Skip to main content
The Journal of Hygiene logoLink to The Journal of Hygiene
. 1976 Feb;76(1):1–10. doi: 10.1017/s0022172400054887

Bacteriological evaluation of a mobile laminar cross-flow unit for surgery, under laboratory circumstances.

D van der Waaij, N Wiegersma, J Dankert
PMCID: PMC2129597  PMID: 1107410

Abstract

A mobile laminar cross-flow unit for surgery has been evaluated by the use of an experimental bacterial aerosol of Escherichia coli in different concentrations, generated at several different sites. A separate ventilation system, mounted underneath the table, produced an almost downward directed curtain of sterile air along both sides of the table. When the velocity of the air stream, discharged by the cross-flow unit, was adjusted at 0-50 m./sec. at 2 m. from the filter face (at the head end of the operation table), the surface of the table could be maintained free of bacterial settling even after aerosolization of heavily concentrated suspensions of 10(8) bacteria/ml. at different sites outside the enclosure and underneath the table as well.

Full text

PDF
1

Selected References

These references are in PubMed. This may not be the complete list of references from this article.

  1. BERNARD H. R., SPEERS R., Jr, O'GRADY F., SHOOTER R. A. REDUCTION OF DISSEMINATION OF SKIN BACTERIA BY MODIFICATION OF OPERATING-ROOM CLOTHING AND BY ULTRAVIOLET IRRADIATION. Lancet. 1965 Sep 4;2(7410):458–461. doi: 10.1016/s0140-6736(65)91421-2. [DOI] [PubMed] [Google Scholar]
  2. Foord N., Lidwell O. M. The control by ventilation of airborne bacterial transfer between hospital patients, and its assessment by means of a particle tracer. I. An airborne-particle tracer for cross-infection studies. J Hyg (Lond) 1972 Jun;70(2):279–286. doi: 10.1017/s0022172400022336. [DOI] [PMC free article] [PubMed] [Google Scholar]
  3. Hambraeus A. Transfer of Staphylococcus aureus via nurses' uniforms. J Hyg (Lond) 1973 Dec;71(4):799–814. doi: 10.1017/s0022172400023068. [DOI] [PMC free article] [PubMed] [Google Scholar]
  4. LIDWELL O. M. The evaluation of ventilation. J Hyg (Lond) 1960 Sep;58:297–305. doi: 10.1017/s0022172400038419. [DOI] [PMC free article] [PubMed] [Google Scholar]
  5. Lewis H. E., Foster A. R., Mullan B. J., Cox R. N., Clark R. P. Aerodynamics of the human microenvironment. Lancet. 1969 Jun 28;1(7609):1273–1277. doi: 10.1016/s0140-6736(69)92220-x. [DOI] [PubMed] [Google Scholar]
  6. Whyte W. Bacteriological aspects of air-conditioning plants. J Hyg (Lond) 1968 Dec;66(4):567–584. doi: 10.1017/s002217240002831x. [DOI] [PMC free article] [PubMed] [Google Scholar]
  7. van der Waaij D., Heidt P. J., Hendriks W. D. Bacteriological evaluation of a laminar cross-flow tunnel for surgery under operational conditions. J Hyg (Lond) 1974 Apr;72(2):145–153. doi: 10.1017/s0022172400023330. [DOI] [PMC free article] [PubMed] [Google Scholar]

Articles from The Journal of Hygiene are provided here courtesy of Cambridge University Press

RESOURCES