Analytical modelling of food storage cooling with solar ammonia-water absorption system, powered by parabolic trough collectors. Method

Octavian G Pop a, Alexandru Dobrovicescu b, Alexandru Serban b, Mihaela Ciocan b, Anass Zaaoumi c, Daniel P Hiris d, Mugur C Balan a,d,
PMCID: PMC9860445  PMID: 36691669

Abstract

The study presents a new analytical model capable to reveal the thermal behaviour of all the components of the solar ammonia-water absorption system, powered by parabolic trough collectors, serving different types of food storages: refrigeration chamber, refrigerated food storage, freezing chamber and frozen food storage. The heat inputs, that determine the total cooling load, for each food storage spaces consist of: heat gains through walls, heat gains through ventilation (fresh air), heat that must be dissipated from the stored products (technological cooling load required to cool down the products) and heat gains through operation. The influence of the number of solar parabolic trough collectors and of the storage tank size on different parameters of the refrigeration plant are investigated under low and high storage temperatures.

  • Food cooling with solar absorption refrigeration system.

  • Hourly based variation of NH3-H2O solar absorption system performances.

  • Long term simulation of solar absorption cooling for refrigeration and cooling.

Keywords: Solar cooling, Absorption, Ammonia-water, Parabolic trough collectors, Food storage cooling, Modelling

Method name: Analytical modelling of food storage cooling with solar ammonia-water absorption system, powered by parabolic trough collectors

Graphical abstract

Image, graphical abstract


Specifications Table

Subject Area: Refrigeration, Solar Energy, and Analytical Modelling
More specific subject area: Analytical modelling of solar refrigeration system
Method name: Analytical modelling of food storage cooling with solar ammonia-water absorption system, powered by parabolic trough collectors
Name and reference of original method: Not applicable
Resource availability: Not applicable

Introduction

In industrial solar thermal cooling applications, if the required temperatures are near 0 °C or below, the absorption-based systems with ammonia-water (NH3—H2O) are the most appropriate options [9]. The temperature of the hot heat transfer fluid required for driving such equipment are recommended in the range of (120 … 180) °C [1] or of (140 … 200) °C [27]. If solar energy is used to power these systems, solar collectors with concentrators (SCC) are required. Experimental studies investigating solar cooling below 0 °C provided by linear SCC, are reported in [27,10]. The basic principles of modelling solar parabolic trough collectors (SPTC) are presented in [20].

Modelling the NH3—H2O absorption cycles starts with the calculation of thermal properties of this solution, as presented in [30, 14] and later in [26,28].

A mathematical model of a solar NH3—H2O absorption system is provided in [2] and was applied to milk cooling applications in [3]. Thermal performances of a NH3—H2O refrigeration system are investigated in [18] while optimizations of such systems are proposed in [4]. Solar absorption refrigeration systems were modelled in [13] where a 5-days simulation is presented. A complex NH3—H2O absorption system providing freezing, air conditioning and heating was proposed in [11].

Combinations of different SCC and different types of LiBr-H2O absorption chillers with single and double effect were investigated in [25]. Parabolic dish collectors are investigated in solar refrigeration and desalinization systems [19]. SPTC can be used to power both NH3—H2O heat pumps [7] and adsorption refrigeration systems [15].

Heat storage must be used to allow continuous operation of the absorption refrigeration system, due to the well-known variability of solar radiation. Both hot or cold storage tanks can be used [12,21].

The number of investigations related to the solar refrigeration systems based on SCC is mentioned to be very low in some studies. In [27], it is stated that studies on the testing of NH3—H2O absorption systems with SCC are scarce. In [5], it is reported that the number of publications related to absorption systems with SCC are “far to be comparable” to the number of studies investigating the classic low temperature solar collectors. The same study mentions that in 2012 the total number of operational absorption systems with SCC was of only 46. A review related to these systems mentions that in 2011 < 30 systems based on these SCC were operational worldwide and only 6 of them could provide negative temperatures [1].

Long term simulations of the dynamic thermal behaviour of SCC based absorption systems are also rare, like the one-year simulations of solar LiBr-H2O single effect and double effect absorption systems that are presented in [5] and [31], respectively. Also, one-year simulations of a solar NH3—H2O absorption system is analysed in [16].

  • According to the presented literature review, the following aspects were not investigated:

  • - Food cooling with solar absorption refrigeration system.

  • - Hourly based modelling of food cooling load variation.

  • - Hourly based variation of NH3—H2O solar absorption system performances.

  • - Long term simulation of solar absorption cooling for refrigeration and cooling.

The goal of the study is to present the methodology for the analytical investigation of the food storage cooling with solar ammonia-water absorption system, powered by SPTC. The refrigeration plant considered in this study, consists of one stage NH3—H2O absorption, powered by SPTC. The heat is evacuated through water in a closed circuit equipped with a cooling tower. The backup equipment is a classic one stage mechanical compression refrigeration plant with NH3 as refrigerant. A seasonal heat storage is also considered.

Method

Preliminary considerations

  • This study is focused on the solar cooling of four types of food storages:

  • - Refrigeration chamber (RC) (fresh products are cooled above 0 °C),

  • - Refrigerated food storage (RS) (previously refrigerated products are maintained at above 0 °C),

  • - Freezing chamber (FC) (fresh products are cooled below 0 °C),

  • - Frozen food storage (FS) (previously frozen products are maintained at below 0 °C).

For simplicity, for this solar cooling study, it was considered that all types of the studied food storage spaces are employed for chicken meat. The influence of other products can also be investigated based on the same method.

The climatic data considered for calculations were taken from the typical meteorological year (TMY), available on the European Union web site [17], that provides hourly based variations of several climatic parameters: dry bulb (or ambient) temperature (tdb [ °C]), relative humidity (φ [%]), global solar radiation on the horizontal plane (I [W/m2]), direct solar radiation (Idir [W/m2]), diffuse solar radiation (Idif [W/m2]), direct normal irradiance (DNI [W/m2]), etc.

The cooling load types, considered for each food storage space, are presented in Table 1.

Table 1.

Cooling load types for each food storage space.

Storage type Walls1 Ventilation2 Technological3 Operation4
RC
RS
FC
FS
1

Heat gains through walls;.

2

Heat gains through ventilation (fresh air);.

3

Technological cooling load (required to cool down the products);.

4

Heat gains through operation.

For all the cold spaces, each wall, ceiling, and floor, were considered to be manufactured from sandwich panels filled with polyurethane. The width of these panels was calculated considering the ambient temperature and relative humidity of 40 °C and 40%, respectively.

The inside temperature was considered to be 3 °C for refrigeration and −20 °C for freezing. The inside relative humidity was considered to be 90% in all cases.

The air flow rate for ventilation was considered to be 3 storage volumes in 24 h (15,000 m3/h).

The technological cooling load (required to cool down the chicken meat), for both refrigeration and freezing was determined based on the specific enthalpy variation with temperature, as presented in Table 2.

Table 2.

Chicken meat specific enthalpy variation with temperature.

Temperature [ °C] −18 −15 −10 −5 −1 0 1 5 10 15 20 25
Specific enthalpy [kJ/kg] 4.6 12.97 30.13 57.34 186.2 232.3 235.6 248.2 264.5 280.4 296.7 312.6

The cooling charge duration was considered to be 10 h for refrigeration and 20 h for freezing.

The main refrigeration equipment is of one stage absorption type with ammonia-water as working couple.

The backup refrigeration equipment, to be used in periods without available solar heat is a one stage mechanical refrigeration machine, with ammonia as refrigerant. In order to increase the availability of solar heat, a heat storage tank was proposed, and its influence was investigated.

For the heat rejection, from both thermal (absorption) and electrical (mechanical compression) machines, a cooling tower with closed water circuit is used.

The principle scheme of the investigated system is presented in Fig. 1.

Fig. 1.

Fig 1

The principle scheme of the solar cooling system with electric backup.

It can be observed that cold can be extracted from the cold storage spaces by both the main absorption machine, driven by solar heat or by the mechanical machine, driven by electricity. The thermal behaviour and the energy exchange of both machines was investigated. In this study, the electric energy consumption of the pump was computed, but no particular attention was granted to the source of this electrical energy and to its value, that was neglected when the COP of the absorption machine was computed.

Time variation of the cooling load through walls

The time variation of the cooling load (or heat gain) through walls is determined by the ambient temperature variation and the dependence between this type of cooling load and the ambient temperature is linear.

The cooling load through walls (Q˙w[W]) can be determined with the Eq. (1):

Q˙w=k·S·(tdbti)[W] (1)

where:

  • k·S [W/K] is the thermal characteristic of the cold storage spaces

  • tdb [°C] is the variable dry bulb (ambient) temperature

  • ti [°C] is the inside temperature of the cold storage spaces (3 °C for RC and RS and −20 °C for FC and FS)

The values of (k·S) for the investigated cold storage spaces are presented in the Table 3.

Table 3.

The values of (k·S) for the food cold storage spaces.

Storage type RC RS FC FS
(k·S) [kW/K] 0.0135 0.676 0.0083 0.50

These values depend on each wall's level of insulation and on the dimensions of the storage.

The cooling load through walls (Q˙w[W]) can also be determined with the Eq. (2):

Q˙w=Q˙ntnti·tdbQ˙n·tltnti[W] (2)

where:

  • Q˙n[W] is the nominal cooling load through walls, determined in nominal working conditions (0.5 kW for RC, 25 kW for RS, 0.5 kW for FC and 30 kW for FS)

  • tn = 40 °C is the nominal dry bulb (ambient) temperature considered in this study

Time variation of the ventilation cooling load

The single ventilated cold storage space is RS, and the ventilation cooling load is determined by the need to cool down the fresh air from the variable ambient temperature to the inside temperature.

The ventilation cooling load (Q˙v[W]) can be calculated with the Eq. (3):

Q˙v=ρ·V˙·c·(tdbti)[W] (3)

where:

  • ρ [kg/m3] is the fresh air density

  • V˙ [m3/s] is the fresh air volume flow rate calculated to supply the 3 vol air change in 24 h

  • c [kJ/kgK] is the fresh air specific heat capacity

Time variation of the technological cooling load

The time variation of the technological cooling load was considered based on the shape of the cooling load curves presented in [6].

Fig. 2 presents the considered cooling load variation in time, for both refrigeration and freezing of the chicken meat.

Fig. 2.

Fig 2

The variation of the technological cooling load for 1 kg of chicken meat.

For the calculation of the technological cooling load (Q˙t[W/kg]) in the case of chicken meat , the variation with time (τ [h]) was taken into account using the proposed equation:

Q˙t=a·τ2b·τ+c (4)

The coefficients a, b and c, are provided in Table 4.

Table 4.

Values of coefficients.

Coefficients a b c
Refrigeration 0.2120 4.30615 21.9990
Freezing 0.0813 3.11665 29.8795

To the best of the authors' knowledge, such an equation is not available in the literature.

Time variation of the operation cooling load

The operation cooling load is determined by the heat gain through the operations of loading, unloading, lighting, etc.

In this study, the operation cooling load (Q˙op[W]) was determined as a share of the cooling load through walls with the Eq. (5):

Q˙op=0.4·Q˙w (5)

Analytical model for the thermal efficiency of the parabolic trough collectors

The analytical model of the SPTC, is presented, and validated in [29]. Some information about SPTC is also presented in [20]. The location is determined by longitude (λ [°]) and latitude (φ [°]) while the position of the sun is defined by the angle of the solar altitude (γS [°]) and the angle of solar azimuth (αS [°]). The orientation of the collectors is defined by the tilt angle (γt [°]) and the orientation angle related to the azimuth (αt [°]). The solar angle of incidence on the tilted surface of the SPTC (θ [°]) and the global thermal efficiency of the SPTC (η [-]) were computed.

The thermal regime of the cooling tower

The investigation of the thermal regime of the cooling tower during the whole year operation period is important because this equipment is used by both types of refrigerating plants: the solar driven absorption plant and the electrical driven plant used as backup.

The cooling water temperature (at the return from the cooling tower) was determined as a function of the wet bulb temperature (twb [ °C]):

tw=twb+5[C] (6)

The difference of 5 °C is in agreement with [22] where this temperature difference, for such kind of applications, is reported in the range (3.2 – 4.8) °C and with [23] where this temperature difference is reported in the range (1.5 – 5.5) °C.

The wet bulb temperature is determined by the ambient (dry bulb) temperature (tdb [°C]) and by the relative humidity (φ [%]) of the ambient air and was calculated using the equation provided in [24]:

twb=tdb·atan[0.151977·(φ+8.313659)1/2]+atan(tdb+φ)atan(φ1.676331)+0.00391838·φ3/2·atan(0.023101·φ)4.686035 (7)

The operation of the cooling tower was considered adjustable to maintain a minimum temperature of the cooling water at outlet of 10 °C. Thus, if the ambient temperature decreases, the fans speed will be reduced, to maintain the minimum set up temperature of the cooling water.

Thermal behaviour of the storage tank

The storage tank is considered fully mixed, is filled with diathermic oil, and operates as a heat buffer to power the absorption plant in periods with reduced or without solar radiation. The tank is heated when solar radiation is available in excess and is cooled down when the stored heat is used.

The maximum temperature of the oil in the storage tank can be either the maximum expected value of the required hot temperature or the higher temperature that can be reached in the SPTC (400 °C). In this study both situations were considered. A heat exchanger is considered to provide the exact required variable heating power at the required variable temperature, according to the variable operating conditions of the plant. The heating power and temperature are regulated depending on the available oil temperature in the storage tank, by also regulating the oil flow rate.

The minimum temperature of the oil in the storage tank should be the minimum required hot temperature for the operation of the absorption plant, depending on the operating conditions.

The temperature variation of the storage tank oil (Δt [ °C]) in a period (τ [s]), can be determined as a function of the exchanged heat (Qst [kJ]):

Δt=Qstm·c (8)

where:

  • - m [kg] is the mass of the oil in the storage tank

  • - c = 1.85 kJ/kgK is the average specific heat capacity of the oil.

The exchanged heat can be calculated from the heat balance on the storage tank:

Qst=Qsol,exQop,stQloss (9)

where:

  • - Qsol,ex [kJ] is the solar heat that exceeds the required heat for the absorption plant operation

  • - Qop,st [kJ] is the heat extracted from the storage tank for the absorption plant operation

  • - Qloss [kJ] is the heat loss through the storage tank insulation under the variable temperature difference between the oil and the exterior air.

A layer of polyurethane thermal insulation with a thickness of 0.5 m was considered.

Absorption refrigeration plant

The principle scheme of the main one stage absorption refrigerating plant with NH3—H2O is presented in Fig. 3.

Fig. 3.

Fig 3

The principle scheme of the NH3—H2O absorption refrigerating plant.

The main refrigerating circuit is composed of the condenser, the expansion device, the evaporator, and the heat exchanger, while the thermochemical compressor consists of the following components: absorber; rich solution pump; generator; expansion device of the weak solution and heat exchanger. The refrigerant is NH3 and the solvent is H2O. The working process of the main refrigerating circuit is presented in Fig. 4 in the pressure – enthalpy diagram, while the working process of the NH3—H2O solution is presented in Fig. 5 in the enthalpy – concentration diagram.

Fig. 4.

Fig 4

The working process of the main refrigerating circuit.

Fig. 5.

Fig 5

The working process of the NH3—H2O solution.

The internal working conditions were determined as a function of the external working conditions.

The evaporating temperature (t0 [ °C]) was determined as a function of the inside temperature (ti [ °C]):

t0=t7=ti13[C] (10)

The assumption that the vapors of the refrigerant at the outlet of the evaporator are at the evaporating temperature agrees with [8]. The evaporating temperature determines the evaporating pressure (p0 [bar]).

The condensing temperature (tk [ °C]) was determined as a function of the cooling water temperature (tw [ °C]) at the return from the cooling tower:

tk=t4=tw+8[C] (11)

The assumption that the liquid refrigerant at the outlet of the condenser is saturated, agrees with [4]. The condensing temperature determines the condensing pressure (pk [bar]).

The saturated weak solution temperature at the outlet of the generator (tg [ °C]) was determined as a function of the hot oil temperature (th [ °C]) at the return from the SPTC:

tg=t3=th10[C] (12)

The difference of 10 °C agrees with [2].

The superheated refrigerant temperature (t8 [°C]) at the outlet of the heat exchanger from the main refrigerant circuit, was determined as:

t8=tk20[C] (13)

The specific enthalpy of the subcooled refrigerant (h5 [kJ/kg]) at the outlet of the heat exchanger from the main refrigerant circuit, was determined from the energy balance equation on the heat exchanger:

h5=h4h8+h7[kJ/kg] (14)

The specific enthalpy at the outlet of the expansion valve on the main refrigerant circuit (h6 [kJ/kg]) is equal with the specific enthalpy at the inlet:

h6=h5[kJ/kg] (15)

The parameters of the saturated vapors of the refrigerant at the outlet of the generator (state 2) were determined at the condensing pressure (p2 = pk) and temperature (t2 = tk).

The parameters of the saturated liquid weak solution at the outlet of the generator (state 3) were determined at the condensing pressure (p3 = pk) and at the temperature at the outlet of the generator (t3 = tg).

The parameters of the saturated liquid rich solution at the outlet of the absorber (state 9) were determined at the evaporating pressure (p9 = p0) and at the condensing temperature (t9 = tk).

The specific enthalpy of the liquid rich solution at the outlet of the pump (state 10) was determined as a function of the specific mechanical work of the pump (wP [kJ/kg]) as:

h10=h9+wP[kJ/kg] (16)

with

wP=Δp·v9[kJ/kg] (17)

where (Δp = pk – p0) and v9 [m3/kg] is the specific volume of the liquid rich solution at the inlet of the pump.

The parameters of the saturated liquid rich solution in the concentrating column of the generator (state L) were determined at the condensing pressure (pL= pk) and at the concentration of the rich solution.

The parameters of the saturated vapors in equilibrium with the rich solution in the concentrating column of the generator (state V) were determined at the condensing pressure (pV= pk) and at the equilibrium temperature of the rich solution and of the vapors (tV = tL).

The temperature of the subcooled liquid rich solution at the inlet of the generator (t1 [ °C]) was determined as a function of the temperature of the saturated liquid (state L):

t1=tL3[C] (18)

The recirculating factor (f [-]), representing the ratio between the flow rate of the rich solution (m˙r[kg/s]) and the flow rate of the refrigerant in the main refrigerating circuit (m˙[kg/s]), was determined as a function of the concentrations of NH3 in the main refrigerating circuit (ξ”=1), in the rich solution circuit (ξr) and in the weak solution circuit (ξw):

f=ξξwξrξw=1ξwξrξw (19)

where (ξw = ξ3) and (ξr = ξ9).

The specific enthalpy of the subcooled weak solution at the inlet of the expansion valve (h11 [kJ/kg]), was determined from the energy balance equation on the heat exchanger on the NH3—H2O solutions circuit:

h11=h3ff1·(h1h10)[kJ/kg] (20)

The specific enthalpy at the outlet of the expansion valve on the weak solution circuit (h12 [kJ/kg]) is equal with the specific enthalpy at the inlet:

h12=h11[kJ/kg] (21)

The specific enthalpy of the ideal pole of rectification (hPi [kJ/kg]) was determined as a function of the enthalpies (hL [kJ/kg]) and (hV [kJ/kg]) and of the concentrations of NH3L [kJ/kg]) and V (ξL [kJ/kg]) in the states L and V, respectively:

hPi=hV·(1ξL)hL·(1ξV)ξVξL (22)

The specific thermal power of the absorber (qAB [kW/kg]) could be determined from the energy balance on the absorber:

qAb=h8+(f1)·h12f·h9 (23)

The specific thermal power of the ideal rectifier (qRi [kW/kg]) that should be evacuated from the rectifier (located in the upper side of the generator's concentrating column), could be computed as:

qRi=hPih2 (24)

The specific thermal power of the real rectifier (qR [kW/kg]) was determined considering an efficiency of the rectification (ηr = 0.88):

qR=qRiηr (25)

The specific thermal power of the generator (qG [kW/kg]) could be determined from the energy balance on the generator:

qG=qR+(f1)·h12f·h9 (26)

The specific thermal power of the condenser (qk [kW/kg]) could be determined from the energy balance on the condenser:

qk=h2h4 (27)

The specific thermal power of the evaporator (q0 [kW/kg]) could be determined from the energy balance on the evaporator:

q0=h7h6 (28)

The coefficient of performance (COP [-]) could be determined as the ratio between the specific thermal powers of the evaporator and of the generator:

COP=q0qG (29)

The thermal power of all the equipment were determined by multiplying the specific thermal powers with the mass flow rates corresponding to each equipment.

Limits of the hot temperature at the outlet of the solar field

The working conditions of the absorption refrigeration plant are determined by the temperatures of the three heat sources:

  • - Inside temperatures of the cold food storage spaces (ti [ °C])

  • - Temperature of the cooling water at the outlet of the cooling tower (tw [ °C])

  • - Temperature of the thermal agent at the outlet of the SPTC (also named the hot temperature) (th [ °C]).

During the operation, it was considered that the inside temperatures of the cold food storage spaces were constant (3 °C for the RC and RS and −20 °C for the FC and FS).

Since the temperature of the cooling water is variable under the influence of the ambient conditions (tdb and φ), the hot temperature must be adjusted to maintain a minimum degassing zone (Δξ), representing the difference between the concentrations of the rich solution (ξr) and of the weak solution (ξw):

Δξ=ξrξw (30)

A minimum degassing zone must be maintained because a decrease in degassing zone, will determine an increase in flow rates of the weak and rich solutions.

The hot temperature was determined for both refrigerating and freezing, considering two minimum values of the degassing zone (Δξ = 0.06) and (Δξ = 0.1).

Fig. 6 presents the minimum required hot temperatures as a function of the cooling water temperature for the degassing zones (Δξ = 0.06) and (Δξ = 0.1), for refrigeration and freezing.

Fig. 6.

Fig 6

The minimum required hot temperatures as a function of the cooling water temperature, for refrigeration and freezing.

If the degassing zone is lower, for each value of the hot temperature, the range of compatible cooling water temperatures decreases.

Based on the presented investigation, the minimum required hot temperature (of the heat transfer fluid at the outlet of the SPTC) was determined as a function of the cooling water temperature (at the outlet of the cooling tower), for the two considered degassing zones and for both refrigeration and freezing operating regimes, using the relation:

th=a·tw+b (31)

with the values of the coefficients, a and b presented in Table 5.

Table 5.

Values of the coefficients a and b (Eq. (31)).

Regime Refrigeration (t0 = −10 °C)
Freezing (t0 = −30 °C)
Δξ [-] 0.06 0.10 0.06 0.10
a 2.500 2.727 2.727 2.500
b 50.00 52.27 72.73 90.00
Range tw ≥ 12 °C tw ≥ 10 °C tw ≥ 10 °C tw ≥ 12 °C

To the best of the authors' knowledge, such a recommendation to calculate the minimum required hot temperature as a function of the cooling water temperature is not available in the literature.

The required hot temperatures are higher for higher degassing zones and for lower cooling temperatures.

Coefficient of performance for the absorption refrigeration plant

The coefficient of performance (COP) of the absorption refrigeration plant, depends on the operating conditions represented by the temperatures of the three heat sources. In both refrigeration and freezing operating regimes the inside temperatures of the cold food storage spaces were considered constant (3 °C for the RC and RS and −20 °C for the FC and FS). Previously it was determined that the minimum required hot temperature depends on the cooling water temperature. Thus, it can be concluded that if the hot temperature is maintained at the minimum required value, COP depends only on the cooling water temperature, for each inside temperature.

Figs. 7 and 8 present the influence of the cooling water temperature on the COP considering the minimum required values of the hot temperatures for refrigeration and freezing.

Fig. 7.

Fig 7

Influence of the cooling water temperature on the COP (refrigeration) (evaporating temperature: −10 °C).

Fig. 8.

Fig 8

Influence of the cooling water temperature on the COP (freezing) (evaporating temperature: −30 °C).

In both refrigeration and freezing operating regimes, the COP dependence on the cooling water temperature is linear, and the following correlation was determined:

COP=c·tw+d (32)

with the values of the coefficients, c and d presented in Table 6.

Table 6.

Values of the coefficients c and d (Eq. (32)).

Regime c d
Refrigeration (t0 = −10 °C) −0.0072 0.7182
Freezing (t0 = −30 °C) −0.0062 0.5786

To the best of the authors' knowledge, such a recommendation to calculate the COP as a function of the cooling water temperature, for the minimum hot temperature to maintain a reasonable degassing zone, is not available in the literature.

Coefficient of performance for the electric refrigeration plant

The coefficient of performance (COP) of the electric refrigeration plant, representing the ratio between the cooling power and the electrical power consumed for compression, depends on the operating conditions represented by the temperatures of the two heat sources (the inside temperature of the cold food storage spaces and the cooling water temperature). Like in the case of the absorption refrigeration plant, in both refrigeration and freezing operating regimes, the inside temperatures of the cold food storage spaces were considered constant (3 °C for the RC and RS and −20 °C for the FC and FS). Under these circumstances it can be concluded that the COP depends only on the cooling water temperature, for each inside temperature. COP was calculated for a classical mechanical compression cycle with NH3 as refrigerant.

Fig. 9 presents the COP variation with the cooling water temperature for refrigeration and freezing operating regimes, respectively.

Fig. 9.

Fig 9

COP variation with the cooling water temperature for refrigeration and freezing.

The values of the COP are higher when the refrigeration plant operates in the refrigeration regime in comparison to the freezing regime.

The correlation between the COP and the cooling water temperature, for NH3 as refrigerant was determined as:

COP=e·tw2+f·tw+g (33)

with the values of the coefficients e, f and g presented in Table 7.

Table 7.

Values of the coefficients e, f and g (eq. (33)).

Regime e f g
Refrigeration (t0 = −10 °C) 0.0034 −0.2724 8.3136
Freezing (t0 = −30 °C) 0.0009 −0.0863 3.9280

The presented correlation with the calculated coefficients was used to determine the COP of the backup mechanical refrigerating plant, needed to be used when solar heat is not available or is insufficient.

The mathematical model characterizes the thermal behaviour of all the investigated solar cooling system components: the cold food storage spaces (RC, RS, FC, FS), the food product itself (chicken meat), the parabolic trough collectors, the cooling tower, the main absorption refrigeration system and the backup mechanical refrigeration system.

The different parts of the proposed mathematical model were implemented in Engineering Equation Solver (EES) and in Microsoft Excel.

Discussion and conclusions

The study presents the methodology for the analytical investigation of the food storage cooling with solar ammonia-water absorption system, powered by SPTC. To the best of the authors' knowledge, the study is investigating the following novel aspects:

  • - Food cooling with solar absorption refrigeration system.

  • - Hourly based modelling of food cooling load variation.

  • - Hourly based variation of NH3—H2O solar absorption system performances.

  • - Long term simulation of solar absorption cooling for refrigeration and cooling.

The thermal behaviour of four types of food storages: RC, RS, FC and FS and of the heat storage tank was investigated.

The results of the methodology application are going to be presented in a distinct study.

Declaration of Competing Interest

The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.

Acknowledgement

This study was partially supported by the Project “Entrepreneurial competences and excellence research in doctoral and postdoctoral programs – ANTREDOC no. 56437/24.07.2019”, project co-funded by the European Social Fund.

This study was partially financially supported by the Project “Network of excellence in applied research and innovation for doctoral and postdoctoral programs / InoHubDoc”, project co-funded by the European Social Fund financing agreement no. POCU/993/6/13/153437.

This study was partially supported by a grant of the Ministry of Research, Innovation and Digitization, CCCDI - UEFISCDI, project number PN-III-P2-2.1-PED-2021-0544, within PNCDI III (PED 706).

Data availability

  • Data will be made available on request.

References

  • 1.Ayadi O., Aprile M., Motta M. Solar cooling systems utilizing concentrating solar collectors - an overview. Energy Proc. 2012;30:875–883. [Google Scholar]
  • 2.Alvarez S.G., Trepp C. Simulation of a solar driven aqua-ammonia absorption refrigeration system Part 1: mathematical description and system optimization. Int. J. Refrig. 1986;10:40–48. [Google Scholar]
  • 3.Alvares S.G., Trepp C. Simulation of a solar driven aqua-ammonia absorption refrigeration system Part 2: viability for milk cooling at remote Brazilian dairy farms. Int. J. Refrig. 1987;10:70–76. [Google Scholar]
  • 4.Bulgan A.T. Optimization of the thermodynamic model of aqua-ammonia absorption refrigeration systems. Energy Convers. Manag. 1994;36:135–143. [Google Scholar]
  • 5.Cabrera F.J., Fernández-García A., Silva R.M.P., Pérez-García M. Use of parabolic trough solar collectors for solar refrigeration and air-conditioning applications. Renew. Sustain. Energy Rev. 2013;20:103–118. [Google Scholar]
  • 6.Davey, L., Pham, Q.T., 1996. A technique for measuring product heat load during beef chilling.
  • 7.Dai E., Jia T., Dai Y. Theoretical and experimental investigation on a GAX-Based NH3-H2O absorption heat pump driven by parabolic trough solar collector. Sol. Energy. 2020;197:498–510. [Google Scholar]
  • 8.Sun D.W. Comparison of the performances of NH3-H2O, NH3-LiNO3 and NH3-NaSCN absorption refrigeration systems. Energy Convers. Manag. 1998;39:357–368. [Google Scholar]
  • 9.Dincer I. John Wiley & Sons, Ltd.; Chichester: 2003. Refrigeration Systems and Applications. [Google Scholar]
  • 10.Döll J., Bentaher H., Morgenstern A. First results of a pilot installation of a solar thermally driven cold store. Int. J. Refrig. 2014;39:77–85. [Google Scholar]
  • 11.Du S., Wang R.Z. A unified single stage ammonia-water absorption system configuration with producing best thermal efficiencies for freezing, air-conditioning and space heating applications. Energy. 2019;174:1039–1048. [Google Scholar]
  • 12.Duffie J., Beckman W.A. 4th ed. John Wiley & Sons; New Jersey: 2013. Solar Engineering of Thermal Processes. [Google Scholar]
  • 13.El-Shaarawi M.A.I., Said S.A.M., Siddiqui F.R. Unsteady thermodynamic analysis for a solar driven dual storage absorption refrigeration cycle in Saudi Arabia. Sol. Energy. 2014;110:286–302. [Google Scholar]
  • 14.El-Shaarawi M.A.I., Al-Nimr M.A. Equations for use with computers to evaluate the performance of NH3-H2O intermittent solar refrigerators. Energy Convers. Manag. 1990;30:315–327. [Google Scholar]
  • 15.Fadar A.El, Mimet A., Pérez-García M. Modelling and performance study of a continuous adsorption refrigeration system driven by parabolic trough solar collector. Sol. Energy. 2009;83:850–861. [Google Scholar]
  • 16.Ghorbani B., Mehrpooya M. Concentrated solar energy system and cold thermal energy storage (process development and energy analysis) Sustain. Energy Technol. Assess. 2020;37 [Google Scholar]
  • 17.Huld T. PVMAPS: software tools and data for the estimation of solar radiation and photovoltaic module performance over large geographical areas. Sol. Energy. 2017;142:171–181. [Google Scholar]
  • 18.Manrique J.A. Thermal performance of an ammonia-water refrigeration system. Int. Commun. Heat Mass Transf. 1991;18:779–789. [Google Scholar]
  • 19.Mehrpooya M., Ghorbani B., Hosseini S.S. Thermodynamic and economic evaluation of a novel concentrated solar power system integrated with absorption refrigeration and desalination cycles. Energy Convers. Manag. 2018;175:337–356. [Google Scholar]
  • 20.Pop O.G., Magurean A.M., Pocola A.G., Ciocan M., Zaaoumi A., Balan M.C. In: Environmental and Human Impact of Buildings. Springer Tracts in Civil Engineering. Moga L., Șoimoșan T.M., editors. Springer; Cham: 2021. Performances of solar thermal collectors in different climatic conditions. [Google Scholar]
  • 21.Shirazi A., Taylor R.A., Morrison G.L., White S.D. Solar-powered absorption chillers: a comprehensive and critical review. Energy Convers. Manag. 2018;171:59–81. [Google Scholar]
  • 22.Syed A., Izquierdo M., Rodriguez P., Maidment G., Missenden J. A novel experimental investigation of a solar cooling system in Madrid. Int. J. Refrig. 2005;28:859–871. [Google Scholar]
  • 23.Stanford H.W., III . 2nd ed. Taylor & Francis; Boca Raton: 2003. HVAC Water Chillers and Cooling Towers. Fundamentals, Application, and Operation. [Google Scholar]
  • 24.Stull R. Wet-Bulb temperature from relative humidity and air temperature. J. Appl. Meteorol. Climatol. 2011;50:2267–2269. [Google Scholar]
  • 25.Tierney M.J. Options for solar-assisted refrigeration-Trough collectors and double-effect chillers. Renew. Energy. 2007;32:183–199. [Google Scholar]
  • 26.Tillner-Roth R., Friend D.G. A Helmholtz free energy formulation of the thermodynamic properties of the mixture {Water + Ammonia} J. Phys. Chem. Ref. Data. 1998;27:63. [Google Scholar]
  • 27.Weber C., Berger M., Mehling F., Heinrich A., Núñez T. Solar cooling with water–ammonia absorption chillers and concentrating solar collector - operational experience. Int. J. Refrig. 2014;39:57–76. [Google Scholar]
  • 28.Xu F., Goswami D.Y. Thermodynamic properties of ammonia–water mixtures for power-cycle applications. Energy. 1999;24:525–536. [Google Scholar]
  • 29.Zaaoumi A., Bah A., Ciocan M., Sebastian P., Balan M.C., Mechaqrane A., Alaoui M. Estimation of the energy production of a parabolic trough solar thermal power plant using analytical and artificial neural networks models. Renew. Energy. 2021;170:620–638. [Google Scholar]
  • 30.Ziegler B., Trepp C. Equation of state for ammonia-water mixtures. Int. J. Refrig. 1984;7:101–106. [Google Scholar]
  • 31.Zheng X., Shi R., Wang Y., You S., Zhang H., Xia J., Wei S. Mathematical modeling and performance analysis of an integrated solar heating and cooling system driven by parabolic trough collector and double-effect absorption chiller. Energy Build. 2019;202 [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Data Availability Statement

  • Data will be made available on request.


Articles from MethodsX are provided here courtesy of Elsevier

RESOURCES