and x6. To further understand the relationship between NSDD and the suggested indices, Figure 11 displays the x1, x3, x4, x5, and x6 vs. NSDD curves with SDD of 0.2 mg/cm2, Wt of 6 mL/h, and Pu/PL of 1/1.

Figure 11.

Figure 11

The impact of NSDD on indicator shift.

5.2.3. Indicator Trends under Different Wt

The relationship between the proposed indices x1–x6 and Wt for porcelain insulator under SDD of 0.2 mg/cm2, NSDD of 0.35 mg/cm2, and Pu/PL of 1/1 and different Wt is demonstrated in Figure 12. It is worth noting that when Wt increases, the x2 and x6 fall while the x1, x3, x4, and x5 increase. For example, under SDD of 0.2 mg/cm2, NSDD of 0.35 mg/cm2, and Pu/PL of 1/1, the x1 increased by 13.4% and 15.4% when Wt increased from 3 to 6 mL/h and from 3 to 9 mL/h, respectively, whereas under the same conditions, the x2 decreased by 72.1% and 57.2% when Wt increased from 3 to 6 mL/h and from 6 to 9 mL/h, respectively.

Figure 12.

Figure 12

The impact of Wt on indicators shift.

5.2.4. Indicator Trends under Different Nonuniform Pollution Distribution (Pu/PL)

The relationship between proposed indices x1–x6 and nonuniform pollution distribution Pu/PL for a polluted porcelain insulator under SDD of 0.2 mg/cm2, NSDD of 0.35 mg/cm2, and Wt of 9 mL/h and different Pu/PL as an example is shown in Figure 13. It can be observed that an increase in Pu/PL causes an increase in the x2 and x6 and a decrease in the x1, x3, x4, and x5. This means that the sample under uniform contamination conditions is more dangerous in terms of flashover incidence than the sample under nonuniform pollution levels.

Figure 13.

Figure 13

The impact of Pu/PL on indicator shift.

5.3. Insulator Condition Based on the Test Data of Indices

5.3.1. Insulator Condition Classification Based on Test Preparation

In this section, the ranges of the indicators corresponded to the level of SDD, NSDD, Wt, and Pu/PL are classified. The experimental data indicated that the values of x1, x3, x4, and x5 increased in proportion to an increase in SDD, NSDD, and Wt, but a decrease in Pu/PL. Meanwhile, the indicators x2 and x6 decreased with an increase in SDD, NSDD, and Wt, and decrease in Pu/PL. The proposed index values in the normal range were observed under the clean and low-pollution cases with Wt less than 4 mL/h and NSDD less than 0.2 mg/cm2. In this case, the possibility of discharge occurrence is almost nonexistent. According to indicator results in Table 5, the insulator was in an abnormal state under low contamination (0.05 mg/cm2) with heavy wetting Wt (9 mL/h) and medium and high NSDD (0.25 and 0.35 mg/cm2) for all contamination distribution (Pu/PL), except when Pu/PL = 1/8. In addition, the insulator under examination displayed an abnormal condition in the presence of moderate pollution (0.12 mg/cm2) under moderate wetting Wt of 6 mL/h, NSDD of 0.25 mg/cm2, and Pu/PL of 1/1 and 1/5. The probability of a discharge occurring in these conditions is low, except in cases of extreme wetting, where the possibility of flashover increases. Meanwhile, the critical condition of the insulator under test was found under two circumstances: first, under medium contamination conditions with Wt of 9 mL/h, NSDD of 0.35 mg/cm2, and all contamination distribution Pu/PL cases; and second, when SDD is high under medium and heavy levels for Wt, NSDD, and all Pu/PL cases. The flashover possibility occurring in these conditions is high, especially under high wetting and high NSDD.

5.3.2. Insulator Condition Classification Based on Proposed Indicators

To develop a statistical technique for identifying diagnostic indicator borders based on the x1, x2, x3, x4, x5, and x6 inputs, the naïve Bayes classification algorithm [46] was trained with the experimental data to predict the insulator’s state. In this study, MATLAB’s Deep Learning Toolbox was employed to develop the classification model. In the classification procedure, 952 data sets for each indicator were used in the classification process using the naïve Bayes classifier algorithm, where 70% of the data (666 data) were chosen for the model training, 15% of the data (143 data) were utilized for the model performance verification, and the other 15% of the data (143 data) were selected for the model testing, as shown in Figure 14. The boundary classification results of indicators x1, x2, x3, x4, x5, and x6 based on naïve Bayes classification are also shown in Figure 14.

Figure 14.

Figure 14

Visualization of the training samples of leakage current indicators: (a) x1; (b) x2; (c) x3; (d) x4; (e) x5; (f) x6.

Figure 15 depicts the limitations of the suggested indicators for diagnosing insulator conditions (normal, abnormal, and critical). Taking indicator x1 as an example, the insulator condition is normal when the x1 value is less than 7.59 mA, abnormal when it is about 20.88 mA, and critical when it is more than 46.6 mA. Of note, the restriction was set at 75% of each level’s data in the box plot (Figure 14). Therefore, the insulator state is normal when x1 is less than 9.33 and abnormal when x1 is between 15.9 mA and 25.3 mA; otherwise, the insulator condition is critical.

Figure 15.

Figure 15

Limitation of insulator condition indicators: (a) x1; (b) x2; (c) x3; (d) x4; (e) x5; (f) x6.

5.4. Determination of Indices’ Performance

To determine the performance of the proposed indices precisely, the ability of the indicators to accurately estimate the insulator state taken from the data set of 952 tests observation was examined. The sensitivity, precision, and accuracy of these indices were calculated using the confusion matrix shown in Figure 16 during the assessment based on the naïve Bayes classification. The parameters of the confusion matrix were specified based on the insulator condition preparation. The decision of test results and proposed indices are defined as:

  1. True positive (TP) represents the number of insulator tests that have been properly classified using the indicators to have pollution, meaning they have the pollution.

  2. True negative (TN) represents the number of correctly classified insulator tests using the indicators as clean and it in fact is clean.

  3. False positive (FP) represents the number of misclassified insulator tests using the indicators as polluted, but in fact they are polluted.

  4. False negative (FN) represents the number of insulator tests misclassified using the indicators as polluted, but in fact are not polluted.

Figure 16.

Figure 16

Confusion matrix for evaluating of the proposed indicators.

Experimentally, 905 test results out of 952 total tests reflected the insulator condition correctly, whereas 47 test results provided negative results. The explanation for the erroneous test results is a lack of implementation of pollutants on the insulator surface in a proper way or measuring-device error. In comparison to the total number of test outcomes, the number of prediction results for each indicator varied.

The variation in the prediction results may assist in determining which indicators are the best. It can be observed that the indices with a high number of correct prediction results are the best and will achieve high accuracy.

According to the indicator-prediction output, the greatest number of correct predicted results was observed for indicator x6 (906), followed by x3 (894), x4 (890), x1 (883), x5 (879), and x2 (873). As a result, the highest indicator accuracy is x6, followed by x3, x4, x1, x5, and x2 accordingly, as shown in Table 6. Meanwhile, the greatest sensitivity was in indicator x3, followed by x6, x4, x1, x5, and x2 accordingly. Moreover, the “best” performance is that where the variance between sensitivity and specificity is the least [47]. According to Table 5, the smallest difference between sensitivity and specificity is shown with the indicator x6, followed by x3, x4, x1, x5 and x2 accordingly. The sensitivity, precision, and accuracy of these indices were calculated using the confusion matrix shown in Figure 16 during the assessment.

Table 6.

The indices’ sensitivity, specificity, and accuracy for the 143 tests based on naïve Bayes algorithm.

Indicator Sensitivity Specificity Accuracy
x1 0.932 0.329 0.868
x2 0.947 0.295 0.849
x3 0.951 0.452 0.901
x4 0.948 0.413 0.892
x5 0.950 0.338 0.868
x6 0.954 0.540 0.918

6. Conclusions

This paper reports on an experimental investigation of leakage current indices to determine the stability of polluted insulators. Porcelain insulators of 11 kV and 33 kV distribution lines under different levels of contamination (SDD), wetting rate (Wt), insoluble deposit density (NSDD), and nonuniform distribution pollution (Pu/PL) were investigated. The temporal and frequency characteristics of the leakage current were then derived from the laboratory test results and used as assessment indicators for the insulators’ physical properties. The leakage current indication ranges were classified using the naïve Bayes technique into three levels of insulator health status. The suggested indicator’s performance was evaluated using the confusion matrix approach. The indicators used in this study are all useful in detecting the pollution levels of the insulators. According to the confusion matrix study, the odd harmonic indicator x6, slope indicator x3, and crest factor indicator x4 perform better than the others in terms of accuracy, with 0.918, 0.901, and 0.892, respectively.

Acknowledgments

This work was supported by collaboration between National Defence University of Malaysia (UPNM) and the Post-Doctoral Fellowship Scheme under the Professional Development Research University Grant (05E68) from Universiti Teknologi Malaysia (UTM).

Author Contributions

Conceptualization, A.A.S., K.Y.L. and S.A.A.-G.; methodology, A.A.S.; K.Y.L. and Z.A.-M.; software, A.A.S., S.M.A.-A., A.M., A.A.S.A. and S.S.M.G.; validation, A.A.S. and Z.A.-M.; formal analysis, A.A.S., K.Y.L., S.A.A.-G. and M.T.I.; investigation, A.A.S., K.Y.L., S.M.A.-A. and M.T.I.; resources, A.A.S. and K.Y.L.; data curation, A.A.S.; writing—original draft preparation, A.A.S. and K.Y.L.; writing—review and editing, A.A.S., S.A.A.-G., K.Y.L., M.T.I., S.M.A.-A., S.S.M.G., A.M, A.A.S.A. and Z.A.-M.; visualization, A.A.S. and K.Y.L.; supervision, A.A.S., K.Y.L., M.T.I., S.S.M.G. and Z.A.-M.; project administration, A.A.S. and K.Y.L.; funding acquisition, K.Y.L., M.T.I. and Z.A.-M. All authors have read and agreed to the published version of the manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

Funding Statement

This research was funded by collaboration between National Defence University of Malaysia (UPNM) and the Post-Doctoral Fellowship Scheme under the Professional Development Research University Grant (05E68) from Universiti Teknologi Malaysia (UTM).

Footnotes

Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

References

  • 1.Sopelsa Neto N.F., Stefenon S.F., Meyer L.H., Bruns R., Nied A., Seman L.O., Gonzalez G.V., Leithardt V.R.Q., Yow K.-C. A Study of Multilayer Perceptron Networks Applied to Classification of Ceramic Insulators Using Ultrasound. Appl. Sci. 2021;11:1592. doi: 10.3390/app11041592. [DOI] [Google Scholar]
  • 2.Salem A.A., Abd-Rahman R., Al-Gailani S.A., Salam Z., Kamarudin M.S., Zainuddin H., Yousof M.F.M. Risk Assessment of Polluted Glass Insulator Using Leakage Current Index Under Different Operating Conditions. IEEE Access. 2020;8:175827–175839. doi: 10.1109/ACCESS.2020.3026136. [DOI] [Google Scholar]
  • 3.Lan L., Mu L., Yuan X., Yan J., Wang Y., Wang W., Shen Y., Hao L. Studies on metallurgical contamination accumulation characteristics on ceramic insulator of 500 kV AC transmission line. IET Sci. Meas. Technol. 2019;13:722–728. doi: 10.1049/iet-smt.2018.5099. [DOI] [Google Scholar]
  • 4.Zhang D., Xu H., Liu J., Yang C., Huang X., Zhang Z., Jiang X. Research on the Non-Contact Pollution Monitoring Method of Composite Insulator Based on Space Electric Field. Energies. 2021;14:2116. doi: 10.3390/en14082116. [DOI] [Google Scholar]
  • 5.Zhang Z., Yang S., Jiang X., Qiao X., Xiang Y., Zhang D. DC Flashover Dynamic Model of Post Insulator under Non-Uniform Pollution between Windward and Leeward Sides. Energies. 2019;12:2345. doi: 10.3390/en12122345. [DOI] [Google Scholar]
  • 6.Liu Y., Li Q., Du B., Farzaneh M. Feature extraction and classification of surface discharges on an ice-covered insulator string during AC flashover using gray-level co-occurrence matrix. Sci. Rep. 2021;11:2542. doi: 10.1038/s41598-021-82254-9. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 7.Mestriner D., Brignone M. Corona Effect Influence on the Lightning Performance of Overhead Distribution Lines. Appl. Sci. 2020;10:4902. doi: 10.3390/app10144902. [DOI] [Google Scholar]
  • 8.Yamashita T., Ishimoto R., Furusato T. Influence of series resistance on dry-band discharge characteristics on wet pollute insulators. IEEE Trans. Dielectr. Electr. Insul. 2018;25:154–161. doi: 10.1109/TDEI.2018.007005. [DOI] [Google Scholar]
  • 9.Ren A., Liu H., Wei J., Li Q. Natural Contamination and Surface Flashover on Silicone Rubber Surface under Haze–Fog Environment. Energies. 2017;10:1580. doi: 10.3390/en10101580. [DOI] [Google Scholar]
  • 10.De Barros Bezerra J.M., Lima A.M.N., Deep G.S., da Costa E.G. An Evaluation of Alternative Techniques for Monitoring Insulator Pollution. IEEE Trans. Power Deliv. 2009;24:1773–1780. doi: 10.1109/TPWRD.2009.2016628. [DOI] [Google Scholar]
  • 11.Choi I.H., Koo J.B., Woo J.W., Son J.A., Bae D.Y., Yoon Y.G., Oh T.K. Damage Evaluation of Porcelain Insulators with 154 kV Transmission Lines by Various Support Vector Machine (SVM) and Ensemble Methods Using Frequency Response Data. Appl. Sci. 2020;10:84. doi: 10.3390/app10010084. [DOI] [Google Scholar]
  • 12.Suda T. Frequency Characteristics of Leakage Current Waveforms of Artificially Polluted Suspension insulators. IEEE Trans. Dielectr. Electr. Insul. 2005;8:705–709. doi: 10.1109/94.946726. [DOI] [Google Scholar]
  • 13.Hussain M.M., Farokhi S., McMeekin S.G., Farzaneh M. Risk Assessment of Failure of Outdoor High Voltage Polluted Insulators under Combined Stresses Near Shoreline. Energies. 2017;10:1661. doi: 10.3390/en10101661. [DOI] [Google Scholar]
  • 14.Fofana I., N’cho J.S., Betie A., Hounton E., Meghnefi F., Yapi K.M.L. Lessons to Learn from Post-Installation Pollution Levels Assessment of Some Distribution Insulators. Energies. 2020;13:4064. doi: 10.3390/en13164064. [DOI] [Google Scholar]
  • 15.Chen W., Wang W., Xia Q., Luo B., Li L. Insulator Contamination Forecasting Based on Fractal Analysis of Leakage Current. Energies. 2012;5:2594–2607. doi: 10.3390/en5072594. [DOI] [Google Scholar]
  • 16.Salem A.A., Abd-Rahman R., Al-Gailani S.A., Kamarudin M.S., Ahmad H., Salam Z. The Leakage Current Components as a Diagnostic Tool to Estimate Contamination Level on High Voltage Insulators. IEEE Access. 2020;8:92514–92528. doi: 10.1109/ACCESS.2020.2993630. [DOI] [Google Scholar]
  • 17.Jiang Y., McMeekin S.G., Reid A.J., Nekahi A., Judd M.D., Wilson A. Monitoring contamination level on insulator materials under dry condition with a microwave reflectometer. IEEE Trans. Dielectr. Electr. Insul. 2016;23:1427–1434. doi: 10.1109/TDEI.2015.005594. [DOI] [Google Scholar]
  • 18.Fontana E., Martins-Filho J.F., Oliveira S.C., Cavalcanti F.J.M.M., Lima R.A., Cavalcanti G.O., Prata T.L., Lima R.B. Sensor network for monitoring the state of pollution of high-voltage insulators via satellite. IEEE Trans. Power Deliv. 2012;27:953–962. doi: 10.1109/TPWRD.2012.2183623. [DOI] [Google Scholar]
  • 19.Douar M.A., Mekhaldi A., Bouzidi M.C. Flashover process and frequency analysis of the leakage current on insulator model under non-uniform pollution conditions. IEEE Trans. Dielectr. Electr. Insul. 2010;17:1284–1297. doi: 10.1109/TDEI.2010.5539701. [DOI] [Google Scholar]
  • 20.Palangar M.F., Mirzaie M. Diagnosis Porcelain and Glass Insulators Conditions Using Phase Angle Index Based on Experimental Test. IEEE Trans. Dielectr. Electr. Insul. 2016;23:3–9. doi: 10.1109/TDEI.2015.005586. [DOI] [Google Scholar]
  • 21.Shaik M.G., Karuppaiyan V. Investigation of Surface Degradation of Aged High Temperature Vulcanized (HTV) Silicone Rubber Insulators. Energies. 2019;12:3769. doi: 10.3390/en12193769. [DOI] [Google Scholar]
  • 22.Zhao S., Jiang X., Zhang Z., Hu J., Shu L. Flashover voltage prediction of composite insulators based on the characteristics of leakage current. IEEE Trans. Power Deliv. 2013;28:1699–1708. doi: 10.1109/TPWRD.2013.2257879. [DOI] [Google Scholar]
  • 23.Terrab H., Bayadi A. Experimental Study Using Design of Experiment of Pollution Layer Effect on Insulator Performance Taking into Account the Presence of Dry Bands IEEE Trans. Dielectr. Electr. Insul. 2014;21:2486–2495. doi: 10.1109/TDEI.2014.004542. [DOI] [Google Scholar]
  • 24.Liu Y., Du B.X. Recurrent plot analysis of leakage current on flashover performance of rime-iced composite insulator. IEEE Trans. Dielectr. Electr. Insul. 2010;17:465–472. doi: 10.1109/TDEI.2010.5448102. [DOI] [Google Scholar]
  • 25.Li J., Sima W., Sun C., Sebo S.A. Use of leakage currents of insulators to determine the stage characteristics of the flashover process and contamination level prediction. IEEE Trans. Dielectr. Electr. Insul. 2010;17:490–501. doi: 10.1109/TDEI.2010.5448105. [DOI] [Google Scholar]
  • 26.Ghosh R., Chatterjee B., Chakravorti S. A novel leakage current index for the field monitoring of overhead insulators under harmonic voltage. IEEE Trans. Ind. Electron. 2018;65:1568–1576. doi: 10.1109/TIE.2017.2733490. [DOI] [Google Scholar]
  • 27.Kordkheili H.H., Abravesh H., Tabasi M., Dakhem M., Abravesh M.M. Determining the probability of flashover occurrence in composite insulators by using leakage current harmonic components. IEEE Trans. Dielectr. Electr. Insul. 2010;17:502–512. doi: 10.1109/TDEI.2010.5448106. [DOI] [Google Scholar]
  • 28.Park K.C., Yoon J.R. Analysis of the insulators’ radiation noises for error detections. Symp. Ultrason. Electron. 2009;30:249–250. [Google Scholar]
  • 29.Park K.C., Motai Y., Yoon J.R. Acoustic fault detection technique for high-power insulators. IEEE Trans. Ind. Electron. 2017;64:9699–9708. doi: 10.1109/TIE.2017.2716862. [DOI] [Google Scholar]
  • 30.Ha H., Han S., Lee J. Fault detection on transmission lines using a microphone array and an infrared thermal imaging camera. IEEE Trans. Instrum. Meas. 2012;61:267–275. doi: 10.1109/TIM.2011.2159322. [DOI] [Google Scholar]
  • 31.Wang B. Automatic fault diagnosis of infrared insulator images based on image instance segmentation and temperature analysis. IEEE Trans. Instrum. Meas. 2020;69:5345–5355. doi: 10.1109/TIM.2020.2965635. [DOI] [Google Scholar]
  • 32.Upadhyay A.K., Johri P., Reddy C.C., Sandhu A. Direct measurement of accumulated space charge using external currents. IEEE Trans. Instrum. Meas. 2021;70:1–8. doi: 10.1109/TIM.2020.3041381. [DOI] [Google Scholar]
  • 33.Salem A.A., Lau K.Y., Abdul-Malek Z., Tan C.W. Classifying insulator conditions of room temperature vulcanized coated glass insulators under different coating damage modes. Measurement. 2022;194:111032. doi: 10.1016/j.measurement.2022.111032. [DOI] [Google Scholar]
  • 34.Stefenon S.F. Classification of insulators using neural network based on computer vision. IET Gener. Transm. Distrib. 2022;16:1096–1107. doi: 10.1049/gtd2.12353. [DOI] [Google Scholar]
  • 35.Corso M.P., Perez F.L., Stefenon S.F., Yow K.C., Ovejero R.G., Leithardt V.R. Classification of contaminated insulators using k-nearest neighbors based on computer vision. Computers. 2021;10:112. doi: 10.3390/computers10090112. [DOI] [Google Scholar]
  • 36.CEI Artificial pollution tests on high-voltage insulators to be used on A.C. systems. IEC; Geneva, Switzerland: 2013. [Google Scholar]
  • 37.Salem A.A. Proposal of a Dynamic Numerical Approach in Predicting Flashover Critical Voltage. Int. J. Power Electron. Drive Syst. IJEPDS. 2019;10:602–610. doi: 10.11591/ijpeds.v10.i2.pp602-610. [DOI] [Google Scholar]
  • 38.Salem A.A., Abd-Rahman R., Rahiman W., Al-Gailani S.A., Al-Ameri S.M., Ishak M.T., Sheikh U.U. Pollution Flashover Under Different Contamination Profiles on High Voltage Insulator: Numerical and Experiment Investigation. IEEE Access. 2021;9:37800–37812. doi: 10.1109/ACCESS.2021.3063201. [DOI] [Google Scholar]
  • 39.Arshad A., Tahir A., Stewart B.G., Nekahi A. Forecasting Flashover Parameters of Polymeric Insulators under Contaminated Conditions Using the Machine Learning Technique. Energies. 2020;13:3889. doi: 10.3390/en13153889. [DOI] [Google Scholar]
  • 40.Salem A.A., Lau K.Y., Rahiman W., Al-Gailani S.A., Abdul-Malek Z., Abd Rahman R., Al-Ameri S.M., Sheikh U.U. Pollution Flashover Characteristics of Coated Insulators under Different Profiles of Coating Damage. Coatings. 2021;11:1194. doi: 10.3390/coatings11101194. [DOI] [Google Scholar]
  • 41.Selection and Dimensioning of High-Voltage Insulators Intended for Use in Polluted Conditions. IEC; Geneva, Switzerland: 2008. [Google Scholar]
  • 42.Zhang Z., Qiao X., Yang S., Jiang X. Non-Uniform Distribution of Contamination on Composite Insulators in HVDC Transmission Lines. Appl. Sci. 2018;8:1962. doi: 10.3390/app8101962. [DOI] [Google Scholar]
  • 43.Hsu S.C., Chen I.C., Huang C.L. Image classification using Naive Bayes classifier with pairwise local observations. J. Inf. Sci. Eng. 2017;33:1–15. [Google Scholar]
  • 44.Aydogan A., Atalar F., Ersoy Yilmaz A., Rozga P. Using the Method of Harmonic Distortion Analysis in Partial Discharge Assessment in Mineral Oil in a Non-Uniform Electric Field. Energies. 2020;13:4830. doi: 10.3390/en13184830. [DOI] [Google Scholar]
  • 45.Bashir N., Ahmad H. Odd harmonics and third to fifth harmonic ratios of leakage currents as diagnostic tools to study the ageing of glass insulators. IEEE Trans. Dielectr. Electr. Insul. 2010;17:819–832. doi: 10.1109/TDEI.2010.5492255. [DOI] [Google Scholar]
  • 46.Rish I. An empirical study of the naive Bayes classifier; Proceedings of the IJCAI 2001 Workshop on Empirical Methods in Artificial Intelligence; Seattle, WA, USA. 4–10 August 2001; [Google Scholar]
  • 47.Fielding A.H., Bell J.F. A review of methods for the assessment of prediction errors in conservation presence/absence models. Environ. Conserv. 1997;24:38–49. doi: 10.1017/S0376892997000088. [DOI] [Google Scholar]