Skip to main content
Scientific Reports logoLink to Scientific Reports
. 2025 Nov 25;15:45296. doi: 10.1038/s41598-025-28882-x

Design and operational challenges of renewable-powered isolated microgrids: a zero-carbon approach

Wender M Figueredo 1, Osvaldo R Saavedra 1,2,, Pedro B Leite Neto 1, Denisson Q Oliveira 1
PMCID: PMC12749607  PMID: 41291048

Abstract

This article investigates the characteristics, operation and challenges of zero carbon microgrids, including size, generation from renewable sources, energy balance, and costs. An isolated zero-carbon microgrid is powered exclusively by renewable energy sources. It utilizes energy storage technologies, such as long-duration batteries or hydrogen storage, to mitigate intermittency and ensure a reliable power supply, allowing it to meet demand even under conditions of low production or high variability. The temporal variability between generation and load has technical and economic implications for microgrid sizing. This mismatch can be mitigated by combining renewable sources with diverse intermittency profiles, affecting both the storage system and the size of the generating units to be installed. This article formulates the sizing problem of an isolated microgrid designed to meet all load requirements solely through renewable sources and storage. The implications of this objective are analyzed and discussed, and sensitivity analysis studies are conducted to explore potential load shedding agreements and their impact on the solution. Solar, wind, and tidal energy exhibit a good degree of complementarity and help reduce storage requirements. However, the high cost of storage makes the oversizing of renewable sources even more attractive to ensure 100% load supply. On the other side, it was observed that allowing a load shedding of only 2.5% results in an approximate 46% reduction in the total system cost. Although the studies are carried out on a small microgrid, the conclusions can be expanded to systems of any size.

Keywords: Renewable energy, Standalone microgrid, Zero carbon, Hybrid renewable resource, Multiple storage technologies

Subject terms: Engineering, Electrical and electronic engineering, Renewable energy, Hydrogen energy, Solar energy, Wind energy

Introduction

Intelligent microgrids represent the cornerstone of modern electrical systems, leading the way in the search for reliability, resilience, and cost reduction. Global demands for decarbonizing the economy have recently highlighted another important benefit of microgrids: zero emissions. Microgrids must rely solely on clean energy sources to meet their energy needs while maintaining performance standards. The technological implications for these challenges are significant and, although there are technologies capable of meeting these requirements, they are still maturing, especially in the efficient integration of various renewable energy sources and storage1.

A zero-carbon intelligent microgrid exemplifies our vision of a sustainable global electrical system. Recent studies have highlighted the opportunities and challenges of operating microgrids powered exclusively by renewable energy sources. These studies collectively focus on the feasibility, energy management, control strategies, and techno-economic aspects of achieving 100% renewable microgrids, especially in isolated or mission-critical contexts.

Rousan et al.2 discuss the design and operation of a 1 MW islanded microgrid, focusing on managing excess renewable generation through energy storage and generation curtailment strategies. They used a grid-forming battery energy storage inverter to balance load and generation, demonstrating the technical feasibility of operating with 100% renewable capacity while ensuring stability and reliability. Campagna et al.3 emphasize the challenges related to the green transition towards 100% renewable energy sources, addressing technical, economic, and policy aspects. They highlight the need for technological innovations, government policies, and social acceptance to address these challenges effectively. The authors also point out that achieving a complete transition involves overcoming traditional system limitations and adapting to innovative paradigms that include renewable energy sources and smart inverters.

In4, Bastos and Trevisan investigated the feasibility of microgrids for powering remote communities with renewable sources. Using an island on the coast of Maine as a case study, they analyzed the optimal sizing of solar PV and battery energy storage systems. Their results show that the island can primarily be powered by renewable sources, utilizing a 400 kW PV system and a 2 MWh battery energy storage system, thereby reducing dependence on backup diesel generators. In5 and6, Li et al. studied hydrogen-based storage systems for renewable microgrids. They proposed a model that includes hydrogen tanks, electrolyzers, and batteries to create a power station capable of supplying energy to microgrid clusters, such as residential and industrial areas. The study emphasized the significance of hydrogen in meeting long-term energy storage needs, thereby ensuring a reliable power supply during periods when solar or wind energy resources are unavailable.

In7, Abdelsalam et al. proposed an energy management system for a hybrid AC/DC microgrid consisting of PV, wind, diesel, and hydrogen storage systems. The study included a sensitivity analysis to optimize the installed capacity of each renewable resource, aiming to minimize the levelized cost of electricity and carbon emissions. Their findings showed that hydrogen storage and a balanced mix of renewable sources could reduce reliance on diesel by approximately 72.44%, enhancing environmental sustainability. Wang8 analyzed the impact of different inverter control strategies-grid-following (GFL) and grid-forming (GFM)-on microgrid stability. The study demonstrated that mixed use of synchronous generators with GFL and GFM inverters could achieve better transient and steady-state stability, paving the way for reliable 100% renewable systems. Harasis9 also investigated DG connected through GFM and GFL inverters in islanded inverter-based microgrids. The author proposed a dynamic droop control to flexibly shape the transient power of microgrid’s DGs. A small-signal verification model of a microgrid under the proposed control has also been performed. Harasis et al.10 demonstrated the tradeoff between the operating cost and the reliability in microgrid operation. Although the authors deployed flexible control algorithms to optimize the power flow between different energy sources using the particle swarm algorithm, the results showed that the presence of dispatchable sources fueled by fossil fuels is a standard solution to avoid oversizing renewable and energy storage plants. Such a sizing approach decreases initial investments in generation and storage, impacting reliability indices, but it is not aligned with zero-carbon policies.

Daneshvar et al.11 proposed a transactive energy solution for managing 100% renewable multi-microgrids integrated with gas grids. Using stochastic optimization, the authors introduced a fair and risk-averse model that minimized economic risks while ensuring energy reliability. Their results showed that such integrated systems could effectively manage the uncertainties associated with renewable energy production. In12, Li et al. developed an optimal method for planning and operating a dual net-zero emissions islanded microgrid. Their results indicate that the proposed method reduces planning costs by 25% compared to other methods. Shen et al.13 propose a technical solution for planning a net-zero microgrid based on hydrogen storage in renewable-rich remote areas. Their main finding is the viable pathway to decarbonize microgrids using hydrogen storage technology. Wang et al.14 have presented an economic sizing of a renewable off-grid system using hydrogen storage, wind, solar, and bio-waste sources. Stochastic optimization is employed to represent the uncertainties associated with load, renewable resources, and electric vehicle recharge, and the Red Panda Optimization approach is employed to obtain a reliable optimal solution. The findings demonstrate the acceptable performance of the strategy in boosting the economic status of the island system. Naghibi et al.15 have developed an approach to allocating and sizing a renewable integrated energy system that incorporates power-to-hydrogen (P2H) and hydrogen-to-power (H2P) technologies within an active distribution network, considering wind, solar, and bio-waste resources, as well as hydrogen storage. The results show an improvement in network operation, reducing voltage drops, and increasing the maximum load capacity.

Shahzad et al.16 conduct a techno-economic analysis of green hydrogen integration in smart grids, evaluating the impacts of the efficiency and costs of electrolysis technologies, including PEM and alkaline systems. The results show that although green hydrogen reduces carbon emissions and enhances grid flexibility, the infrastructure and cost challenges remain, demanding policy support through incentives to make its adoption viable.

Recent literature highlights a growing effort to move towards power systems that are less dependent on fossil fuels and progressively closer to net-zero emissions. In this context, microgrids emerge not merely as a conceptual trend, but as practical testbeds and scalable solutions for decarbonization. By enabling the coordinated use of diverse renewable sources, storage technologies, and local control strategies, microgrids contribute to reshaping the energy mix, increasing system resilience, and reducing greenhouse gas emissions in a measurable way.

Research gaps

Table 1 summarizes the main highlights of the literature reviewed in this work. The diversity of the studies analyzed reflects a significant research interest in grid decarbonization, with microgrids playing a central role in this process. Renewable energy sources (RES) such as photovoltaic (PV), wind, and waste-to-energy systems are commonly considered, as are storage technologies like batteries and hydrogen. However, there is a noticeable lack of specific studies that include ocean-based renewable sources, such as tidal energy, and that examine how different types of intermittency affect the formation of hybrid renewable generation clusters. Furthermore, there is a shortage of in-depth discussions and analyses regarding the cost of achieving 100% renewable generation and its implications under varying scales of intermittency of primary energy sources.

Table 1.

Bibliographic review summary.

Reference No. of RES types Islanded operation 100% renewable Battery storage H2V storage Comments
2 2 Yes Yes Yes No

This paper evaluates the islanded operation of a microgrid comprised

of wind, solar, and battery power. The analysis is

conducted over a 24-hour horizon.

3 2 No Yes Yes No

The objective is to assess the main challenges for 100% emissions-free

microgrids. The article does not propose new methods

for sizing or analyzing microgrid operations.

4 1 Yes No Yes No

The objective is to evaluate the feasibility of an isolated microgrid

being 100% served by PV and BESS sources, minimizing

the use of a diesel generator.

5 1 No Yes Yes Yes

The study considers one type of generation source.

The focus is on meeting 100% of demand, and does not include a sensitivity

analysis regarding the cost of reliability.

6 1 No Yes Yes Yes

The objective is to build a zero carbon microgrid using

multi-objective optimization to minimize total cost,

exchanged energy and maximize installed renewable energy.

7 2 No No No Yes

The study proposes a sizing method based on sensitivity analysis involving

LCOE, discount rate and fuel price increase rate, however, it does not present

a sensitivity analysis between costs and pre-defined reliability criteria.

8 1 No Yes Yes No

This paper proposes an analysis of a microgrid with different renewable

generation penetration rates, focusing on the stability and control strategies

of electronic converters. Economic and load-supply reliability analyses are

beyond the scope of this work.

9 1 Yes Yes No No

This paper proposes a control strategy for a microgrid with multiple distributed

sources. The focus is on transient analysis in microgrids consisting of GFM

and GFL inverters. A planning (sizing) study focusing on economic and

reliability assessment is beyond the scope of this paper.

10 1 Yes No Yes No

The objective is to optimize a set of operational parameters, considering the

tradeoff between operating costs and microgrid reliability. The methodology

does not include the analysis of multiple sources or hybrid storage systems,

nor does it include sensitivity analysis between the total costs and different

predefined levels of reliability.

11 No Yes Yes Yes

The objective is to optimize power flow between microgrid components

and propose a dynamic operating scheme for the storage system.

It uses a numerical index to quantify microgrid reliability.

However, the focus does not include assessing the cost of reliability

in serving the load.

12 3 Yes Yes No Yes

The objective is to optimize the operation of an isolated microgrid with

multiple sources and hydrogen. The approach includes a technical and

economic analysis of the microgrid’s operation. The work consists of an

economic feasibility analysis based on the prices of the microgrid components.

However, it does not include an assessment of economic feasibility based on

the reliability of meeting demand.

13 2 Yes Yes Yes Yes

This paper proposes a technical-economic analysis of a microgrid with two

renewable sources and a hybrid storage system. It also proposes an economic

sensitivity analysis based on the expected cost reductions of the main microgrid

components, without considering different load-supply reliability criteria.

14 3 Yes Yes No Yes

It proposes the use of stochastic optimization to design an off-grid microgrid

with multiple sources, hydrogen, and electric vehicles. The methodology does

not include a cost analysis of load-servicing reliability.

15 3 No Yes No Yes

This paper proposes a strategy for planning a system with multiple renewable

generation sources and hydrogen storage. The objective is to reduce the

installation and maintenance costs of the integrated system. Economic analyses

of the cost of reliability are beyond the scope of this work.

16 2 No No No Yes

The objective of the study is to evaluate the integration of green hydrogen into

smart grids. The work does not address integration with other storage technologies,

such as BESS, or the integration of these resources into isolated zero-carbon microgrids.

Contributions

In this paper, the authors address the sizing problem of an isolated zero-emission microgrid supplied by renewable sources such as photovoltaic, wind, and tidal power. The temporal mismatch in generation caused by the distinct intermittency patterns of the three renewable sources is investigated. The proposed microgrid includes a hydrogen facility to evaluate the potential for mitigating the temporal mismatch between the installed renewable sources and to analyze its impact on consistent performance in meeting the full annual load demand. This article considers isolated operation as it represents the most severe operational case for a microgrid. The motivation is to illustrate, through a small-scale model, the relevant challenges and viable solutions for the energy transition, with conclusions that can be generalized to any future renewable-based system. The problem is formulated as a multi-objective optimization, in which sensitivity analyses of its components are performed to identify their impacts and contributions to autonomous microgrid operation.

By evaluating critical aspects of zero-carbon microgrids, simulating their operation to draw relevant conclusions about their sizing, temporal variability in generating renewable sources, energy balance, and cost projections, it is possible to address the challenges of managing a microgrid with intermittent and distributed energy sources, highlighting the need for innovation in energy storage technologies and forecasting methods to improve energy generation and distribution.

The focus of this paper is on exploring the interaction among renewable sources with diverse intermittency patterns, which collectively contribute to an integrated energy resource capable of fully meeting demand with the support of multiple storage technologies, as illustrated in Fig. 1.

Fig. 1.

Fig. 1

Graphical abstract: Key concepts in designing and operating zero-carbon isolated microgrids.

To address the gaps identified in Section “Research gaps”, this work introduces a sizing framework that distinguishes itself from previous studies in three key aspects: (1) it incorporates not only sources with well-known synergy (wind and solar) but also a less common, highly predictable source (tidal energy); (2) rather than targeting a predefined reliability level (typically 100%) as most studies do, this work identifies and evaluates the practical implications of the trade-off between cost and reliability; (3) it co-optimizes both short-term (BESS) and long-term seasonal (GH2) storage systems to balance this specific mix of generation sources.

The contributions of this article are as follows: a) It has been demonstrated that the autonomous operation of microgrids solely with renewable sources is feasible; b) The critical role of both short- and long-term storage in enabling autonomous microgrid operation has been established; c) The results demonstrated that uninterrupted zero-carbon operation is costly and requires a high rate of curtailed energy; consequently, small load sheddings can significantly decrease both spilled energy and the required size of generation assets; d) The mix of renewable sources has a beneficial impact on microgrid sizing and storage requirements. The article also illustrates the concept of zero-carbon microgrids as building blocks for the energy transition, enabling the development of scalable multi-microgrid compositions for the grids of the future.

The article is organized as follows. In Section “Zero-carbon microgrid”, the concept of a zero-carbon microgrid is introduced and thoroughly explained. Section “Problem formulation” formulates the microgrid sizing problem. Subsequently, the key components of the microgrid, including renewable energy sources and storage systems, are modeled in detail. In Section “Microgrid components”, the cost expressions associated with the microgrid’s operation and infrastructure are elaborated. Finally, the last three sections present a case study, followed by simulations that validate the approach. The discussion section interprets the results, highlighting key insights and implications, while the final section draws conclusions.

Zero-carbon microgrid

Typically, microgrids incorporate a high penetration of renewable energy sources, positioning them as a key component in the decarbonization of the electricity sector. However, the use of dispatchable sources, such as diesel generators, remains a common strategy to compensate for the inherent variability of renewable sources. Although this configuration is a well-established paradigm, it results in carbon emissions during the microgrid’s operation. In this context, a new paradigm is emerging: the zero-carbon microgrid (NZM), a system designed to operate with zero or near-zero carbon emissions. Figure 2 illustrates the concept of an NZM.

Fig. 2.

Fig. 2

Zero-carbon microgrid. Source Elaborated by the authors.

According to17, the main characteristic of an NZM is the limitation of carbon-emitting sources. To meet this condition, advanced control strategies over generation sources are required, in addition to greater dependence on energy storage systems. Furthermore, an NZM can be designed to achieve a net-zero emission balance by offsetting any emissions produced during its operation through the use of its renewable resources.

An isolated NZM, also referred to as a dual-zero microgrid (DZM), is an off-grid microgrid whose operation results in zero carbon emissions and does not exchange electrical power with an external conventional grid18. In this context, planning and operating a DZM become more challenging. To meet a predefined reliability target, the absence of an external grid and fossil-fuel-based sources necessitates a greater dependence on existing renewable sources and storage systems.

According to19, current developments for NZMs follow three trends: 1 – high penetration of renewable sources, where the large-scale integration of renewable sources compensates the displacement of fossil fuel-based sources; 2 – extensive deployment of storage systems to compensate for the high variability of renewable sources; 3 – higher number of power electronic devices, since both renewable sources and storage systems typically use electronic converters, this directly affects the stability and control of the microgrid.

In this context, different approaches have been proposed to support the implementation of an NZM, such as storage systems20, carbon capture18, optimization of the integration between renewable sources and the control strategy21, and demand response22.

These approaches demonstrate the technical and economic feasibility of NZMs; however, the relationship between total costs and reliability still requires further investigation. More specifically, the potential for drastically reducing total costs by introducing controlled flexibility in reliability and allowing a predefined small level of load shedding is an aspect that requires further investigation. Therefore, this article presents a sizing methodology to quantify the relationship between these costs and the system reliability, quantified by the Probability of Loss of Supply (LPSP), in a DZM formed of solar, wind, and tidal sources, as well as hybrid battery and hydrogen storage.

Problem formulation

The problem aims to determine the optimal sizing of wind and tidal turbines, photovoltaic (PV) panels, as well as the capacity of the BESS (short-term storage) and the hydrogen generation plant (medium/long-term storage), including the fuel cell and converter for the deferred return of this energy as electricity. The formulation consists of a multi-objective nonlinear optimization problem with constraints, as described below.

Objective function

Equation (1) defines the multi-objective function, which aims to minimize both the total cost and the total spilled energy:

graphic file with name d33e749.gif 1

Where the terms Inline graphic and Inline graphic are described in detail in the following sections, while Inline graphic denotes the vector of decision variables, as defined in Table 2.

Table 2.

Control variables.

Parameter Description
Inline graphic Number of PV Panels (units)
Inline graphic Number of Wind Turbines (units)
Inline graphic Number of Tidal Turbines (units)
Inline graphic BESS Capacity (kWh)
Inline graphic GH2 Plant Capacity (kWh)

Source: Elaborated by the authors

The total cost of the standalone zero-carbon microgrid is given by Eq. (2). The total cost consists of the installation, replacement, operation, and maintenance costs of all microgrid equipment.

graphic file with name d33e775.gif 2

Where, Inline graphic: Total cost of the system ($); Inline graphic: Total installation cost ($); Inline graphic: Total O&M cost ($) and Inline graphic: Total replacement cost ($).

The total spilled energy (kWh) is given by Eq. (3):

graphic file with name d33e802.gif 3
graphic file with name d33e806.gif 4

Where: Inline graphic: Total spilled energy (kWh); Inline graphic: Spilled power at instant Inline graphic (kW); Inline graphic: Time interval; Inline graphic: Total simulation time and Inline graphic: Operation time instant.

Control variables

The control variables of the problem are described in Table 2. These include parameters related to the number of photovoltaic panels (PV), wind turbines, and tidal turbines, as well as the capacities of the BESS and the GH2 plant.

The capacities in kW of each unit are specified in the case study. This approach avoids dependence, in the problem formulation, on the unit sizes currently offered by the market for each generation technology.

Problem constraints

The optimization problem is subject to the following constraints, detailed below:

Power balance

The power balance must be satisfied at every operational instant of the microgrid. Equation (5) represents the power balance equation at time Inline graphic:

graphic file with name d33e920.gif 5

Where: Inline graphic: Power demand from the load (kW); Inline graphic: Power used to charge the BESS (kW); Inline graphic: Power consumed by the GH2 electrolyzer (kW); Inline graphic: Total power generated by renewable sources (kW); Inline graphic: Power discharged from the BESS (kW); Inline graphic: Power supplied by the GH2 fuel cell (kW); Inline graphic: Power loss due to load shedding (kW).

Renewable generation system constraints

The constraints related to the capacities of PV panels (Inline graphic), wind turbines (Inline graphic), and tidal turbines (Inline graphic) are expressed by Eqs. (6), (7), and (8), respectively:

graphic file with name d33e980.gif 6
graphic file with name d33e984.gif 7
graphic file with name d33e988.gif 8

The maximum limits for these renewable sources are defined by the nominal capacity of each source to meet the total load demand alone. The minimum limits are determined based on the minimum operational capacity, corresponding to installing at least one equipment unit for each renewable source.

BESS model and constraints

The BESS is an energy storage system composed of batteries. In this study, lithium-ion batteries are used. It is important to note that a lithium battery has an average lifespan of approximately 8 to 15 years, depending on the depth of charge used23. The nominal storage capacity of the BESS can be calculated using Eq. (9):

graphic file with name d33e1004.gif 9

Where: Inline graphic: Nominal storage capacity of the BESS (kWh); Inline graphic: Nominal capacity of a single battery (Ah); Inline graphic: Nominal voltage of the battery (V); Inline graphic: Number of batteries connected in series (units) and Inline graphic: Number of batteries connected in parallel (units).

The power of the BESS at time Inline graphic is given by Eq. (10).

graphic file with name d33e1039.gif 10

Where: Inline graphic: Power of the BESS at time Inline graphic (kW); Inline graphic: Input power to the BESS, charging (kW); Inline graphic: Charging efficiency of the BESS (Inline graphic); Inline graphic: Output power from the BESS, discharging (kW) and Inline graphic: Discharging efficiency of the BESS (Inline graphic).

The C-rate is the charge and discharge rate of a battery. For lithium-ion batteries, a 1C C-rate is commonly used, meaning the full charge or discharge is performed within 1 hour at maximum current. The maximum instantaneous charge and discharge power of the BESS are represented by Eqs. (11) and (12), respectively.

graphic file with name d33e1085.gif 11
graphic file with name d33e1089.gif 12

Where: Inline graphic: Charging rate of the BESS and Inline graphic: Discharging rate of the BESS.

The SOC represents the state of charge of the BESS, and it is calculated using Eq. (13).

graphic file with name d33e1107.gif 13

Where: Inline graphic: SOC (Inline graphic); Inline graphic: Initial state of charge of the battery (Inline graphic); Inline graphic: Amount of charge supplied to or withdrawn from the battery during its operation (Inline graphic) and Inline graphic: Maximum charge the battery can store (Inline graphic).

Equation (14) represents the Inline graphic, which is the ratio between the current SOC and the maximum SOC of the BESS.

graphic file with name d33e1154.gif 14

The SOC update equation is given by:

graphic file with name d33e1159.gif 15

The maximum capacity Inline graphic and Inline graphic (maximum state of charge) are not necessarily the same. The maximum capacity of a BESS refers to the total amount of energy the system can store, as specified by the manufacturer (nameplate data). On the other hand, SOC is a metric that indicates the current charge level of the battery as a percentage of its total maximum capacity. The maximum SOC may differ from the maximum capacity due to operational restrictions, safety measures, or even battery aging. For our case, for simplicity, we will consider that the sized capacity of the BESS coincides with the maximum Inline graphic, that is:

graphic file with name d33e1177.gif 16

Thus, in the operation of the microgrid, the SOC must satisfy the following constraint.

graphic file with name d33e1182.gif 17

The power limit of the BESS is represented in Eq. (18).

graphic file with name d33e1190.gif 18

Equations (19) and (20) represent the maximum charge and discharge power of the BESS, respectively.

graphic file with name d33e1202.gif 19
graphic file with name d33e1206.gif 20

Where: Inline graphic: BESS charge C-rate, and Inline graphic: BESS discharge C-rate.

Equations (21) and (22) express the maximum and minimum limits of the BESS’s charging and discharging power.

graphic file with name d33e1227.gif 21
graphic file with name d33e1231.gif 22

The nominal capacity of the BESS is defined according to Eq. (23).

graphic file with name d33e1239.gif 23

GH2 model and constraints

Energy storage in the form of GH2 involves three main components: the electrolyzer, responsible for converting surplus energy into green hydrogen; the GH2 storage tank; and the fuel cell, responsible for converting the stored green hydrogen back into electrical energy. Considering this complete cycle, the system can be viewed as a large battery and, therefore, has associated parameters.

Equation (24) represents the instantaneous net power of the GH2 system. It accounts for the power consumption of the electrolyzer and the power injected back by the fuel cell, including their respective efficiency values.

graphic file with name d33e1252.gif 24

Where, Inline graphic: Power of the GH2 system (Inline graphic); Inline graphic: Input power to the electrolyzer (Inline graphic); Inline graphic: Efficiency of the electrolyzer (Inline graphic); Inline graphic: Output power of the fuel cell (Inline graphic); and Inline graphic: Efficiency of the fuel cell (Inline graphic).

Similar to the BESS, we can also define the state of charge (SOC) for the GH2 system. Equation (25) represents the Inline graphic:

graphic file with name d33e1308.gif 25

The SOC update equation for the GH2 system is given by Eq. (26).

graphic file with name d33e1316.gif 26

Where, Inline graphic: SOC of the GH2 system at time Inline graphic (Inline graphic) and Inline graphic: SOC of the GH2 system at the previous time step Inline graphic (Inline graphic).

The storage capacity Inline graphic of GH2 is determined by the optimization process, which establishes a balance between the expected curtailment of renewable energy sources and the plant size. In the absence of operational or safety constraints, the value of Inline graphic can reach the maximum capacity Inline graphic, as follows.

graphic file with name d33e1360.gif 27

In the operation of the microgrid, the constraint must be taken into account:

graphic file with name d33e1365.gif 28

In terms of power, the constraint is as follows:

graphic file with name d33e1371.gif 29

The electrolyzer is designed for maximum efficiency, sized to match the maximum load demand, as shown in Eq. (30). This means that even if the microgrid’s consumption is zero at any given time, the electrolyzer can efficiently redirect the unused energy to generate GH2 accordingly. The power limits of the electrolyzer during operational simulation are defined by Eq. (31), ensuring its efficient operation.

graphic file with name d33e1382.gif 30
graphic file with name d33e1386.gif 31

The nominal power of the fuel cell can be determined in a manner similar to the previous case, that is, requiring that the maximum peak of the load demand can be met solely by it, as stated in Eq. (32).

graphic file with name d33e1395.gif 32

The power limits of the fuel cell for the simulation of the operation are defined by Eq. (33).

graphic file with name d33e1403.gif 33

The nominal capacity of the BESS is defined according to Eq. (34).

graphic file with name d33e1411.gif 34

Loss of power supply probability (LPSP)

This is a key reliability metric used in the energy and power sectors to evaluate the likelihood that electricity demand will surpass supply capacity at a given time. In this context, LPSP is employed to assess the impact of supply shortages on loads over short time intervals throughout the year.

Considering that the unmet energy (Loss of Power Supply - LPS) at the time [Inline graphic] is given by Eq. (35), the value of Inline graphic can be calculated using Eq. (36). Equation (37) expresses the limit of the load loss restriction. The Inline graphic limit values adopted in this study are: 0%, 2.5%, 5%, 7.5%, and 10%.

graphic file with name d33e1446.gif 35
graphic file with name d33e1450.gif 36
graphic file with name d33e1454.gif 37

Where: Inline graphic: total energy not supplied (kWh); Inline graphic: Percentual energy not supplied (Inline graphic); Inline graphic: Maximum allowed energy not supplied (Inline graphic); Inline graphic: Loss of power at the instant t (kW) and Inline graphic: Load demand at the instant t (kW);

Multi-objective optimization algorithm

In this study, the multi-objective optimization problem formulated in the previous section was solved using the Non-dominated Sorting Genetic Algorithm II (NSGA-II). For complex multi-objective problems, the NSGA-II is specifically designed to identify a set of non-dominated solutions that constitute the Pareto front, effectively mapping the trade-off between conflicting objectives. The algorithm’s ability to recombine and modify solutions through selection, crossover, and mutation operators ensures robust and efficient convergence. Consequently, the NSGA-II is notably recognized as a powerful tool for solving microgrid sizing and operation problems, as seen in2426.

The algorithm was implemented in the MATLAB environment using the gamultiobj function from the Global Optimization Toolbox. The simulations were configured with a population size of 100 individuals, 500 generations, and rates for crossover, mutation, and elitism of 10%, 5%, and 5%, respectively.

Microgrid components

Photovoltaic system

The power generated by the PV system at time Inline graphic is given by Eq. (38)27. In this study, the CS6W-550MS photovoltaic module manufactured by Canadian Solar was used. This model has a nominal power of 550 W and an efficiency of 21.3%28.

graphic file with name d33e1532.gif 38

Where, Inline graphic: Number of photovoltaic panels (Inline graphic); Inline graphic: Nominal power of each photovoltaic panel (Inline graphic); Inline graphic: Reduction factor for photovoltaic generation (Inline graphic); Inline graphic: Irradiation value incident on the panels at time Inline graphic (Inline graphic); Inline graphic: Temperature coefficient of the panel (−0.45%Inline graphic); Inline graphic: Temperature of the PV panels (Inline graphic); Inline graphic: Nominal operating temperature of the PV panels (Inline graphic).

Wind generation model

In this study, the Excel 7.5 kW Wind Generator turbine from Bergey, shown in Fig. 3, was used29. Table 3 shows the specifications of the wind turbine.

Fig. 3.

Fig. 3

Bergey Excel 7.5 kW Turbine. Source:29.

Table 3.

Wind turbine specifications.

Parameter Specification Value
Inline graphic Nominal power 7.5 kW
Inline graphic Cut-in wind speed 3 m/s
Inline graphic Cut-out wind speed 15.6 m/s
Inline graphic Nominal wind speed 13 m/s

Source: 29

The wind turbine power curve provided by the manufacturer is modeled by a 9th-degree polynomial function of wind speed, represented as Inline graphic in Eq. (39). The turbine power curve indicates the turbine’s power output as a function of the available wind speed. Figure 4 compares the polynomial function with the power curve provided by the manufacturer.

graphic file with name d33e1719.gif 39

Where, Inline graphic: Polynomial function of wind speed; Inline graphic through Inline graphic: Coefficients of the polynomial.

graphic file with name d33e1737.gif

Fig. 4.

Fig. 4

Wind turbine power curve. Source: Elaborated by the authors.

Wind turbine generation power is modeled by Eq. (40).

graphic file with name d33e1756.gif 40

Where, Inline graphic: Modeled power of a wind turbine (kW); Inline graphic: Wind speed (m/s); Inline graphic: Cut-in wind speed (m/s); Inline graphic: Cut-out wind speed (m/s); Inline graphic: Nominal wind speed (m/s); Inline graphic: Nominal power of the wind turbine (kW).

The modeled power will be multiplied by the number of turbines installed, as expressed in Eq. (41).

graphic file with name d33e1791.gif 41

Where, Inline graphic: Number of wind turbines (units); Inline graphic: Modeled power of a wind turbine (kW).

Tidal generation model

The tidal turbine model SmartMonofloat with a nominal power of 5 kW, shown in Figure 5, was considered. Table 4 presents its technical specifications.

Fig. 5.

Fig. 5

Smart Monofloat turbine. Source:30.

Table 4.

Specifications of the tidal turbine.

Parameter Specification Value
Inline graphic Nominal power 5 kW
Inline graphic Cut-in speed 0.5 m/s
Inline graphic Cut-out speed 2.8 m/s
Inline graphic Nominal speed 2.8 m/s

Source: 30

The power curve as a function of tidal current speed, provided by the turbine manufacturer, was modeled using a 5th-degree polynomial function given by Eq. (42). Figure 6 compares the polynomial function with the power curve provided by the manufacturer.

graphic file with name d33e1918.gif 42

Where, Inline graphic: Polynomial function of tidal current speed.

graphic file with name d33e1927.gif

Fig. 6.

Fig. 6

Tidal turbine power curve. Source: Elaborated by the authors.

The power generation of tidal turbines is modeled by Eq. (43).

graphic file with name d33e1946.gif 43

Where, Inline graphic: Modeled power of a tidal turbine (kW); Inline graphic: Tidal current speed (m/s); Inline graphic: Cut-in speed of the tidal turbine (m/s); Inline graphic: Cut-out speed of the tidal turbine (m/s); Inline graphic: Nominal speed of the tidal turbine (m/s); Inline graphic: Polynomial function of the tidal power curve; Inline graphic: Nominal power of the tidal turbine (kW).

The modeled power will be multiplied by the number of installed turbines, as expressed in Eq. (44). In this tidal model, the effects of turbulence between turbines are not considered.

graphic file with name d33e1985.gif 44

Where, Inline graphic: Number of tidal turbines (units); Inline graphic: Modeled power of a tidal turbine (kW).

Costs

The total cost of acquisition and installation of microgrid components is expressed by Eq. (45).

graphic file with name d33e2005.gif 45

Where, Inline graphic: Total installation cost ($); Inline graphic: Number of PV panels (units); Inline graphic: Number of wind turbines (units); Inline graphic: Number of tidal turbines (units); Inline graphic: Capacity of the BESS (kWh); Inline graphic: Capacity of the GH2 system (kWh); Inline graphic: Acquisition and installation cost of PV panels ($/unit); Inline graphic: Acquisition and installation cost of wind turbines($/unit); Inline graphic: Acquisition and installation cost of tidal turbines ($/unit); Inline graphic: Acquisition and installation cost of the BESS ($/kWh); and Inline graphic: Acquisition and installation cost of the GH2 system (electrolyzer and fuel cell) ($/kWh).

The annual operation and maintenance (O&M) costs are expressed by Eq. (46), adjusted by the interest rate Inline graphic over the system’s lifetime.

graphic file with name d33e2065.gif 46

Where, Inline graphic: Total O&M cost ($); Inline graphic: O&M cost of PV panels ($); Inline graphic: O&M cost of wind turbines ($); Inline graphic: O&M cost of tidal turbines ($); Inline graphic: O&M cost of the BESS ($); Inline graphic: O&M cost of the GH2 system (electrolyzer and fuel cell) ($); Inline graphic: Annual O&M interest rate (Inline graphic); Inline graphic: Project year (Inline graphic); and Inline graphic: Project lifetime (Inline graphic).

The replacement cost is given by Eq. (47), where each component type has a different lifetime. The replacement value is adjusted according to the simulation time. Replacement costs for the GH2 system include the electrolyzer and the fuel cell.

graphic file with name d33e2125.gif 47

Where, Inline graphic: Total replacement cost ($); Inline graphic: Replacement cost of PV panels ($/unit); Inline graphic: Replacement cost of wind turbines ($/unit); Inline graphic: Replacement cost of tidal turbines ($/unit); Inline graphic: Replacement cost of the BESS ($/kWh); Inline graphic: Replacement cost of the GH2 system (electrolyzer and fuel cell) ($/kWh) Inline graphic: Annual replacement interest rate (Inline graphic); Inline graphic: Project year (Inline graphic); and Inline graphic: System lifetime (Inline graphic).

The total cost of the microgrid is defined by Eq. (2).

Case study

The case study focuses on the São Marcos Bay region, specifically the Boqueirão Channel, formed by Medo Island and São Luís Island (the capital of the State of Maranhão, Brazil). Figure 7 shows an aerial image of the study area, located approximately at 2.5288Inline graphicS, 44.3596Inline graphicW. The hypothetical microgrid of this case study has a demand profile representative of the various oceanic islands in the study area. Figures 8 and 9 illustrate, respectively, the typical demand profile of communities in the region, both annually and weekly. The average demand is approximately 42 kW, with a maximum peak of 77 kW. The total annual energy demand is 365.73 MWh. These data were processed to obtain a semi-synthetic curve representing a period of 1 year with a sampling interval of 1 min, as described in31.

Fig. 7.

Fig. 7

Aerial view of the study area. Source: Aerial photograph taken by the authors.

Fig. 8.

Fig. 8

Annual load demand. Source: Elaborated by the authors.

Fig. 9.

Fig. 9

Weekly load demand. Source: Elaborated by the authors.

Considering that a key objective of this work is to analyze how different generation source profiles impact system efficiency (measured by spilled energy) and cost, using a case study based on real data provides greater practical validity to the technical and economic conclusions. Furthermore, this approach enables a more realistic assessment of the complementarity between sources, particularly tidal power. An analysis of this nature would be unfeasible if conducted with the generic or non-existent data provided by standard benchmark systems.

Energy characterization of the area

Measurements of tidal current velocity were conducted through moorings in the Boqueirão Channel, located within São Marcos Bay. Wind speed and solar irradiance data were obtained from the measurement stations of the Alcântara Launch Center (CLA). The favorable wind regime in the Baía de São Marcos is strongly influenced by the trade winds, with both synoptic regimes and the sea breeze tending to align perpendicular to the coast32.

Figures 10, 11, and 12 respectively show the measurement data for solar irradiance, wind speed, and tidal current velocity. The measurement data, collected over a period of 1 year with an initial sampling interval of 10 minutes, were interpolated to 1-minute intervals, resulting in a total of 525,600 data points.

Fig. 10.

Fig. 10

Solar irradiance. Source: Elaborated by the authors.

Fig. 11.

Fig. 11

Wind speed. Source: Elaborated by the authors.

Fig. 12.

Fig. 12

Tidal current velocity. Source: Elaborated by the authors.

Based on the measurement data and using Eqs. (38), (40), and (43), it is possible to calculate the power generated by the solar, wind, and tidal energy sources, respectively. The specifications of the wind and tidal turbines used are detailed in Tables 3 and 4, respectively.

Figures 13, 14, and 15 illustrate the daily energy generation by a single unit of each source.

Fig. 13.

Fig. 13

Daily photovoltaic generation. Source: Elaborated by the authors.

Fig. 14.

Fig. 14

Daily wind generation. Source: Elaborated by the authors.

Fig. 15.

Fig. 15

Daily tidal generation. Source: Elaborated by the authors.

The capacity factors of the renewable generation components of the microgrid are shown in Table 5.

Table 5.

Capacity factors.

Equipment CF (%)
Photovoltaic panel 15.09%
Wind turbine 32.15%
Tidal turbine 17.04%

Source: Elaborated by the authors

Equipment costs

The costs were estimated based on3337. The values presented in Table 6 are estimates that encompass purchase, installation, transportation, loading, mounting, electrical cabling, and other items. The O&M cost was estimated at 10% of the installation cost.

Table 6.

Equipment costs.

Equipment Installation
cost
Reference Nominal
capacity
PV USD 1,000.00 USD/unit 550 W
Wind USD 30,000.00 USD/unit 7.5 kW
Tidal USD 25,000.00 USD/unit 5 kW
BESS USD 458.00 USD/kWh 1 kWh
GH2 USD 600.00 USD/kWh 1 kWh

Source: Elaborated by the authors

Storage specifications

The maximum capacity limit of the BESS, as a short-term storage system, was assumed to be up to eight times the maximum load demand peak (576 kWh). The maximum capacity limit of the green hydrogen (GH2) storage system, considering its function as long-term storage, was assumed to be up to one hundred times the maximum load demand peak (7500 kWh). These limits can also be interpreted as a reflection of investment constraints in the project. From the perspective of the optimization metaheuristic, they establish an upper bound to aid in a more efficient search process.

Table 7 summarizes the specifications of the storage devices (BESS and GH2) established for this investigation. The simulations considered the following priority order of source dispatch: tidal, wind, and photovoltaic.

Table 7.

Technical specifications for BESS and GH2.

Parameter Values used
Inline graphic initial 100%
Inline graphic 30%
Inline graphic 70%
Inline graphic 1C
Inline graphic 1C
Inline graphic 95%
Inline graphic 95%
Inline graphic initial 0%
Inline graphic 100%
Inline graphic 0%
Inline graphic 100%
Inline graphic 127 kW
Inline graphic 70%
Inline graphic 127 kW
Inline graphic 70%

Source: Elaborated by the authors

General and optimization parameters

Table 8 summarizes the key parameters, control variable limits, and objective functions that define the optimization framework and simulation scenario.

Table 8.

Summary of general and optimization parameters.

Category Parameter (description) Symbol (unity) Value Used in Eq(s).
General simulation parameters
Simulation horizon Inline graphic (min) 525,600 (3), (35), (36)
Time step Inline graphic (min) 1

(3),

(15),

(26),

(35),

(36)

Load Shedding Scenarios Inline graphic (%) 0 to 10 (37)
Cost model parameters

O&M Cost (% of

each installation cost)

(%) 10 (46)
Project lifetime Inline graphic (years) 25 (46), (47)
Annual O&M interest rate Inline graphic (%) 5 (46)
Annual replacement interest rate Inline graphic 5 (47)
PV panels lifetime (years) 20 (47)
Wind turbines lifetime (years) 20 (47)
Tidal turbines lifetime (years) 20 (47)
GH2 system lifetime (years) 15 (47)
Control variables (Limits)
Limits for PV panels Inline graphic [1, 400] (6)
Limits for wind turbines Inline graphic [1, 40] (7)
Limits for tidal turbines Inline graphic [1, 40] (8)
Limits for BESS capacity Inline graphic (kWh) [288, 576] (23)
Limits for GH2 capacity Inline graphic (kWh) [0, 7500] (34)
Objective functions (Optimization Outputs)
Total system cost Inline graphic ($)

To be

minimized

(1), (2)
Total spilled energy Inline graphic (kWh)

To be

minimized

(1), (3)

Results

The case study was conducted using the configuration of the isolated microgrid shown in Fig. 1, with real data obtained from on-site measurements in the São Marcos Bay region. Sizing studies were carried out considering: i) meeting the load 24 hours a day throughout the year; ii) sensitivity analysis assuming increasing load shedding from 0 to 10%; and iii) the impact of source intermittency characteristics on the sizing process.

Case 1: Operation of a zero-carbon microgrid with three renewable sources to meet 100% of load demand

The zero-carbon microgrid consists of three distinct renewable energy sources: wind, tidal, and photovoltaic energy. It is designed to meet 100% of the energy demand. To support this, a hybrid energy storage system combines battery energy storage systems (BESS) and green hydrogen (GH2). The maximum storage capacity of the BESS is set at 576 kWh, which is approximately eight times the maximum peak load demand.

Figure 16 illustrates the Pareto Front for two objective functions: minimizing total cost and minimizing spilled energy. A total of thirty-five solutions were identified, each representing a trade-off between these functions. As illustrated in Fig. 16, the solution called Solution 1 offers the lowest total cost but results in the highest spilled energy, while the solution called Solution 35 presents the highest total cost but with the lowest spilled energy. The Pareto Front shows an inversely proportional relationship between the two objective functions: as solutions are adopted to minimize spilled energy, the total cost tends to increase. In contrast, a higher spilled energy implies a lower total cost. These results suggest that the objective functions are not aligned and are in conflict with one another.

Fig. 16.

Fig. 16

Pareto Frontier for Case 1. Source: Elaborated by the authors.

Details of the Pareto Front results shown in Fig. 16 are presented in Fig. 17. The control variables listed in Table ?? and the constraints in Table 7 were considered. For each solution, the following parameters are detailed: installed generation capacity (kW), reflecting the composition of renewable sources; installed storage capacity (kWh), representing the composition of energy storage systems; total cost (US$); and finally, spilled energy (kWh).

Fig. 17.

Fig. 17

Result compositions for Case 1. Source: Elaborated by the authors.

The Pareto Front solutions presented in Fig. 17 show that the lower the spilled energy, the higher the total cost, influenced by increased installed storage capacity. It is also observed that as storage capacity grows, installed generation capacity tends to decrease.

In Fig. 14, the daily wind energy generation throughout the year is displayed, highlighting lower generation between March and June and generation peaks between August and September. Due to this variation, wind power plant must be oversized to meet load demand during periods of low generation, which consequently leads to a significant increase in spilled energy during months of higher wind generation. On the other hand, tidal generation exhibits lower variability and is more predictable, contributing as a more stable energy source.

Among the solutions presented in the Pareto Front (Fig. 16), the extremes are solution 35 (higher cost with lower spilled energy) and solution 1 (lower cost with higher spilled energy). The latter is less expensive because, although it involves installing larger generation units with smaller storage capacity, the cost of storage is significantly higher and dominates the objective function. This most economical case is described in detail below.

Table 9 presents a summary of the sizing of Solution 1. This solution prioritizes the lowest total cost and presents a more modest storage system sizing. In this case, the installed generation capacity is 331.65 kW, and the storage capacity is 1476 kWh.

Table 9.

Sizing Summary for Case 1 - Solution 1.

Description Sizing Installed capacity
FV 153 units 84.15 kW
Wind 21 units 157.5 kW
Tidal 18 units 90 kW
BESS 576 kWh 576 kWh
GH2 900 kWh 900 kWh

Source: Elaborated by the authors

Figures 18 and 19 show the monthly and daily energy balances, respectively. The amount of spilled energy, primarily from PV and tidal sources, is particularly significant from September to December. One reason for this increase in spilled energy is the limited investment in storage solutions, which results in insufficient capacity to store all the available energy generated. There are notable monthly fluctuations in energy generation, with wind energy being the dominant source.

Fig. 18.

Fig. 18

Monthly energy balance for Case 1 - Solution 1. Source: Elaborated by the authors.

Fig. 19.

Fig. 19

Daily energy balance for Case 1 - Solution 1. Source: Elaborated by the authors.

The figures indicate that energy demand remains relatively constant throughout the year; however, the limited storage capacity means some available energy goes unused. This insufficient storage results in a greater reliance on current energy sources and contributes to increased energy spillage during periods of high generation.

Figures 20 and 21 show the monthly and daily composition of the spilled energy, respectively. Spilled energy is significant year-round, especially from June onward, with wind power contributing the most. The limited storage system prevents the microgrid from utilizing all available energy, particularly during increased wind and solar availability.

Fig. 20.

Fig. 20

Monthly composition of spilled energy for Case 1 - Solution 1. Source: Elaborated by the authors.

Fig. 21.

Fig. 21

Daily composition of spilled energy for Case 1 - Solution 1. Source: Elaborated by the authors.

Figure 22 shows the variation of the SOC of BESS and GH2 over the evaluated period. The SOC of the BESS varies more frequently, indicating that this storage system is used extensively to balance demand. In contrast, the SOC of the GH2 remains more stable, suggesting that hydrogen serves primarily as a long-term reserve, with a smaller capacity of 900 kWh.

Fig. 22.

Fig. 22

SOC BESS and SOC GH2 for Case 1 - Solution 1. Source: Elaborated by the authors.

Table 10 presents the energy summary of Solution 1 (lower cost) compared to Solution 35 (lower spilled energy). The total renewable generation reached Inline graphic, with wind contributing Inline graphic, tidal Inline graphic, and PV Inline graphic. The total spilled energy amounted to Inline graphic, equivalent to Inline graphic of the load demand. Wind energy accounted for Inline graphic of this spilled energy, highlighting the lack of storage capacity. Notably, the spilled energy nearly equaled the total load demand.

Table 10.

Energy summary for Case 1 - Solution 1 and 35.

Description Solution 35 (less spilled energy) Solution 01 (less costly)
Supplied energy (MWh)
 PV 126.08 36.79
 Wind 20.09 203.78
 Tidal 249.45 132.85
 Total 395.63 373.43
Energy consumption (MWh)
 Load 365.72 365.72
Renewable sources details
Spilled energy (MWh)
 PV 15.70 74.44
 Wind 1.03 239.75
 Tidal 4.35 1.51
 Total 21.08 315.72
Additional Details
 Total cost (USD) 5,457,221.29 3,485,795.30

Source: Elaborated by the authors

These two extreme Pareto solutions are particularly illustrative, as they emphasize the considerable impact of storage investments relative to the cost of generation equipment. The less efficient solution, characterized by a high level of spilled energy, proves more economically feasible for ensuring continuous load supply. Conversely, minimizing spilled energy through greater storage investments increases the total cost from $2.4 million to $5.4 million. Encouragingly, the cost per MWh of storage is decreasing, which could significantly change this scenario38.

Figure 23 shows the composition of the total cost for this solution. Note that renewable sources represent the largest part of the total cost, corresponding to 77% of the total value. GH2 and BESS are evaluated with 13% and 10%, respectively. Since the strategy in this solution aims to minimize total cost, there is a lower investment in storage. However, this reduction in storage investment leads to increased spilled energy.

Fig. 23.

Fig. 23

Composition of the total cost for Case 1 - Solution 1. Source: Elaborated by the authors.

Case 2: Microgrid operation considering load shedding scenarios

In this section, the authors conduct a sensitivity analysis of the microgrid operation, examining the implications of not fully meeting demand and its effect on total costs. A gradual reduction, ranging from 0% to 10% of the annual load, was applied to evaluate the behavior of the microgrid and its components, as well as the impact on the investment cost.

Figure 24 presents the Pareto Front for different levels of load shedding: 0%, 2.5%, 5%, 7.5%, and 10%, and shows the relationship between the total cost and the spilled energy for each allowed load shedding scenario. Allowing for a more significant load shedding reduces total costs, though this reduction is not linear. In scenarios with 0% load shedding, the total cost is higher due to the need for robust infrastructure sizing. As the acceptance of load shedding increases, the solutions shift to more economical configurations, resulting in a reduction in spilled energy; however, this relationship presents a saturation point, where the gains in cost reduction become less pronounced.

Fig. 24.

Fig. 24

Pareto Front for the Case 2. Source: Elaborated by the authors.

Figure 25 compares the different configurations of installed generation and storage capacities for the microgrid, considering various load shedding percentages: 0%, 2.5%, 5%, 7.5%, and 10%. The figure illustrates how the composition of generation and storage capacity changes along the Pareto Front solutions based on different levels of load shedding.

Fig. 25.

Fig. 25

Generation and storage capacities under different load shedding levels for Case 2. Source: Elaborated by the authors.

As load shedding is allowed, the sizing of generation and storage sources is progressively reduced, especially for load losses of 2.5% to 5%. However, the reduction in installed capacity is much less pronounced for higher levels of loss, such as 7.5% and 10%. Similarly, Figure 26 compares total cost and spilled energy along the Pareto Front solutions for different load shedding levels: 0%, 2.5%, 5%, 7.5%, and 10%.

Fig. 26.

Fig. 26

Total cost and spilled energy under different load shedding levels for Case 2. Source: Elaborated by the authors.

Table 11 presents the energy summary for Case 2, considering load shedding of 2.5% and 10%. It is important to note that allowing load shedding of 2.5% and 10% results in total costs that correspond to 46% and 35%, respectively, of the total cost of Solution 35 in the Table 10 (0% load shedding and lower energy spill). If 10% of the load is allowed to be cut, the investment decreases to nearly one-third of the initial value.

Table 11.

Energy summary for Case 2 - 2.5% and 10% of load shedding.

Loss load 2.5% 10%
Supplied energy (MWh)
 PV 38.20 24.99
 Wind 182.48 292.71
 Tidal 14.01 14.93
 Total Renewable Generation 360.79 332.64
Energy consumption (MWh)
 Base load 365.72 365.72
 Load Shedding 9.14 36.57
 Total 356.59 329.16
Spilled energy (MWh)
 PV 63.38 21.53
 Wind 203.91 214.19
 Tidal 2.54 0.00
 Total 269.83 235.72
Costs
 Total cost (USD) 2,497,898.37 1,906,821.42
 Cost reduction 46% 35%

Source: Elaborated by the authors

From now on, without loss of generality, only the scenario with 10% load shedding is illustrated in more detail. Table 12 summarizes the sizing for this case, with installed generation and storage capacities of 225.2 kW and 576 kWh, respectively. The wind source dominates, with 180 kW, while the photovoltaic (PV) and tidal sources contribute 35.2 kW and 10 kW, respectively. High variability in wind sources contributes to energy losses. In this case, the tolerance for a 10% load shedding was sufficient not to implement GH2 storage.

Table 12.

Sizing Summary for the Case 2 (10% Load Shedding).

Description Sizinhg Installed capacity
PV modules 64 units 35.2 kW
Wind turbines 24 units 180 kW
Tidal turbines 2 units 10 kW
BESS Capacity 576 kWh 576 kWh
GH2 Capacity 0 kWh 0 kWh

Source: Elaborated by the authors

Figures 27 and 28 show the monthly and daily energy balance, respectively. Wind energy is predominant throughout the year. Load shedding is more evident between January and July, with peaks in April coinciding with the lowest wind energy generation. Between August and December, load shedding decreased due to the growth in wind energy generation.

Fig. 27.

Fig. 27

Monthly energy balance for the case 2 (10% Load Shedding). Source: Elaborated by the authors.

Fig. 28.

Fig. 28

Daily Energy Balance for the Case 2 (10% Load Shedding). Source: Elaborated by the authors.

Figures 29 and 30 illustrate the energy spilled on a monthly and daily scale, respectively. A greater amount of spilled energy is observed between August and December, which corresponds to the peak period of wind energy generation. The high volume of spilled energy is attributed to the variability of wind energy and the relatively small size of the storage capacity.

Fig. 29.

Fig. 29

Monthly composition of spilled energy for Case 2 (10% Load Shedding). Source: Elaborated by the authors.

Fig. 30.

Fig. 30

Daily composition of spilled energy for Case 2 (10% Load Shedding). Source: Elaborated by the authors.

The variation of the SOC (State of Charge) of the BESS throughout the operation of the microgrid is shown in Fig. 31. During the first months of the year, higher cycling is observed due to the increased variability of renewable generation. In the second half of the year, the SOC variability is less pronounced, remaining closer to its maximum value for longer periods.

Fig. 31.

Fig. 31

SOC of BESS and GH2. Source: Elaborated by the authors.

Figure 32 presents the cost composition for this case. It is observed that 63% of the costs are attributed to the contribution of the wind source, while the other components have a smaller share in the cost composition.

Fig. 32.

Fig. 32

Composition of total cost. Source: Elaborated by the authors.

Impact of renewable energy sources on microgrid sizing and operation

In this section, the authors analyze how the type of renewable energy source and its intermittent characteristics influence the sizing, operation, and efficiency of the system. Two scenarios were considered:

  1. Operation with PV and Tidal Energy

  2. Operation with PV and Wind Energy

In scenario (a), solar energy generation depends on daily solar radiation, while tidal energy offers a more predictable generation pattern.

In Figure 33, the Pareto Front distribution indicates that, for scenarios with 0% load loss, solutions require higher infrastructure investments to ensure total demand fulfillment, resulting in lower levels of energy spillage. As a higher load loss is allowed, the reduction in total costs becomes more pronounced at initial levels (e.g., from 0 to 2.5% and 5%). This reduction reflects the decreased requirements for generation and storage capacity, enabling the microgrid to operate with less robustness. However, when allowed load loss exceeds 5%, economic gains diminish compared to the increase in energy spillage, highlighting a saturation point in terms of cost-benefit trade-offs.

Fig. 33.

Fig. 33

Pareto Frontier for PV and tidal energy sources. Source: Elaborated by the authors.

Figure 34 illustrates that the installed generation and storage capacity tend to decrease as the load loss increases. In scenarios with 0% load loss, the installed capacity of photovoltaic and tidal energy sources is maximized to meet all demand, requiring robust generation systems and storage capacities. As flexibility in demand increases (up to a 10% load loss), a gradual decrease in installed capacity is observed, reflecting an optimization strategy to reduce oversizing, particularly in storage systems such as Battery Energy Storage Systems (BESS) and Green Hydrogen (GH2). This reduction is most evident at intermediate levels of load loss, resulting in lower total costs and reduced capacity sizing requirements.

Fig. 34.

Fig. 34

Comparison of load loss for PV and tidal energy sources - Generation and Storage Capacity. Source: Elaborated by the authors.

The case (b) considers only PV (Photovoltaic) and Wind Energy, both characterized by high variability. Figure 35 shows the Pareto Front for different levels of load shedding, similar to the previous case.

Fig. 35.

Fig. 35

Pareto Front for PV and Wind Energy Sources. Source: Elaborated by the authors.

Figure 36 highlights the comparison of installed generation and storage capacity for different levels of load shedding.

Fig. 36.

Fig. 36

Comparison of Load Shedding for PV and Wind Energy Sources - Generation and Storage Capacity. Source: Elaborated by the authors.

In Case (a), which combines PV and Tidal Energy, the stability of generation is more pronounced due to the higher predictability of tidal generation. This feature results in a lower storage capacity requirement compared to the other scenarios. The solutions found tend to have lower total costs and less energy spillage, as tidal generation acts as a stabilizing factor, offsetting the variability of PV generation.

On the other hand, Case (b), which combines only PV and Wind Energy, is characterized by the high variability and intermittency of both sources. This configuration has implications for storage requirements and their lifespan31. The result is greater energy spillage and higher total costs in many cases, reflecting the challenges of maintaining stability and efficiency with more intensely intermittent sources.

Discussion of results

The simulations were conducted to minimize total cost and spilled energy, as illustrated by the presented Pareto Fronts. Solutions that offer higher energy efficiency tend to require higher initial investments, while more cost-effective solutions lead to higher levels of spilled energy. Therefore, the choice of objective functions directly influences the sizing of generation and storage sources, consequently affecting the microgrid’s behavior under different operational scenarios.

A key finding of this work is that, over the course of a year, the critical periods of renewable source insufficiency are few and relatively short. This fact becomes evident when a load shedding simulation is performed, for instance, with a 2.5% reduction. This results in a significant reduction in the required sizing of the generation plant. For higher load reductions (between 5 and 10%), the investment reduction is not as significant.

This scenario is beneficial, as with minimal effort - and negotiating through an interruption agreement - it is possible to enable not a zero-carbon microgrid, but rather a low-carbon microgrid. The composition of generation sources (photovoltaic, wind, and tidal) and storage systems (BESS and GH2) has a direct impact on system performance. In Case 2, which considers operation with only two renewable sources, greater variability was observed, highlighting the need for increased storage capacity to ensure regularity in supply, particularly in the short term.

A key finding of this work is the non-linear relationship between reliability and total system cost, exemplified by the 46% cost reduction when the Loss of Power Supply Probability (LPSP) is relaxed from 0 to 2.5%. This result reveals a fundamental principle of this type of microgrid: the prohibitive cost of achieving 100% reliability in load supply. To make this perfect reliability scenario possible, heavy investments in energy assets are necessary, even if they are rarely used at their nominal capacity. By allowing for some flexibility in reliability (e.g., an LPSP of 2.5%), the microgrid is released from the obligation to meet even the rarest mismatch between generation and load. This permits a drastic reduction in the sizing of energy assets and can even lead to the complete elimination of some components, as illustrated in the 10% LPSP case (Table 12), which enables the removal of the GH2 system. These findings support the need to adopt demand-side management strategies and contracts that tolerate controlled load curtailment. Such strategies should not be seen as complementary tools but as enabling mechanisms for the economic viability of zero-carbon microgrids.

Conclusion

The operation of isolated microgrids powered 100% by renewable sources faces significant technical and economic challenges, mainly due to the temporal variability between generation and load over time. This imbalance directly influences system sizing, affecting storage needs and generator capacities. Furthermore, a zero-carbon microgrid can be considered the cornerstone of the energy transition.

In this paper, the problem of sizing an isolated 100% renewable microgrid was formulated, considering only clean energy sources to meet the load demand. This approach enables a detailed analysis of the technical and economic implications associated with the design and operation of sustainable microgrids. The following observations and conclusions can be highlighted from this investigation.

  • The use of storage technologies, including seasonal storage alternatives, such as hydrogen storage systems, is essential to ensure the reliability of energy supply in zero-carbon microgrids. These systems help mitigate the intermittency of renewable sources, ensuring the ability to meet demand even during periods of low production or high variability.

  • It is concluded that a renewable source with a less intermittent profile, in this case, tidal energy, can reduce storage dependence, helping to smooth generation variability. This choice has a positive impact on the sizing of generator units and the storage system. When comparing the PV-Wind and PV-Tidal configurations to supply 100% of the load with minimal spilled energy, the excess energy amounts to 4.9 kWh and 0.8 kWh, respectively, with investment costs of USD 5.3 million and USD 4.9 million. Clearly, the PV-Tidal configuration significantly reduces spilled energy while requiring a lower investment cost.

  • The least-cost configuration with three renewable sources supplies 100% of demand but generates excess energy equivalent to 86.33% of the load, predominantly from wind (75.91%), due to limited storage use. Curtailing this surplus requires storage expansion, which raises total costs from USD 2.4 million to USD 5.4 million. A key finding is that if a small load curtailment of 2.5% is accepted, the cost decreases to 46% of this value - practically matching the minimum cost - while eliminating all spilled energy. This result underscores the role of demand reduction or interruption agreements as a viable mechanism to enhance the feasibility of low-carbon energy systems.

  • The studied structure for the zero-carbon microgrid in islanded operation can be expanded for application in larger networks, contributing to large-scale energy transition. This expansion may involve the interconnection of multiple microgrids, enabling greater flexibility, resource sharing, improved load demand management, and cost reductions at the regional level.

  • Green hydrogen has excellent potential as seasonal and long-term storage, complementing short-term storage with lithium-ion batteries and similar technologies. The results showed that green hydrogen is a viable solution to compensate for the seasonal variability of renewable sources.

  • The integration of different renewable sources, such as solar, wind, and tidal energy, was found to contribute to the microgrid with a reasonable degree of complementarity. The use of short-term storage systems (BESS) and long-term storage (GH2) is effective in balancing the different variability scales of sources, reducing spillage. However, combining more intermittent sources, such as solar and wind, may require greater investment in storage, especially short-term storage.

  • Although spilled energy is a clear waste, in practice, it can be minimized but is hardly eliminated.

Although the current costs associated with operating zero-carbon microgrids, especially those with storage systems, may be high, they tend to decrease with technological advancements, larger production scales, and economic incentives. The results indicate that technological evolution and incentive policies can make costs more competitive, which favors greater adoption of microgrids. The study was conducted on a small-scale microgrid; however, the analyses and conclusions remain valid for systems of any scale. This claim is grounded in the well-established scientific practice of employing minimal and scale models to capture the essential dynamics of complex phenomena39.

Acknowledgements

This research is part of ongoing work within the scope of the National Institute of Science and Technology in Oceanic and Fluvial Energies (INEOF), with financial support from the Coordination for the Improvement of Higher Education Personnel (CAPES) – Brazil, under the PDPG Amazonia Legal (CAPES Process No. 88881.510240/2020-01), the National Council for Scientific and Technological Development (CNPq), and the Foundation for the Support of Research and Scientific and Technological Development of Maranhão (FAPEMA). O. Saavedra gratefully acknowledges the support provided by São Paulo Research Foundation through grant FAPESP2021/11380-5 (CPTEn). The authors also express their gratitude to the Alcântara Launch Center (CLA - Brazil) for providing meteorological station data.

Author contributions

W.M., O.R., P.B. and D.Q. wrote the manuscript text; W.M. prepared the simulation tools and the figures; W.M., O.R., P.B. and D.Q. developed the conceptualization and the problem formulation. All authors reviewed the manuscript.

Funding

This publication has been funded by CAPES under the PDPG Amazonia Legal Project (Grant Inline graphic88881.510240/2020-01). INEOF has financial support from CNPq and FAPEMA. Partial support for author O. Saavedra was provided by FAPESP under project number 2021/11380-5.

Data availability

The datasets used and/or analysed during the current study are available from the corresponding author on reasonable request.

Declarations

Competing interests

The authors declare no competing interests.

Ethics approval and consent to participate

The authors declare for whom it concerns that the submitted paper is not under consideration for publication elsewhere, that its publication is approved by all authors and tacitly or explicitly by the responsible authorities where the work was carried out, and that, if accepted, it will not be published elsewhere in the same form, in English or any other language, including electronically without the written consent of the copyright-holder. All authors have consented to participate in the paper.

Consent for publication

The authors agree with the paper publication, when/if accepted, respecting all publishing policies from Springer.

Footnotes

Publisher’s note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

References

  • 1.Ribeiro, L. A. S., Saavedra, O. R., Lima, S. L., de Matos, J. G. & Bonan, G. Making isolated renewable energy systems more reliable. Renew. Energy45, 221–231 (2012). [Google Scholar]
  • 2.Rousan, T., Higginson, M. & Pabst, P. Design and operation of an islanded power system with 100% renewable energy supply. In 2018 IEEE/PES Transmission and Distribution Conference and Exposition (T &D) 1–5 (Denver, CO, USA, 2018).
  • 3.Campagna, N. et al. Challenges for the goal of 100% renewable energy sources to fit the green transition. In 2022 Workshop on Blockchain for Renewables Integration (BLORIN) 230–235 (Palermo, Italy, 2022).
  • 4.Bastos, A. F. & Trevizan, R. D. Feasibility of 100% renewable-energy-powered microgrids serving remote communities. In 2023 IEEE Power & Energy Society Innovative Smart Grid Technologies Conference (ISGT) 1–5 (Washington, DC, USA, 2023).
  • 5.Li, B. Build 100% renewable energy based power station and microgrid clusters through hydrogen-centric storage systems. In 2020 4th International Conference on HVDC (HVDC) 1253–1257 (Xi’an, China, 2020).
  • 6.Li , B. & Roche, R. Sizing a 100% renewable energy based power supply system based on multi-objective optimization. In 2021 IEEE Madrid PowerTech 1–6 (Madrid, Spain, 2021).
  • 7.Abdelsalam, R. A., Abdallah, Y. S., Shabar, N. M., Afifi, O. A., Fouda, M. H. & El-Deib, A. A. Energy management and techno-economic optimization of an isolated hybrid ac/dc microgrid with green hydrogen storage system. In 2023 IEEE Conference on Power Electronics and Renewable Energy (CPERE) 1–7 (Luxor, Egypt, 2023).
  • 8.Wang, J. Study of inverter control strategies on the stability of microgrids toward 100% renewable penetration. In IECON 2022 – 48th Annual Conference of the IEEE Industrial Electronics Society 1–6 (Brussels, Belgium, 2022).
  • 9.Harasis, S. Controllable transient power sharing of inverter-based droop controlled microgrid. Int. J. Electr. Power Energy Syst.155, 109565 (2024). [Google Scholar]
  • 10.Harasis, S., Sozer, Y. & Elbuluk, M. Reliable islanded microgrid operation using dynamic optimal power management. IEEE Trans. Ind. Appl.57(2), 1755–1766 (2021). [Google Scholar]
  • 11.Daneshvar, M., Mohammadi-Ivatloo, B. & Zare, K. A fair risk-averse stochastic transactive energy model for 100% renewable multi-microgrids in the modern power and gas incorporated network. IEEE Trans. Smart Grid14(3), 1933–1945 (2023). [Google Scholar]
  • 12.Li, H., Ren, Z., Trivedi, A., Srinivasan, D. & Liu, P. Optimal planning of dual-zero microgrid on an island toward net-zero carbon emission. IEEE Trans. Smart Grid15(2), 1243–1257 (2024). [Google Scholar]
  • 13.Shen, X., Li, X., Yuan, J. & Jin, Y. A hydrogen-based zero-carbon microgrid demonstration in renewable-rich remote areas: System design and economic feasibility. Appl. Energy326, 120039 (2022). [Google Scholar]
  • 14.Wang, R., Akbari, E., Bagherzadeh, L. & Pirouzi, S. Stochastic economic sizing of hydrogen storage-based renewable off-grid system with smart charge of electric vehicles according to combined hydrogen and power model. J. Energy Storage108, 115171 (2025). [Google Scholar]
  • 15.Naghibi, A. F., Akbari, E., Shahmoradi, S., Pirouzi, S. & Shahbazi, A. Stochastic economic sizing and placement of renewable integrated energy system with combined hydrogen and power technology in the active distribution network. Sci. Rep.14, 28354 (2024). [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 16.Shahzad, S., Alsenani, T. R., Kilic, H. & Wheeler, P. Techno-economic analysis of green hydrogen integration in smart grids: Pathways to sustainable energy systems. Int. J. Hydrogen Energy143, 989–999 (2025). [Google Scholar]
  • 17.McJunkin, T. R. & Reilly, J. T. Net-zero carbon microgrids. Technical Report INL/EXT-21-65125, Idaho National Laboratory, Idaho Falls, Idaho, November 2021. Prepared for the U.S. Department of Energy, Office of Electricity under DOE Idaho Operations Office Contract DE-AC07-05ID14517.
  • 18.Li, H., Ren, Z., Trivedi, A., Srinivasan, D. & Liu, P. Optimal planning of dual-zero microgrid on an island toward net-zero carbon emission. IEEE Trans. Smart Grid15(2), 1243–1257 (2023). [Google Scholar]
  • 19.Chen, L., Gao, L., Xing, S., Chen, Z. & Wang, W. Zero-carbon microgrid: Real-world cases, trends, challenges, and future research prospects. Renew. Sustain. Energy Rev.203, 114720 (2024). [Google Scholar]
  • 20.Bhatt, A., Ongsakul, W. & Nimal, M. M. Optimal techno-economic feasibility study of net-zero carbon emission microgrid integrating second-life battery energy storage system. Energy Convers. Manag.266, 115825 (2022). [Google Scholar]
  • 21.Hang, Yu., Niu, S., Zhang, Y. & Jian, L. An integrated and reconfigurable hybrid ac/dc microgrid architecture with autonomous power flow control for nearly/net zero energy buildings. Appl. Energy263, 114610 (2020). [Google Scholar]
  • 22.Ye, Y., Wang, B., Ren, X., Song, Z., Zhao, C. & Han, D. A multi-objective time of use pricing strategy for the net-zero microgrid considering uncertainty in loads and renewable energy resources. In 2022 Power System and Green Energy Conference (PSGEC) 241–245 (IEEE, 2022).
  • 23.Sadhukhan, J.  & Christensen, M. An in-depth life cycle assessment (lca) of lithium-ion battery for climate impact mitigation strategies. Energies14(17), (2021).
  • 24.Torkan, R., Ilinca, A. & Ghorbanzadeh, M. A genetic algorithm optimization approach for smart energy management of microgrids. Renew. Energy197, 852–863 (2022). [Google Scholar]
  • 25.Zhu, X. et al. Multi-objective sizing optimization method of microgrid considering cost and carbon emissions. IEEE Trans. Ind. Appl.60(4), 5565–5576 (2024). [Google Scholar]
  • 26.Li, X. & Jones, G. Optimal sizing, location, and assignment of photovoltaic distributed generators with an energy storage system for islanded microgrids. Energies15(18), 6630 (2022). [Google Scholar]
  • 27.Leite Neto, P. B. et al. Contribuições para a operação energética e econômica de microrredes isoladas com fontes renováveis. (Phd in electrical engineering, Universidade Federal do Maranhão, São Luís, 2017).
  • 28.Canadian Solar. Hiku6 mono perc. Data Sheet. (2024). in: https://static.csisolar.com/wp-content/uploads/2020/06/21135332/CS-Datasheet-HiKu6_CS6W-MS_v2.1_EN.pdf. Acesso em: 01 Sept 2024.
  • 29.Bergey Wind Power CO. Bergey 7.5 kw wind generator. Bergey Excel. (2024). Disponível em: https://nooutage.com/excel-r.htm. Accessed in: 01 Sept 2024.
  • 30.SMART HIDRO POWER. Smart monofloat turbine. (2024). In: https://smart-hydro.de/wp-content/uploads/2015/12/Datasheet_SMART_Monofloat.pdf. Accessed in: 01 Sept 2024.
  • 31.Leite Neto, P. B., Saavedra, O. R. & Oliveira, D. Q. The effect of complementarity between solar, wind and tidal energy in isolated hybrid microgrids. Renew. Energy147, 339–355 (2020). [Google Scholar]
  • 32.Assireu, A. T., Pimenta, F. M., de Freitas, R. M., Saavedra, O. R., Neto, F. L. A., Júnior, A. R. T., Oliveira, C. B. M., Lopes, D. C. P., de Lima, S. L., Veras, R. B. S., Saraiva, N. P., Marcondes, L. G. P. & Oliveira, D. Q. Eosolar project: Assessment of wind resources of a coastal equatorial region of Brazil-overview and preliminary results. Energies15(7), (2022).
  • 33.U.S. solar photovoltaic system and energy storage cost benchmarks, with minimum sustainable price analysis: Q1 2023. NRL. (2011). Disponível em: https://www.nrel.gov/docs/fy23osti/87303.pdf Accessed in: 01 Sept 2024.
  • 34.Bergey Wind Power CO. Retail price list. (2011). in: https://www.bergey.com/wp-content/uploads/2012/05/685d0a6f733ef2bbd913a05d15e442cd.pdf. Accessed in: 01 Sept 2024.
  • 35.Smart prices & products overview. Smart Hidro Power, 2024. In: https://www.smart-hydro.de/renewable-energy-systems/prices-hydrokinetic-photovoltaic/. Accessed in: 01 Sept 2024.
  • 36.Cost projections for utility-scale battery storage: 2023 update. NREL. 2023. Disponível em: https://www.smart-hydro.de/renewable-energy-systems/prices-hydrokinetic-photovoltaic/. Acesso em: 01 set. 2024.
  • 37.Hasan, T. et al. Techno-economic assessment of a hydrogen-based islanded microgrid in north-east. Energy Rep.9, 3380–3396 (2023). [Google Scholar]
  • 38.Cole, W. & Karmakar, A. Cost projections for utility-scale battery storage: 2023 update. Technical Report NREL/TP-6A40-85332, National Renewable Energy Laboratory, Golden, CO, June 2023. Contract No. DE-AC36-08GO28308.
  • 39.Robert, W. Batterman and Collin rice. Minimal model explanations. Philos. Sci.81(3), 349–376 (2014). [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Data Availability Statement

The datasets used and/or analysed during the current study are available from the corresponding author on reasonable request.


Articles from Scientific Reports are provided here courtesy of Nature Publishing Group

RESOURCES