Abstract
Background
This study illustrates for the first time the performance (sensitivity and selectivity) of the selective medium BCYEα +AB suggested by the new edition of ISO 11731 for legionella isolation and enumeration. We compared the efficacy of the selective BCYEα +AB medium with that of the highly selective MWY medium.
Results
Legionella spp. was detected in 48.2 and 47.1% of the samples by BCYEα +AB and MWY agar, respectively. For optimal detection of Legionella spp., most protocols recommend using selective media to reduce the number of non-Legionella bacteria. Agreement between the two media was 86.7%.
Conclusions
According to the results, both media have a very similar performance and they both have advantages and disadvantages over each other. In AB medium there is the risk of being less selective so more interfering microbiota may grow but in MWY medium there is the risk of being too selective. The low selectivity of the AB medium could be resolved if other treatments are applied after filtration, e.g. acid and/or heat treatment, but it must be taken into account that these treatments still reduce the number of viable Legionella. In conclusion, we recommend using MWY as a selective medium for the detection of Legionella spp. as it is easier discern suspected colonies and facilitate the final Legionella spp. count.
Supplementary Information
The online version contains supplementary material available at 10.1186/s12866-021-02109-1.
Keywords: Legionella, Culture media, Environmental monitoring
Background
Legionella pneumophila, which represents the etiological agent responsible for Legionnaires’ disease (LD), was first isolated by McDade et al. in [21]. After its discovery, several occurrences of Legionella infection have been reported to be associated with water distribution systems, air conditioning devices, spas and cooling towers [4, 12, 21, 22]. As potable water has long been identified as a potential source of nosocomial and community-acquired LD, environmental surveillance of water systems for the identification of Legionella spp. is now being recommended worldwide.
More than 66 Legionella species comprising 70 distinct serogroups have been identified to date (https:/l-1psn.dsmz.de/genusl-1egionella). Most Legionella species have been isolated from aqueous environments, with at least 30 of them capable of causing infection in humans, mainly in the lower respiratory tract [3].
Legionella is a particularly fastidious gram-negative bacterium: in the late 1970s, Feeley and Gorman prepared a new agar medium, cysteine F-G agar-iron, with L-cysteine hydrochloride and soluble ferric pyrophosphate [11], while Feeley et al. modified the medium by replacing casein acid hydrolysate with yeast extract and by adding activated charcoal as a scavenger of radicals and peroxides [10] and the resulting charcoal yeast extract agar (CYE) medium enhanced the growth of Legionella spp. Later on, Pasculle et al. supplemented the CYE medium with N-(2-Acetamido)-2-aminoethanesulfonic acid (ACES) buffer, thereby obtaining buffered charcoal yeast extract agar (BCYE) which, under aerobic conditions, enabled a better recovery of Legionella [27], and Edelstein further increased this medium’s sensitivity by adding α-ketoglutarate (i.e., BCYEα agar) [8].
Since then, numerous selective media based on different inhibiting agents have been developed so as to limit the development of interfering microbiota that may reduce or inhibit the recovery of these bacteria. Notable among these are GVPC agar, a BCYEα medium supplemented with 3 g/l glycine, 0.001 g/l vancomycin, 80,000 IU/l polymyxin B and 0.08 g/l cycloheximide, and the modified Wadowsky–Yee (MWY) medium [9, 32], another BCYEα medium containing, differently from GVPC medium, 3 g/l glycine, 50,000 IU/l polymyxin B, 0.001 g/l vancomycin, 0.08 g/l anisomycin and the colors bromothymol blue and bromocresol purple, which stain the colonies and aid in the identification of the organisms. For optimal detection of Legionella spp. via reduction of non-Legionella bacteria, most protocols, i.e. Health Protection Agency [15], AFNOR [1], ISO [16] and Centers for Disease Control and Prevention [2], recommend using selective agar consisting of buffered charcoal yeast extract (BCYEα) agar containing 1 g/l alpha-ketoglutarate supplemented with glycine, vancomycin, polymyxin B and cycloheximide (GVPC). Although this medium is now widely used in laboratories worldwide, the presence of contaminating bacterial flora in water samples frequently reduces the recovery of Legionella spp. due to overgrowth or inhibition [29].
Since 1997, our laboratory has been conducting Legionella spp. testing on environmental samples using two types of medium: BCYEα and MWY [5]. We adopted MWY because its dyes stain the colonies with better differentiation [9, 30]. The combined use of BCYEα agar with selective agar for improved Legionella detection has been recently (2017) recommended by the second edition of ISO 11731 [17]. This new edition also proposes three different types of selective media for Legionella isolation: GVPC or MWY agar for water samples with a high concentration of interfering microbiota, and BCYEα +AB agar (i.e., natamycin, cefazolin and polymyxin B) for samples containing low concentrations of interfering microbiota. This latter selective medium was first recommended by the Dutch Standard NEN 6265 [26].
The goal of this study was to compare the performance of the BCYEα +AB vs. MWY agar in terms of sensitivity and selectivity in suppressing the growth of interfering microbiota from water samples taken from hospital water supplies.
Results
A total of 263 hot water samples, all taken from hospital potable water faucets, were cultured on two different media (i.e., BCYEα +AB and MWY) to isolate Legionella spp. Of these, 143 (54.4%) were Legionella positive at least on one medium. The distribution of the results between the two media is shown in Table 1.
Table 1.
MWY agar | BCYEα + AB agar | Total | (%) |
---|---|---|---|
negative | negative | 111 | 42.2 |
negative | positive | 19 | 7.2 |
positive | positive | 108 | 41.1 |
positive | negative | 13 | 4.9 |
positive | overgrowtha | 3 | 1.1 |
negative | overgrowtha | 4 | 1.5 |
overgrowtha | overgrowtha | 5 | 1.9 |
263 |
aovergrowth of background flora. Corresponding samples were considered as Legionella-negative as described in the Results
A small minority of the specimens (5/263) contained Gram-negative bacteria that were not inhibited by either selective medium (i.e., MWY and BCYEα +AB), while 7 further samples contained flora whose growth was inhibited by the MWY selective medium but not by BCYEα+AB (Table 1). Therefore, the evaluation of the presence of Legionella in our samples (and enumeration of Legionella spp. colonies for positive samples) was possible for 98.1% (258/263) of the samples seeded on MWY agar and 95.4% (251/263) of those seeded on BCYEα +AB agar, whereas all samples contaminated by overgrowth of Gram-negative bacteria were deemed as Legionella negative.
Agreement between the two methods was 86.7%. Calculation of Cohen’s κ-coefficient showed good concordance (κ = 0.733) (Table 2).
Table 2.
BCYEα + AB agar | ||||
---|---|---|---|---|
Positive (n) | Negative (n) | Total (n) | ||
MWY agar | Positive (n) | 108 | 16 | 124 |
Negative (n) | 19 | 120 | 139 | |
Total (n) | 127 | 136 | 263 |
Agreement = 86.7%; κ = 0.733
Table 3 compares the results concerning Legionella counts of the 108 concordant positive samples.
Table 3.
No. (%) of samples |
MWY agar | BCYEα + AB agar | |||||
---|---|---|---|---|---|---|---|
Geometric mean |
Median | Range | Geometric mean |
Median | Range | ||
Higher counts on MWY | 37 (34.3%) | 1.7 × 103 | 1.6 × 103 | 2.0 × 102 - 1.7 × 104 | 1.0 × 103 | 9.0 × 102 | 5.0 × 101 - 1.6 × 104 |
Higher counts on BCYEα + AB | 56 (51.8%) | 8.1 × 102 | 9.5 × 102 | 5.0 × 101 - 8.3 × 103 | 1.3 × 103 | 1.2 × 103 | 1.0 × 102 - 1.7 × 104 |
Counts on MWY agar = counts on on BCYEα AB | 15 (13.9%) | 6.1 × 102 | 3.0 × 102 | 5.0 × 101 - 3.3 × 105 | 6.1 × 102 | 3.0 × 102 | 5.0 × 101 - 3.3 × 105 |
The most frequently isolated species was L. pneumophila (59.4%) and was detected equally using the two agar media. In 29 of the 143 positive water samples, L. pneumophila grew with associated non-pneumophila Legionella species. The most frequently isolated serogroups were L. pneumophila serogroup 6 and serogroup 1. The distribution of the results is shown in Table 4.
Table 4.
Species | Serogroups | Total (n) |
---|---|---|
L. pneumophila sg 1 | 22 | |
L. pneumophila sg 2 | 4 | |
L. pneumophila | L. pneumophila sg 3 | 5 |
L. pneumophila sg 6 | 40 | |
L. pneumophila sg 7–14 | 14 | |
L. species non-pneumophila | autofluorescens | 35 |
Other | 23 | |
143 |
Among the 124 samples who tested Legionella spp. positive on MWY agar, 23 showed the presence of accompanying microbiota (18.5%), whereas accompanying microbiota was observed in 52 out of 127 Legionella spp. positive samples (40.9%) on BCYEα+AB agar (Fig. 1).
To determine whether the medium composition had an effect on Legionella spp. enumeration, we compared the final counts obtained from each medium through the Wilcoxon signed-rank test, which showed absence of significant correlation between the counts and the medium (p = 0.09934). The same analysis yielded a statistically significant difference in non-Legionella flora growth between the MWY and BCYEα +AB media (p < 0.0001). Furthermore, the counts from the 108 positive samples on both agars were compared by evaluating Kendall’s tau correlation coefficient, which showed a high degree of correlation (τ = 0.7852, p < 0.0001) (Fig. 2).
Discussion
Legionella spp. is characterized by an extended lag period of growth, requiring at least 3 days to produce visible colonies on BCYEα agar, so its detection is often hindered by the presence of other bacteria. In this regard, the selective media MWY and GVPC, recommended when isolating these bacteria from environmental specimens, rarely achieve a good balance between false positive and false negative results, which reduces the recovery of the target organism (i.e., Legionella spp.) [13, 19]. In a previous study, we demonstrated that these limitations can be overcome by using BCYEα agar, which can significantly improve isolation and enumeration of Legionella spp. [5].
More recently, the new edition of ISO 11731 [17] has proposed the use of three different types of selective media for detecting Legionella species: GVPC or MWY agar for water samples with a high concentration of background flora and BCYEα+AB agar for samples with a low concentration of interfering microorganisms. However, given that the selective culture of Legionella may also be influenced by the degree of susceptibility of the microorganisms to antimicrobials, which varies according to their physiological state, here we inquired whether the use of BCYEα +AB agar could improve the sensitivity of Legionella spp. detection in environmental water samples over that of current methods. To our knowledge, this is the first study addressing detection and enumeration of Legionella species on BCYEα +AB medium.
Agreement between the results obtained with the two media was 86.7%. Importantly, parallel seeding showed that the number of Legionella CFUs on BCYEα +AB agar was not significantly higher than the number of CFUs found on MWY agar (medium with higher concentrations of antibiotics and antifungals) (p = 0.09934), indicating that there are no significant differences in sensitivities between the two selective procedures. Thus, our results demonstrate that both selective media are suitable for primary plating of environmental specimens for the isolation of Legionella spp.
According to the results, both methods have a very similar performance and they both have advantages and disadvantages over each other. In AB media there is the risk of being less selective so more interfering microbiota may grow but in MWY media there is the risk of being too selective and Legionella spp. cells that are harmed or not that much active in the water systems would not grow. The low selectivity of the AB medium could be resolved if other treatments are applied after filtration, e.g. acid and / or heat treatment, but it must be taken into account that these treatments still reduce the number of viable Legionella.
Conclusions
In conclusion, we recommend using MWY as a selective medium for the detection of Legionella spp. as it is easier discern suspected colonies and facilitate the final Legionella spp. count (see Additional file 2).
Methods
Environmental sampling
Hot water samples were collected from in-building distribution systems of healthcare facilities of acute care hospitals while conducting environmental monitoring programs for Legionella spp. detection. All samples were collected from water faucets without previously running the water and without flaming the outlet point, in accordance with the Italian Guidelines for water sampling in common use conditions, namely ‘instantaneous sampling’, to simulate theoretical user exposure [23]. Each sample was collected in sterile one-liter plastic bottles. Sodium thiosulphate solution (100 mg/l) was added to the samples to neutralize free chlorine in treated water supplies. The samples were then transported to the laboratory at room temperature and processed on the day of collection.
Laboratory procedure
Analyses for the quantification of Legionella spp. were performed according to an internal method [5]. Water samples were cultured onto MWY agar (Xebios Diagnostics GmbH, Düsseldorf, Germany), i.e., BCYEα agar with the addition of glycine (3 g/l), polymyxin B (50,000 IU/l), vancomycin (0.001 g/l), anisomycin (0.08 g/l), bromothymol blue (0.01 g/l) and bromocresol purple (0.01 g/l, colors which help distinguish more easily between Legionella and non-Legionella bacteria), and onto BCYEα+AB (Xebios Diagnostics GmbH, Düsseldorf, Germany), consisting of natamycin (65 mg/l), cefazolin (9 mg/l) and polymyxin B (80,000 IU/l).
Briefly [5], the one liter water samples was concentrated 100-times by filtration using 0.22 μm polycarbonate filter (Millipore, Billerica, MA, USA). After filtration, the membrane filter was aseptically placed in one of the bottom corners of a stomacher bag with 10 ml Page solution (pH 6.8) and rubbed for 1 min, in order to detach bacteria. A 0.2 ml volume of the concentrated sample was placed in duplicate on plates of MWY and BCYEα+AB agar, and the plates were then incubated at 36 °C with 2.5% CO2 for 10 days. The plates were checked at days 2, 3, 5 and then at the end of the incubation period. Presumptive Legionella colonies were confirmed by subculturing on blood agar (Oxoid Ltd., Basingstoke, UK) and BCYEα agar. Colonies grown on MWY agar or BCYEα+AB agar were identified according to ISO 11731 procedure (one colony type: three presumptive colonies were subcultured; more colonies types: at least one colony from each type were subcultured) by means of an agglutination test (Legionella latex test; Oxoid). The latex test allows separate identification of L. pneumophila serogroup 1 and serogroups 2 to 14 and detection of seven other non-pneumophila Legionella spp. (L. longbeachae 1 and 2, L. bozemanii 1 and 2, L. dumoffii, L. gormanii, L. jordanis, L. micdadei, and L. anisa) [7, 14, 18, 20, 25, 31]. Colonies recognized as L. pneumophila serogroup 2 to 14 were further tested with single Legionella agglutination latex reagents (Pro-Lab Diagnostics, Richmond Hill, Canada) for the identification of the different L. pneumophila serogroups. If the agglutination test with the colonies was negative, the isolates underwent a polymerase chain reaction test (in-house PCR) for the amplification of the 16S rRNA gene of Legionella spp., as previously described [24]. The plate with the higher number of confirmed colonies was used to estimate the number of Legionella spp. in the original sample. Legionella spp. concentrations in water samples are expressed in colony forming unit per liter (CFU/l). According to the concentration procedure, the detection limit of our method is 50 CFU/l. The presence of background flora was measured through semi-quantitative counting [6]: four categories were determined according to visual density of colonies spread onto the plate, where zero was no background flora and 3+ was massive contamination (See Additional file 1).
Statistical analysis
Statistical analyses were performed using the statistical software R (“stats” package, version 3.6.2) [28]. Agreement between the two media was assessed by comparing the results of the MWY and BCYEα+AB media on two-by-two contingency tables, through Cohen’s κ coefficient. The non-parametric Wilcoxon signed-rank test was applied to all samples in order to compare differences in microbial loads between MWY agar and BCYEα+AB agar for both Legionella spp. and background flora. Kendall’s tau correlation coefficient was employed to compare the ability of the two media to cultivate Legionella. The analysis was performed by taking into account only samples positive for Legionella spp. on both media, after checking the preliminary assumptions.
Supplementary Information
Acknowledgements
Not applicable.
Abbreviations
- BCYE
Buffered Charcoal Yeast Extract agar
- BCYEα
Buffered Charcoal Yeast Extract agar with α-ketoglutarate;
- BCYEα+AB
Buffered Charcoal Yeast Extract agar with α-ketoglutarate and Antibacterials
- CYE
Charcoal Yeast Extract agar
- GVPC
Glycine Vancomycin Polymyxin and Cycloheximide agar
- LD
Legionnaires’ Disease
- MWY
Modified Wadowsky-Yee medium
- PCR
Polymerase Chain Reaction
- rRNA
Ribosomal RNA
Authors’ contributions
Substantial contribution to conception and design of the study: S.D., M.G., formal analysis: M.G., G.M.; data curation: J.G.; drafting and critically revising the manuscript: S.D., M.G., J.G., C.M.Z.; all authors read and approved the final manuscript.
Funding
This work was supported by a grant from the Department fund ZOTC_CT_PREST_18_01, Department of Public Health and Pediatrics, University of Turin. The funding sources were deployed for reagent purchase and sample processing, while had no role in the design of the study, interpretation of data and in writing the manuscript.
Availability of data and materials
The dataset used and/or analysed during the current study are available from the corresponding author on reasonable request.
Ethics approval and consent to participate
Not applicable.
Consent for publication
Not applicable.
Competing interests
The authors declare that they have no competing interests.
Footnotes
Publisher’s Note
Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.
Contributor Information
Savina Ditommaso, Email: savina.ditommaso@unito.it.
Monica Giacomuzzi, Email: monica.giacomuzzi@unito.it.
Gabriele Memoli, Email: gabriele.memoli@unito.it.
Jacopo Garlasco, Email: jacopo.garlasco@unito.it.
Carla M. Zotti, Email: carla.zotti@unito.it
References
- 1.Association Française de Normalisation. Water quality-detection and enumeration of Legionella spp. and Legionella pneumophila. Method by direct inoculation and after concentration by membrane filtration or centrifugation. French standard AFNOR NF T90–431. 2003.
- 2.Centers for Disease Control and Prevention . Legionnaires Disease Procedures Manual for Recovery. 2005. [Google Scholar]
- 3.Cunha BA, Burillo A, Bouza E. Legionnaires’ disease. Lancet. 2016;387:376–385. doi: 10.1016/S0140-6736(15)60078-2. [DOI] [PubMed] [Google Scholar]
- 4.Dennis PJ, Brenner DJ, Thacker WL, et al. Five new Legionella species isolated from water. Int J Syst Evol Microbiol. 1993;43:329–337. doi: 10.1099/00207713-43-2-329. [DOI] [PubMed] [Google Scholar]
- 5.Ditommaso S, Gentile M, Giacomuzzi M, Zotti CM. Recovery of Legionella species from water samples using an internal method based on ISO 11731: suggestions for revision and implementation. Diagn Microbiol Infect Dis. 2011;70:200–206. doi: 10.1016/j.diagmicrobio.2011.01.013. [DOI] [PubMed] [Google Scholar]
- 6.Ditommaso S, Giacomuzzi M, Memoli G, et al. Sensitivity and selectivity of two commercially available Media for Legionella spp. Recovery from Environmental Water Samples. Pathogens. 2020;9. 10.3390/pathogens9070523. [DOI] [PMC free article] [PubMed]
- 7.Doebbeling BN, Ishak MA, Wade BH, et al. Nosocomial Legionella micdadei pneumonia: 10 years experience and a case-control study. J Hosp Infect. 1989;13:289–298. doi: 10.1016/0195-6701(89)90010-8. [DOI] [PubMed] [Google Scholar]
- 8.Edelstein PH. Improved semiselective medium for isolation of Legionella pneumophila from contaminated clinical and environmental specimens. J Clin Microbiol. 1981;14:298–303. doi: 10.1128/JCM.14.3.298-303.1981. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 9.Edelstein PH. Comparative study of selective media for isolation of Legionella pneumophila from potable water. J Clin Microbiol. 1982;16:697–699. doi: 10.1128/JCM.16.4.697-699.1982. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 10.Feeley JC, Gibson RJ, Gorman GW, et al. Charcoal-yeast extract agar: primary isolation medium for Legionella pneumophila. J Clin Microbiol. 1979;10:437–441. doi: 10.1128/JCM.10.4.437-441.1979. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 11.Feeley JC, Gorman GW, Weaver RE, et al. Primary isolation media for legionnaires disease bacterium. J Clin Microbiol. 1978;8:320–325. doi: 10.1128/jcm.8.3.320-325.1978. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 12.Fields BS, Benson RF, Besser RE. Legionella and legionnaires’ disease: 25 years of investigation. Clin Microbiol Rev. 2002;15:506–526. doi: 10.1128/cmr.15.3.506-526.2002. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 13.Gomez-Lus R, Lomba E, Gomez-Lus P, et al. In: In vitro antagonistic activity of Pseudomonas aeruginosa Klebsiella pneumoniae, and Aeromonas spp. against Legionella spp. Barbaree JM, Breiman RF, PDufour A, et al., editors. Washington, DC: Legionella: current status and emerging perspectives Ameri-can Society for Microbiology; 1993. pp. 265–267. [Google Scholar]
- 14.Harris A, Lally M, Albrecht M. Legionella bozemanii pneumonia in three patients with AIDS. Clin Infect Dis. 1998;27:97–99. doi: 10.1086/514618. [DOI] [PubMed] [Google Scholar]
- 15.Health Protection Agency (HPA) Detection and Enumeration of Legionella Species by Filtration and Centrifugation. National Standards Method W 12. Issue 1. 2006. [Google Scholar]
- 16.International Organization for Standardization . ISO 11731: 1998 Water Quality—Enumeration of Legionella. 1998. [Google Scholar]
- 17.International Organization for Standardization . ISO 11731: 2017 Water Quality—Enumeration of Legionella. 2017. [Google Scholar]
- 18.Joly JR, Déry P, Gauvreau L, et al. Legionnaires’ disease caused by Legionella dumoffii in distilled water. CMAJ. 1986;135:1274–1277. [PMC free article] [PubMed] [Google Scholar]
- 19.Kimura S, Tateda K, Ishii Y, et al. Pseudomonas aeruginosa Las quorum sensing autoinducer suppresses growth and biofilm production in Legionella species. Microbiology. 2009;155:1934–1939. doi: 10.1099/mic.0.026641-0. [DOI] [PubMed] [Google Scholar]
- 20.Lindsay DSJ, Brown AW, Brown DJ, et al. Legionella longbeachae serogroup 1 infections linked to potting compost. J Med Microbiol. 2012;61:218–222. doi: 10.1099/jmm.0.035857-0. [DOI] [PubMed] [Google Scholar]
- 21.McDade JE, Shepard CC, Fraser DW, et al. Legionnaires’ disease: isolation of a bacterium and demonstration of its role in other respiratory disease. N Engl J Med. 1977;297:1197–1203. doi: 10.1056/NEJM197712012972202. [DOI] [PubMed] [Google Scholar]
- 22.Mercante JW, Winchell JM. Current and emerging Legionella diagnostics for laboratory and outbreak investigations. Clin Microbiol Rev. 2015;28:95–133. doi: 10.1128/CMR.00029-14. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 23.Ministero della Salute . Linee guida per la prevenzione ed il controllo della legionellosi. 2015. [Google Scholar]
- 24.Miyamoto H, Yamamoto H, Arima K, et al. Development of a new seminested PCR method for detection of Legionella species and its application to surveillance of legionellae in hospital cooling tower water. Appl Environ Microbiol. 1997;63:2489–2494. doi: 10.1128/AEM.63.7.2489-2494.1997. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 25.Murdoch DR, Chambers ST. Detection of Legionella DNA in peripheral leukocytes, serum, and urine from a patient with pneumonia caused by Legionella dumoffii. Clin Infect Dis. 2000;30:382–383. doi: 10.1086/313656. [DOI] [PubMed] [Google Scholar]
- 26.NEN . NEN 6265 (nl): Water - Detection and Enumeration of Legionella. 2007. [Google Scholar]
- 27.Pasculle AW, Feeley JC, Gibson RJ, et al. Pittsburgh pneumonia agent: direct isolation from human lung tissue. J Infect Dis. 1980;141:727–732. doi: 10.1093/infdis/141.6.727. [DOI] [PubMed] [Google Scholar]
- 28.R Development Core Team . A Language and Environment for Statistical Computing. 2019. [Google Scholar]
- 29.Toze S, Sly LI, MacRae IC, Fuerst JA. Inhibition of growth ofLegionella species by heterotrophic plate count bacteria isolated from chlorinated drinking water. Curr Microbiol. 1990;21:139–143. doi: 10.1007/BF02091832. [DOI] [Google Scholar]
- 30.Vickers RM, Brown A, Garrity GM. Dye-containing buffered charcoal-yeast extract medium for differentiation of members of the family Legionellaceae. J Clin Microbiol. 1981;13:380–382. doi: 10.1128/JCM.13.2.380-382.1981. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 31.Vinh DC, Garceau R, Martinez G, et al. Legionella jordanis lower respiratory tract infection: case report and review. J Clin Microbiol. 2007;45:2321–2323. doi: 10.1128/JCM.00314-07. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 32.Wadowsky RM, Yee RB. Glycine-containing selective medium for isolation of Legionellaceae from environmental specimens. Appl Environ Microbiol. 1981;42:768–772. doi: 10.1128/AEM.42.5.768-772.1981. [DOI] [PMC free article] [PubMed] [Google Scholar]
Associated Data
This section collects any data citations, data availability statements, or supplementary materials included in this article.
Supplementary Materials
Data Availability Statement
The dataset used and/or analysed during the current study are available from the corresponding author on reasonable request.